12.11 Temperature Correction Factors
The temperature curves can be used in the
TanDelta
test card (see
3.4 ”TanDelta Test Card - Settings Page (2/2)” on page 30).
where
PF(DF)
20
is the corrected Power Factor (Dissipation Factor) to 20 °C
PF(DF)
T
is the Power Factor (Dissipation Factor) measured at T
k is the correction factor
12.11.1 Transformers
PF DF
(
)
20
PF DF
(
)
T
k
×
=
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0
10
20
30
40
50
60
70
D
F
Co
rr
ec
tion
F
a
cto
r k
Temperature in °C
IEEE Std. C57.12.90