background image

8

CMC 850 User Manual

3 Designated Use

CMC 850

 is a test set designated to evaluate, test and commission IEDs (

I

ntelligent 

E

lectronic 

D

evices) in laboratories or substations that utilize GOOSE and Sampled Values according to 

IEC 61850.

Any other use of 

CMC 850

 is considered improper and may result in damage to property or persons.

4 Functionality

CMC 850

 is part of OMICRON 

Test Universe

 system which, in addition to the physical test set, 

consists of a test software for a computer with a Windows

 

operating system, and, if applicable, 

external voltage and/or current amplifiers

1

, PTP, IRIG-B or GPS

1

 time synchronization units or other 

accessories.

4.1 Interfaces to the Test Environment

To interface with the test environment, 

CMC 850

 provides two different functionalities. 

The main focus is put onto IEC 61850 by employing Ethernet communication.

Additionally, 

CMC 850

 provides low level outputs to either directly send low level signals to the device 

under test, or to control external amplifiers.

For detailed information → “Connections and Interfaces” on page 10.

4.2 Operating CMC 850 with a controlling test software

Test Universe

As long as the interaction with devices under test utilizes GOOSE and Sampled Values, the 

CMC 850 

test set supports all test modules of the 

Test Universe

 software. Test plans utilizing GOOSE and 

Sampled Values, initially made for the test sets 

CMC 256plus

 or 

CMC 356, 

can also be used with 

CMC 850

.

An example 

Control Center

 (OCC) document that illustrates how to configure the Sampled Values and 

GOOSE features for 

CMC 850

 is provided in the Test Library that is installed with the OMICRON 

Test Universe

. The OCC document’s name is 

CMC 850 Example.occ

, and it is stored at 

...OTU installation path

\Test Library\Samples\General Examples

.

RelaySimTest

The 

CMC 850 

test set can also be operated by the 

RelaySimTest

 software. For this, we strongls 

recommend a 

NET-2

 interface board to be installed in the test set (→ 5.2.1 "ETH1 and ETH2 Ports").

With a 

NET-2

 board, a 

CMC 850

 test set can work with up to 4 Sampled Values streams and GOOSEs 

simultaneously via both ETH ports.

1.

External voltage/current amplifiers and the 

CMGPS

 Synchronization Unit are not part of the standard scope of delivery. The

 CMGPS

 

Synchronization Unit is a meanwhile discontinued product. For questions about its successor 

CMGPS 588

 contact the OMICRON 

Technical Support or visit our website.

Содержание CMC 850

Страница 1: ...CMC 850 User Manual...

Страница 2: ...is not permitted The product information specifications and technical data embodied in this manual represent the technical status at the time of writing Subject to change without notice OMICRON elect...

Страница 3: ...esignated Use 8 4 Functionality 8 4 1 Interfaces to the Test Environment 8 4 2 Operating CMC 850 with a controlling test software 8 4 3 Time Synchronization 9 4 4 Web Interface 9 5 Connections and Int...

Страница 4: ...w Level Outputs LL out 1 6 and LL out 7 12 18 7 3 Low Level Binary Outputs ext Interf 19 7 4 Technical Data of the Communication Ports 20 7 4 1 The NET 2 Board 20 7 4 2 The NET 1C Board 21 7 4 3 The N...

Страница 5: ...instructions Only operate or even turn on CMC 850 after you have read this manual and fully understood the instructions herein CMC 850 may only be operated by trained personnel Any maloperation can re...

Страница 6: ...eed free and quick access Before connecting and disconnecting test objects verify that all outputs have been turned off Never connect or disconnect a test object while the outputs are active When disc...

Страница 7: ...a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Changes or modifications not expressly approved by the...

Страница 8: ...ontrolling test software Test Universe As long as the interaction with devices under test utilizes GOOSE and Sampled Values the CMC 850 test set supports all test modules of the Test Universe software...

Страница 9: ...ting with CMC test sets and the Test Universe software It serves as the clearing house for IRIG B and PPS signals regardless whether they come from an external clock or from the CMC itself CMIRIG B fa...

Страница 10: ...s enables direct remote control of CMC 850 e g for end to end testing The Ethernet ports also provide the basis for the processing of substation protocols according to the IEC 61850 standard They allo...

