background image

AWAG Elektrotechnik AG   Sandbüelstrasse 2   CH-8604 Volketswil 

3110000.docx / 1876012 

Tel. +41 44 908 19 19  Fax +41 44 908 19 99  [email protected]  www.awag.ch 

SW: UPS_V181107 / 31.11.2018 Seite 1 / 7 

UPS230/10 

Bedienungsanleitung  

Manual 

UP-Multi-Schaltaktor 

Flush mounted multi 

1-Kanal 

switching actuator, 1-channel 

 

Bezeichnung 

Typ / Type 

Art.-No./Item N° 

Designation 

UP-Multi-Schaltaktor 1-Kanal mit Nebenstelleneingang 
Schliesskontakt 8 A potentialfrei, Versorgungsspannung 230 V~ 

UPS230/10

 

3110 000

 

Flush mounted multi switching actuator 1-channel with extension 
input, closing contact 8 A potential free, supply voltage 230 V~ 

KURZ AN LE I TUNG  

  Schaltaktor gemäss Schema anschliessen 

  Drehschalter HEX auf 0 stellen 

  LRN 2 Sekunden drücken 

  Hand- oder Wandsender in der Nähe des Schaltaktors 

zweimal betätigen. CLR leuchtet während einer 
Sekunde, danach ist der Sender eingelernt 

  Weitere Sender einlernen 

  Zum Beenden CLR drücken 

 

FUNK TI ONE N  

  Ein- und Ausschalten 

  Treppenlichtfunktion 

  Tastenfolger 

  Schrittschalter (AW20) 

  Minuterie (AW23/24/25) 

  Fenster- und Schiebetürüberwachung 

  Programmierbarer Nebenstelleneingang 

  Programmierbare Szenen 

  Anwesenheitssimulation 

  Repeaterfunktion 

  EnOcean Equipment Profile (EEP) D2-01-01 

 

ARCO fähig (AWAG Remote Commissioning) 

 

BRI E F  I NS TR UC TI ON    

  Attach switching actuator according to schematic 

  Turn the rotary switch HEX to 0 

  Press LRN 2 seconds 

  Press handheld or wall mounted transmitter twice 

while keeping it close to the actuator. CLR lights up for 
a second, after that the transmitter is programmed  

  Program further transmitters 

  To finish press CLR 

 

FUNC TI ONS  

  Switch On and Off 

  Staircase light function 

  Sequential push-button 

  Step switch (AW20) 

  Timer (AW23/24/25) 

  Window and sliding door surveillance 

  Programmable extension input 

  Programmable scenes 

  Presence simulation 

  Repeater function  

  EnOcean Equipment Profile (EEP) D2-01-01 

 

ARCO ready (AWAG Remote Commissioning) 

AL LGE M E I N  

Die Omnio Aktoren (Empfänger) werden über Funksignale der Omnio Sender  an-
gesteuert. Jeder Sender kann eine unbegrenzte Anzahl von Aktoren ansteuern. Die 
Funksender werden manuell durch ein einfaches Verfahren auf den Aktor ein- und 
ausgelernt. Jedem Sender können am Aktor eine Funktion und verschiedenste Pa-
rameter zugeordnet werden. 
 
Mit ARCO-Technologie lassen sich alle Omnio Aktoren vollständig und ohne ma-
nuellen Zugriff zum Gerät per Funk konfigurieren. Die leistungsstarke Software  
E-Tool  bildet  dabei  das  Herzstück,  um  Projekte  beliebiger  Grösse  bequem  am 
Schreibtisch zu planen, konfigurieren und dokumentieren. 
 

P RODUK TBE S CHRE I B UNG  

Der  Omnio  UP-Multi-Schaltaktor  1-Kanal  UPS230/10  ist  ein  Gerät  zum  Schalten 
von  elektrischen  Verbrauchern.  Sein  potentialfreier  Ausgang  kann  von  bis  zu  50 
Omnio  Funksendern  angesteuert  werden.  Jedem  dieser  Sender  kann  auf  dem 
Schaltaktor  eine  von  über  zwanzig  Funktionen  zugeordnet  werden  wie  z.B.  Ein-
schalten, Ausschalten, Treppenlicht, Tastenfolger, Schrittschalter (AW20), Minute-
rie (AW23/24/25), Fenster- und Schiebetürüberwachung, programmierbare Szenen 
und Anwesenheitssimulation. Diese Funktionen kann man auch einem am Neben-
stelleneingang  angeschlossenen  konventionellen  Taster  oder  Schalter  zuweisen. 
Bidirektionale Kommunikation, EEP D2-01-01, ARCO fähig (AWAG Remote Com-
missioning). Zusätzlich kann bei Reichweitenproblemen die eingebaute Repeater-
funktion aktiviert werden. Geeignet für die Unter- oder Aufputzmontage in Kuststoff-
dosen. 
 

