background image

 

 

 

 

 

CAT EMCP 4 

Installation Guide 

1.  Unpack the monitor, antenna and the data/power cable. The 25 pin 

connector plugs onto the front of the OmniMetrix

®

 Monitor. This cable 

includes wires to power the monitor as well as wires for alarm inputs, 
relay outputs and analog inputs. Take a moment to inspect all 
components to verify there is no shipping damage. 

2.  Place the antenna on the roof of the generator and route the antenna 

cable into the area of the generator control. The antenna used for 
transmitting must be installed to provide a separation distance of at 
least 20 cm from all persons and must not transmit simultaneously 
with any other antenna transmitters. BE SURE to provide a drip loop 
lower than the monitor to keep water from running down the antenna 
cable into the monitor connection.   

3.  Attach the monitor via its magnetic feet, on top of the engine 

controller or other appropriate location. Horizontal surfaces are 
best, but the unit may be mounted vertically or even upside down if 
necessary.

 Note: If mounted vertically, install the monitor with the 

cables down to prevent water from entering the enclosure.

 

4.  Route the data/power cable to the terminal strip to pick up 

generator battery power and RS485 data. 

5.  The monitor connects to the Caterpillar EMCP 4 through a 4-wire 

connection.  Connect the RED wire to generator Battery B+, the 
BLACK wire to generator Battery B- (GND), the WHITE wire to 
Modbus Data+ and the GREEN wire to Modbus Data-. For remote 
start capability, connect the WHITE/YELLOW wire and the 
WHITE/BROWN wire to the Generator 2-wire Start Terminal. 

6.  Attach the antenna cable to the front of the monitor, and tighten 

thumb tight. 

7.  Set up Modbus via the front panel control, using the steps provided 

on the following page. Be sure to utilize a baud rate of 9600, 8 
bits, no parity, and 1 stop bit. 

8.  Turn on the monitor and confirm that the LEDs light up and blink.  

If not, check for power on the terminal strip. If, after 5 minutes, the 
only LED lit is the Power LED, check the antenna mount and cable 
connection. 

9.  Allow 15 minutes for the monitor to log into the network and then 

call OmniMetrix at 770-209-0012 to confirm installation. Access to 
machine data is through the OmniView

®

 web interface at 

www.omnimetrix.net

. Contact OmniMetrix for login instructions 

and web training.