1.3.2
Grounding
Operating the device without PE and ground connection is life-threatening and not permitted.
► Only operate the
CPC
with a mains power supply connected to protective earth (PE).
► Make sure that both the PE connection of the power supply and the ground connector of the
CPC
have a solid and low-impedance connection to the grounding system on site.
This also applies to all other test devices and accessories in the test setup.
► Make sure that the grounding clamp has a good electrical contact to the grounding system on site
and avoid connecting it to corroded or painted surfaces.
► Make sure that the grounding terminal connections of all grounded devices in use remain intact
during the whole measurement procedure, and are not accidentally disconnected.
► Only use ground and supply cables provided by OMICRON.
Connect the
CPC
grounding terminal to the grounding system on site.