IM-817-00 

10-JUL-2020 

TrueGuard

 Pro on Kohler DEC800/ComAp IS-NTC-BB 

Installation Guide 

 

1.  Unpack the monitor, antenna and the data / power cable. Take a 

moment to inspect all components to verify there is no shipping 
damage. 

2.  Place the antenna vertically on the roof of the generator and route 

the antenna cable into the area of the generator control. The 
antenna used for transmitting must be installed to provide a 
separation distance of at least 20 cm from all persons and must not 
transmit simultaneously with any other antenna transmitters. BE 
SURE to provide a 

drip loop

 lower than the monitor to keep water 

from running down the antenna cable into the monitor connection. 

3.  Attach the monitor via its magnetic feet, on top of the engine 

controller or other appropriate location. Horizontal surfaces are 
best, but the unit may be mounted vertically or even upside down if 
necessary. 

Note: If mounted vertically, install the monitor with the 

cables down to prevent water from entering the enclosure.

 

4.  Route the data/power cable through the cable entry on the bottom of 

the generator control. 

5.  The monitor connects to the ComAp interface module by either a 

provided, DB9 (RS-232) cable, as standard, or RS-485 connection, 
which is available through the optional 25-Pin cable #100120 (Green & 
White wires).  Either cable provided comes with Red (B) and 
Black (Battery -) wires for 12vdc or 24vdc power input connection to 
the monitor. 

a.  For RS-485 cable runs greater than 50 feet, install the provided 

120 Ohm resistor 

across the RS485+ and RS485- terminals at 

the device farthest from the OmniMetrix monitor.

  

6.  Attach the antenna cable to the front of the monitor and tighten thumb 

tight.  

7.  Turn on the monitor and confirm that the LEDs light up and blink.  If not, 

check for power on the terminal strip. If, after 5 minutes, the only  
LED lit is the Power LED, check the antenna mount and cable 
connection. 

8.  Allow 15 minutes for the monitor to log into the network and then call 

OmniMetrix at 770-209-0012 to confirm installation. Access to machine 
data is through the OmniView

®

 web interface at 

www.omnimetrix.net

Contact OmniMetrix for login instructions and web training. 

 

 

 

 

 

 

 

RS-232 Data / Power Cable 

 

Optional, 25-Pin Data (RS-485) 
& Power cable with Remote 
Start wires. 

For technical assistance, please call Tech Support at 770-209-0012 or email 

[email protected]

  