DFS2 Doppler Flow Switch 

   

 

 

 

 

 

 

 

Mounting The Transducer 

 

a) 

Select a location for mounting the sensor at a point where the flow profile is fully 
developed.  Generally the principle of 10 pipe diameters of straight pipe upstream, 
and 5 pipe diameters downstream will suffice, but should valves or bends exist 
upstream of the sensor, the amount of straight pipe immediately upstream will need 
to be increased. 

 
b) 

Ensure that the sensor is mounted as far as 
possible from potential noise sources, such as 
pumps, control valves etc. and mount the 
sensor at approximately 3/9 o’clock on the pipe 
(if horizontal) to avoid errors due to air pockets 
on top, or sediment at the bottom of the pipe. 
 

c) 

Either vertical or horizontal pipe runs are acceptable for sensor mounting. 
 

d) 

Before attaching the transducer head to the pipe surface, an area slightly larger than 
the flat surface of the transducer must be cleaned to bare metal.  (A small amount of 
pipe pitting, even with spots of paint or rust, will not cause problems). 
 

e) 

The transducer must be mounted accurately, parallel to the pipe axis, for correct 
performance, and transducer to pipe contact should be along the centre line of the 
transducer head. 
 
  

f) 

Bonding to the pipe is achieved with silicone 
coupling compound.  Be sure to fill in any air 
gaps that may remain at the pipe transducer 
interface with additional compound. 
 
A pipe clamp kit is included with the flow switch.  
It includes silicone coupling compound, a 
Neoprene rubber pad, and four polyamide 12 
straps for pipe diameters up to 300 mm. In 
applications with excessive vibration it is 
recommended that the Neoprene rubber pad is 
inserted between the pipe and the transducer.  
Coupling compound must be applied to both 
sides of the pad. 

 

Mounting the Switch 

 

The DFS2 electronics is housed in a water resistant housing, which should be 
mounted in a location where the ambient temperature is within the range stated in 
the specifications i.e. -10

°

C to 50

°

C.

 

3 O’CLOCK POSITION ON PIPE 
IF HORIZONTAL 

 

GOOD 

Содержание DFS2

Страница 1: ...ice Tel 44 0 845 9000 601 Fax 44 0 845 9000 602 info omniinstruments co uk www omniinstruments co uk Australia Asia Pacific Office Tel 61 0 282 442 363 Fax 61 0 294 751 278 info omniinstruments com au...

Страница 2: ...ay on and delay off adjustable timers The DFS2 requires 24Vdc 115 or 230Vac power supply Two selectable flow ranges of 0 2 m s or 0 6 m s are available and the flow rate is displayed on a bar graph in...

Страница 3: ...rate with or without latch Latch Selection JP2 Position 1 ON latch reset Relay energised in normal conditions i e between high and low limits giving a failsafe mode In alarm condition the relay will d...

Страница 4: ...1 to Hi position and adjust high trip potentiometer to display the required alarm setting NB Return slide switch to centre position for normal operation Delay Off Timer T1 Under normal operating condi...

Страница 5: ...must be cleaned to bare metal A small amount of pipe pitting even with spots of paint or rust will not cause problems e The transducer must be mounted accurately parallel to the pipe axis for correct...

Страница 6: ...ting Relay Does Not Operate Possible Cause High trip point set below low trip point Unit faulty Corrective Action Adjust high trip point above low trip point Return unit to factory Signal Strength LED...

Страница 7: ...1 Relay 1Amp SPDT Transducer Cable 3 metre length Temperature Sensor 20 to 90 C Electronics 10 to 50 C Electronics IP65 Polycarbonate Enclosure 120 x 120 x 55mm Power Input 115 230V ac 50Hz 24V dc 10...

Отзывы: