251
Exchanging Data with the CPU Unit
Section 6-5
The input disconnection detection function can be used when the input signal
range is set for 1 to 5 V (4 to 20 mA).
Allocation for Adjustment
Mode
For adjustment mode, set the operation mode switch on the rear panel of the
Unit as shown in the following diagram. When the Unit is set for adjustment
mode, the ADJ indicator on the front panel of the Unit will flash.
The allocation of CIO words and bits is shown in the following table.
Set Values and Stored
Values
Refer to
6-9-1 Adjustment Mode Operational Flow
for further details.
Input signal range
Voltage/current
1 to 5 V
0.3 V max.
4 to 20 mA
1.2 mA max.
I/O
Word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Output
(CPU to
Unit)
n
Not used.
Inputs and outputs to be adjusted
16
1
16
0
n + 1
Not used.
Not used.
Clr
Set
Up
Down
Gain Off-
set
n + 2
Not used.
n + 3
Not used.
n + 4
Not used.
n + 5
Not used.
n + 6
Not used.
n + 7
Not used.
Input
(Unit to
CPU)
n + 8
Conversion value or set value at time of adjustment
16
3
16
2
16
1
16
0
n + 9
Alarm Flags
Disconnection detec-
tion
Not used.
Input
4
Input
3
Input
2
Input
1
Item
Contents
Input or output to be
adjusted
Sets input or output to be adjusted.
Leftmost digit: 1 (output) or 2 (input)
Rightmost digit: 1 to 4
Offset (Offset Bit)
When ON, adjusts offset error.
Gain (Gain Bit)
When ON, adjusts gain error.
Down (Down Bit)
Decrements the adjustment value while ON.
Up (Up Bit)
Increments the adjustment value while ON.
Set (Set Bit)
Sets adjusted value and writes to EEPROM.
Clr (Clear Bit)
Clears adjusted value. (Returns to default status)
Conversion value for
adjustment
The conversion value for adjustment is stored as 16 bits
of binary data.
Содержание CJ1W-AD041-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 99: ...76 Handling Errors and Alarms Section 2 8...
Страница 191: ...168 Handling Errors and Alarms Section 4 8...
Страница 243: ...220 Handling Errors and Alarms Section 5 8...
Страница 381: ...358 Handling Errors and Alarms Section 7 10...
Страница 385: ...362 Dimensions Appendix A...
Страница 395: ...372 Sample Programs Appendix B...
Страница 396: ...373 Appendix C Data Memory Coding Sheets...
Страница 417: ...394 Data Memory Coding Sheets Appendix C...
Страница 425: ......