GE NE R AL  

The  Omnio  actuators  (receivers)  are  controlled  by  radio  signals  coming  from  the 
Omnio transmitters. Each transmitter is able to control an unlimited number of ac-
tuators. The radio transmitter can be manually programmed and deprogrammed to 
an actuator following a simple procedure. Via actuator each transmitter can be given 
a certain function and different parameters.  
 
With ARCO technology, all Omnio actuators can be configured completely by radio 
without manual access to the device. The powerful software E-Tool constitutes the 
key component for convenient  planning, configuring  and documenting projects of 
any size right at your desk. 
 

P RODUC T  D E S CRI P TI O N   

The Omnio flush mounted multi switching actuator 1-channel UPS230/10 is a de-
vice for switching electrical loads. Its potential free output is able to be controlled by 
up to 50 Omnio radio transmitters. Each transmitter can be programmed with one 
of over twenty different functions, for example switch on, switch off, staircase light, 
sequential push-button, step-switch (AW20), timer (AW23/24/25), window and slid-
ing door surveillance, programmable scenes and presence simulation. These func-
tions can also be assigned to a conventional push-button or a switch connected to 
the  extension  input.  Bidirectional  communication,  EEP  D2-01-01.  ARCO  ready 
(AWAG Remote Commissioning). In addition, this actuator can be used as repeater 
in case of range issues. Suitable for flush mounted sockets. 
 

AN ZE I GE -  UN D  BE DI E NE LE M E NTE  

 
Klemmen 

  L 

Netzspannung L 110 - 240 V~ 

  N 

Netzspannung N 110 - 240 V~ 

  T 

Nebenstelleneingang 

  1 

Relaiskontakt (COM) 

  2 

Relaiskontakt (NO) 

 

 
Bedienelemente 

  CLR 

Taste und LED Clear 

  LRN 

Taste und LED Learn 

  HEX 

Drehschalter 0..15 

DI S P L AY  AN D  OP E R ATI N G  E LEM E NTS  

 
Terminals  

  L 

line voltage L 110 - 240 V~ 

  N 

line voltage N 110 - 240V~ 

  T 

extension input 

  1 

relay contact (COM) 

  2 

relay contact (NO) 

 

 
Operating eleme

nts 

  CLR 

button and LED clear 

  LRN 

button and LED learn 

  HEX 

rotary switch 0..15 

 

 

 

 

EnOcean-Technologie (868 MHz) 

Содержание UPS230/10

Страница 1: ...al UPS230 10 ist ein Ger t zum Schalten von elektrischen Verbrauchern Sein potentialfreier Ausgang kann von bis zu 50 Omnio Funksendern angesteuert werden Jedem dieser Sender kann auf dem Schaltaktor...

Страница 2: ...Tabelle 4 GER TEPARAMETER zu finden 1 Ger teparameter w hlen 2 Drehschalter gem ss Tabelle 4 Spalte 1 einstellen 3 Einlernmodus durch einen langen Tastendruck 2 s auf aktivieren LRN leuchtet und CLR...

Страница 3: ...schalten Einschalten mit einstellbarer Verz gerung siehe Tabelle 3 Ein schaltverz gerung S01 S04 0 2 Taste 2x dr cken press push button 2x S02 Switch on Switch on with adjustable time delay see Table...

Страница 4: ...en Taste I Fernzugriff sperren 2 3 Wippe 2x dr cken press rocker 2x X10 Unlock ARCO Button O Unlock remote access Button I Lock remote access Beispiele Examples S01 Schalten mit Wippe 0 LRN 2 s Wippe...

Страница 5: ...cond steps 1 15 Min in 1 Minuten Schritten 3 1 15 1 15 min in 1 minute steps 4 60 Min in 4 Minuten Schritten 4 1 15 4 60 min in 4 minute steps 15 225 Min in 15 Minuten Schritten 5 1 15 15 225 min in 1...

Страница 6: ...a radius of 5 meters Aus 15 2 s dr cken press 2 s 0 dr cken press Off Level 1 Verst rkt nur Originaltelegramme 1 Level 1 Amplifies original radio telegrams Level 2 Verst rkt Originaltelegramme und ber...

Страница 7: ...FICATIONS Spannungsversorgung 110 240 V 50 60 Hz Voltage supply Standby Verbrauch 0 6 W Standby power consumption Absicherung des Ger tes Sicherung automat 13 A Hardware protection automatic circuit b...

Отзывы: