177
Interrupt Tasks
Section 4-3
Interrupt Task with Maximum Processing Time (A441)
The interrupt task number with maximum processing time is stored in binary
data. Here, 8000 to 80FF Hex correspond to task numbers 00 to FF Hex.
A44115 will turn ON when the first interrupt occurs after the start of operation.
The maximum processing time for subsequent interrupt tasks will be stored in
the rightmost two digits in hexadecimal and will be cleared at the start of oper-
ation.
Interrupt Task Error Flag (Nonfatal Error) (A40213)
If Interrupt Task Error Detection is turned ON in the PLC Setup, the Interrupt
Task Error Flag will turn ON if an interrupt task error occurs.
Interrupt Task Error Flag (A42615)/Task Number Generating the Interrupt
Task Error (A42600 to 42611)
If A40213 turns ON, then the following data will be stored in A42615 and
A42600 to A42611.
Task Number when
Program Stopped (A294)
The type of task and the current task number when a program stops due to a
program error will be stored in the following locations.
4-3-4
Application Precautions
Long Execution Times
with C200H Special I/O
Units or SYSMAC BUS (CS
Series Only)
Be sure all interrupt tasks (I/O, scheduled, power OFF, and external interrupt
tasks) execute within 10 ms when using C200H Special I/O Units or SYSMAC
BUS Remote I/O.
If an interrupt task executes for more than 10 ms during C200H Special I/O
Unit or SYSMAC BUS remote I/O refreshing, an interrupt task error will occur,
A40206 (Special I/O Unit Error Flag) will turn ON, and I/O refreshing will be
stopped for Special I/O Units. The CPU Unit, however, will continue to oper-
ate.
If Interrupt Task Error Detection is turned ON in the PLC Setup, A40213 (Inter-
rupt Task Error Flag) will turn ON when an interrupt task error occurs, and the
A40213
Interrupt Task Error Description
A42615
A42600 to 42611
Interrupt Task Error (If Interrupt
Task Error Detection is turned ON
in the PLC Setup)
If an interrupt task executes for
more than 10 ms during C200H
Special I/O Unit or SYSMAC BUS
Remote I/O refresh
(CS Series
only).
OFF
The interrupt task number will be
stored in 12 bits of binary data
(interrupt task 0 to 255: 000 to
OFF Hex).
When trying to refresh I/O for a
large number of words using the
IORF instruction from an interrupt
task while an Special I/O Unit is
being refreshed by cyclic I/O
refreshing.
ON
The unit number of the Special I/O
Unit being refreshed will be stored
in 12 bits of binary data (unit No. 0
to 95: 000 to 05F Hex).
Type
A294
Interrupt task
8000 to 80FF Hex (corresponds to inter-
rupt task No. 0 to 255)
Cyclic task
0000 to 001F Hex (corresponds to task
No. 0 to 31)
Содержание CJ1G-CPU series
Страница 3: ...iv...
Страница 5: ...vi...
Страница 21: ...xxii Conformance to EC Directives 6...
Страница 169: ...148 Task Control Instructions Section 3 32...
Страница 203: ...182 Programming Device Operations for Tasks Section 4 4...
Страница 253: ...232 Using File Memory Section 5 3...
Страница 337: ...316 Other Functions Section 6 11...
Страница 347: ......
Страница 369: ......
Страница 373: ......
Страница 379: ......
Страница 381: ...360 Revision History...
Страница 383: ...Authorized Distributor Cat No W394 E1 03 Note Specifications subject to change without notice Printed in Japan...