OMNI 4000/7000 Operations and Maintenance Guide
– Rev F
3-30
OMNICONNECT® Operations
3.5.4 Auto Prove Setup
The Auto Prove function is not available for Master Meter proving.
The Auto Prove function selects the criteria for the flow computer to automatically execute a
prove sequence, such as sustained changes in flow rates. A prove sequence may be executed
after a certain amount of flow since the last prove sequence or after a set amount of flow has
occurred after flow meter startup.
To configure the Auto Prove function, follow these instructions:
1.
In the Actions ribbon, click
Configure
.
2.
a. Expand the
Prover
function in the
Configure
tree.
b. Select
Configuration and Setup
to
display the
Prover
configuration
options in the screens on the right.
3.
a. Select the
Auto Prove Setup
tab.
b. Enter the necessary values to
configure
Startup
time and flow,
Flow
Rate Change between Proves
, and
Maximum Flow between Proves
.
c. Click
Apply
to save your changes.
3.5.5 Manual Prove Request
You can access the prover in OMNICONNECT and manually request a prove at any time while
OMNICONNECT is online with the flow computer.
To manually request a prove, follow these instructions:
1.
In the Actions ribbon, click
Operate
.