Страница 11: ...he network This may lead to dangerous situations where a user accidentally connects to a device located on a desk of somebody else emitting unsafe voltages and endangering the person working there To...

Страница 12: ...aiting for an emergency software image download This is the case when pressing the button while powering up the CMC test set B green LED If the yellow LED A is off the green LED B signals the followin...

Страница 13: ...n Protocol and AutoIP APIPA Automatic Private IP Addressing If the IP settings conflict with IP settings of other devices in the network it is possible to reset the test set to factory defaults DHCP a...

Страница 14: ...e the OMICRON supplied CMIRIG B interface unit as reference for the a time synchronization of the IEC 61850 bus system connect the CMIRIG B s front side connector CMC to the CMC 850 s external Interfa...

Страница 15: ...cal data Low Level Outputs LL out 1 6 and LL out 7 12 on page 18 Overload Warning in the Test Software When a low level output is overloaded the test software issues an appropriate warning Refer to th...

Страница 16: ...1 Install the test software on your computer The test software can either be the Test Universe or the RelaySimTest software Both software packages also install the OMICRON Device Link Use OMICRON Devi...

Страница 17: ...ccessible via its Web Interface Any common Web browser can be used to access CMC 850 and to make use of the embedded functions Alternative method to invoking the Web browser by the procedures describe...

Страница 18: ...connector Standard DC barrel jack 2 1 mm x 5 5 mm x 11 mm center pin is positive Output voltage 10 V 10 V Max output current 1 mA Accuracy Typical error 0 025 guaranteed 0 07 at 1 V 10 V Resolution 2...

Страница 19: ...pull up resistor Switching voltage Max 15 V Max input voltage 16 V Switch current Max 5 mA current limited min 100 A Actualization time 100 s Rise time 3 s Vextern 5 V Rpullup 4 7 k Insulation Reinfor...

Страница 20: ...Mbit s USB 1 1 compatible USB connector USB type B connect to computer USB cable USB 2 0 high speed type A B 2 m 6 ft ETH type 10 100 1000Base TX1 twisted pair auto MDI MDIX or auto crossover 1 10Bas...

Страница 21: ...ablished port active green LED ON Traffic via ETH port yellow LED is blinking ETH Power over Ethernet PoE IEEE 802 3af compliant Port capability limited to one Class 1 3 84 W and one Class 2 6 49 W po...

Страница 22: ...ransformers Using IEC 61850 9 2LE of the UCA International Users Group and to the IEC 61869 9 2016 Instrument transformers Part 9 Digital interface for instrument transformers with fixed DataSets Samp...

Страница 23: ...E 37 238 2011 Power Profile IEC PAS 61850 9 3 Communication Networks and Systems for Power Utility Automation Part 9 3 Precision Time Protocol Profile for Power Utility Automation Utility Profile Typi...

Страница 24: ...EU and the low voltage Directive 2014 35 EU Electromagnetic Compatibility EMC Emission Europe International USA EN 61326 1 EN 61000 6 4 EN 61000 3 2 3 IEC 61326 1 IEC 61000 6 4 IEC 61000 3 2 3 FCC Sub...

Страница 25: ...ICRON Open Source Download Area at www omicronenergy com opensource Open this address in your Internet browser click the Download Software button and navigate to the CMC Embedded Image directory Look...

Страница 26: ...26 CMC 850 User Manual...

Страница 27: ...a 43 59495 4444 Additionally you can find our Service Center or Sales Partner closest to you at www omicronenergy com Customer Portal Stay Informed www omicronenergy com customer The Customer Portal o...

Страница 28: ...OSE technical data 22 GPS time synchronization 8 I IP address of CMC 850 17 IP configuration 13 IP parameters 13 IRIG B time synchronization 8 L LED A B Status LED 12 LL out low level outputs 15 techn...

Страница 29: ...tware 8 communication with CMC 850 13 time synchronization technical data 23 time synchronization with IRIG B 14 U USB Port 11 USB port on NET 1C board technical data 20 21 on NET 2 board technical da...

Страница 30: ...CMC 850 User Manual 30...

Страница 31: ...ENU 1015 05 03...

Отзывы: