4.
Installation
5 www.sinetech.co.za
4. Installation
4-1. Selecting Mounting Location
Consider the following points before selecting where to install:
Do not mount the inverter onto flammable materials.
Mount on a solid surface
This inverter can emit noise during operation which may be perceived as a nuisance in
a living area.
Install the inverter at eye level to allow easy reading of the LCD display.
For proper air circulation to dissipate heat, allow a clearance of ± 20 cm to the sides
and ± 50 cm above and below the unit.
Dusty conditions will impair the performance of this inverter.
The ambient temperature should be between 0
°
C and 40
°
C and relative humidity
should be between 5% and 85% to ensure optimal operation.
A vertical installation position is to be adhered to.
For proper operation of this inverter, please use appropriate cables for grid
connection.
The pollution degree of the inverter is PD2. Select an appropriate mounting location.
Install the solar inverter in a protected area that is dry, free of excessive dust and has
adequate air flow. Do NOT operate it where the temperature and humidity is beyond
the specification limits. (Please check the specs for the limitations.)
Installation position shall not impede access to all the connections.
This inverter has an IP20 rating: for indoor applications only.
Regularly clean the fan filter.
4-2. Mounting Unit
WARNING!!
This inverter is heavy! Please be careful when lifting!
Installation to the wall should be implemented with the proper bolts. The device should be
bolted on securely.
The inverter only can be used in an ENCLOSED ELECTRICAL OPERATING AREA.
WARNING!!
FIRE HAZARD.
TO BE MOUNTED ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACES ONLY.