CMC 850
is a test set designated to evaluate, test and commission IEDs (
I
ntelligent
E
lectronic
D
evices) in laboratories or substations that utilize GOOSE and Sampled Values according to
IEC 61850.
Any other use of
CMC 850
is considered improper and may result in damage to property or persons.
4 Functionality
CMC 850
is part of OMICRON
Test Universe
system which, in addition to the physical test set,
consists of a test software for a computer with a Windows
operating system, and, if applicable,
external voltage and/or current amplifiers
1
, PTP, IRIG-B or GPS
1
time synchronization units or other
accessories.
4.1 Interfaces to the Test Environment
To interface with the test environment,
CMC 850
provides two different functionalities.
The main focus is put onto IEC 61850 by employing Ethernet communication.
Additionally,
CMC 850
provides low level outputs to either directly send low level signals to the device
under test, or to control external amplifiers.
For detailed information → “Connections and Interfaces” on page 10.
4.2 Operating CMC 850 with a controlling test software
Test Universe
As long as the interaction with devices under test utilizes GOOSE and Sampled Values, the
CMC 850
test set supports all test modules of the
Test Universe
software. Test plans utilizing GOOSE and
Sampled Values, initially made for the test sets
CMC 256plus
or
CMC 356,
can also be used with
CMC 850
.
An example
Control Center
(OCC) document that illustrates how to configure the Sampled Values and
GOOSE features for
CMC 850
is provided in the Test Library that is installed with the OMICRON
Test Universe
. The OCC document’s name is
CMC 850 Example.occ
, and it is stored at
...OTU installation path
\Test Library\Samples\General Examples
.
RelaySimTest
The
CMC 850
test set can also be operated by the
RelaySimTest
software. For this, we strongls
recommend a
NET-2
interface board to be installed in the test set (→ 5.2.1 "ETH1 and ETH2 Ports").
With a
NET-2
board, a
CMC 850
test set can work with up to 4 Sampled Values streams and GOOSEs
simultaneously via both ETH ports.
1.
External voltage/current amplifiers and the
CMGPS
Synchronization Unit are not part of the standard scope of delivery. The
CMGPS
Synchronization Unit is a meanwhile discontinued product. For questions about its successor
CMGPS 588
contact the OMICRON
Technical Support or visit our website.