13
5.
Converting the program for CS1
On the CX-Programmer, convert the program for CS1.
(1) Start the CX-Programmer and open the saved program file for C200HS. (Select
Open
from the File Menu.)
(2) Change the Device Type from C200HS to CS1.
(Select
Change Model
from the PLC Menu to display the
below dialog box.)
(3) The instructions are automatically converted. The Output Window shows the conversion results. Double-click
an error shown on the Output Window to jump to the corresponding section of the ladder program.
Some instructions cannot be converted. Modify the ladder program referring to
Appendix A. Instructions
converted by Change Model on CX-Programmer.
You can check the program by selecting
Compile
from the Program Menu. The Output Window shows the
checking results.
Errors and warnings at conversion will be displayed.
Double-click an error or a warning to jump to the corresponding circuit.