background image

 CMC 356 Reference Manual

8

S

AFETY

 I

NSTRUCTIONS

Before operating the 

CMC 356

 test set, carefully read the following 

safety instructions.

Only operate (or even turn on) the 

CMC 356

 after you have read this 

reference manual and fully understood the instructions herein.

The 

CMC 356

 may only be operated by trained personnel. Any 

maloperation can result in damage to property or persons.

Rules for Use

• The 

CMC 356

 should only be used when in a technically sound 

condition. Its use should be in accordance with the safety regulations for 
the specific job site and application. Always be aware of the dangers of 
the high voltages and currents associated with this equipment. Pay 
attention to the information provided in the reference manual and the 
software documentation.

• The 

CMC 356

 is exclusively intended for the application areas specified 

in section 1, "Designated Use" on page 11. The manufacturer/ 
distributors are not liable for damage resulting from unintended usage. 
The user alone assumes all responsibility and risk.

• The instructions provided in this reference manual and the associated 

software manuals are considered part of the rules governing proper 
usage.

• Do not open the 

CMC 356

 or remove any of its housing components.

Orderly Practices and Procedures

• The reference manual (or its "electronic PDF pendant", which is installed 

to your computer with the OMICRON Test Universe software) should 
always be available on site where the 

CMC 356

 is used.

Note:

 The OMICRON 

Test Universe

 software also installs a PDF version 

of this reference manual. It can directly be opened by a mouse-click from 
the help topic "User Manuals of OMICRON Test Universe". The 

Test Universe

 Help can be launched by clicking 

Help

 on the 

Start Page

.

• Personnel assigned to using the 

CMC 356

 must have read this reference 

manual and fully understood the instructions herein.

• Do not carry out any modifications, extensions or adaptations at the 

CMC 356

.

Содержание CMC 356

Страница 1: ...CMC 356 User Manual...

Страница 2: ...this manual represent the technical status at the time of writing and are subject to change without prior notice We have done our best to ensure that the information given in this manual is useful acc...

Страница 3: ...0 15 Cable Lug Adapters 16 3 3 3 M5 0 20 Cable Lug Adapters 16 3 4 Starting the Test System 17 4 Setup and Function 19 4 1 Block Diagram 20 4 1 1 Voltage Output Voltage Amplifier 21 4 1 2 Current Out...

Страница 4: ...Voltage Outputs 48 6 3 3 1 Power Diagram for Three Phase Operation 49 6 3 3 2 Power Diagram for Single Phase Operation 50 6 3 4 Operational Limits in Conjunction with Mains Supply 51 6 3 5 Low Level O...

Страница 5: ...Accuracy of Phase Measurement 87 6 10 8 Transient Recording 88 6 10 9 Trend Recording 89 6 11 Option LLO 2 Low Level Outputs 90 7 Increasing the Output Power Operating Modes 91 7 1 Safety Instructions...

Страница 6: ...Scanning Head OSH256 113 9 6 2 Interface Box IFB256 114 9 6 3 Scanning Head TK 326 115 9 6 4 Scanning Head TVS 6 15 1 116 9 6 5 Adapter Cable for Scanning Heads 117 9 6 6 CMLIB B 118 9 6 7 CMLIB A 11...

Страница 7: ...f OMICRON Test Universe In addition to the reference manual and the applicable safety regulations in the country and at the site of operation the usual technical procedures for safe and competent work...

Страница 8: ...d Use on page 11 The manufacturer distributors are not liable for damage resulting from unintended usage The user alone assumes all responsibility and risk The instructions provided in this reference...

Страница 9: ...TAGE OUTPUT 4 respectively to protective earth The N sockets however may be connected to protective earth When connecting to the banana plug sockets only use cables with 4 mm 0 16 safety banana connec...

Страница 10: ...he CMC 356 is only permitted by qualified experts either at the factory or at certified external repair centers If the CMC 356 is opened by the customer all guarantees are invalidated CMC 356 Ethernet...

Страница 11: ...nization units or other accessories Features of the CMC 356 Output of test quantities 4 voltage two galvanically separated three phase current outputs Capability of protection testing with IEC 61850 d...

Страница 12: ...tware also installs a PDF version of this reference manual It can directly be opened by a mouse click from the Test Universe Help topic User Manuals 2 1 Options Available for the CMC 356 Test Set The...

Страница 13: ...refer to 6 3 Outputs on page 41 3 OPERATING THE CMC 356 Only operate or even turn on the CMC 356 after you have read this reference manual and fully understood the instructions herein 3 1 System Comp...

Страница 14: ...mm 0 16 banana plugs of the standard test leads fit into non safety sockets see illustration above Never directly insert one of these retractable sleeves into a CMC 356 output socket at the front of t...

Страница 15: ...MC Wiring Accessory Package includes flexible terminal adapters to connect the regular test leads to screw clamp terminals The terminal adapters have blank ends Therefore turn off the voltage before c...

Страница 16: ...erminal strip first and fasten it before connecting it to a test lead 3 3 3 M5 0 20 Cable Lug Adapters The optional CMC Wiring Accessory Package includes M5 0 20 cable lug adapters to connect regular...

Страница 17: ...most important to make sure that the ventilation slots remain unobstructed Connecting the System Components Figure 3 1 Connecting the CMC 356 to the computer 1 Connect the CMC 356 to the PC with the s...

Страница 18: ...tware A comprehensive hardware test is carried out on the CMC 356 In the process switching sounds from relays in the CMC test set can be heard If any irregularities are determined during the course of...

Страница 19: ...and the CMC 356 hardware connected to the test object OMICRON Test Universe test software running on the computer controls the test signals processes measurement data creates reports generates data en...

Страница 20: ...s and DC inputs are not available 1 1 DC AC Main Group SELV Group AUX DC Internal Supplies VOLTAGE CURRENT A CURRENT B CPU System Control Signal Generator PE Mains Host Interface DC DC PC Ext Ampl Ext...

Страница 21: ...ral N and are galvanically separated from all other outputs of the CMC 356 The two black sockets labeled N are galvanically connected with one another The voltage amplifier and the current amplifiers...

Страница 22: ...off with the error message current on neutral too high In non operative state relay contacts as illustrated in figure 5 3 protect the current amplifier from external power by shortening the outputs to...

Страница 23: ...Hardware Configuration module of the OMICRON Test Universe software When doing so it can be specified whether the contacts are potential sensitive or not When the contacts are potential sensitive the...

Страница 24: ...d again Setting a power up default value means that immediately after the test set is switched on this voltage is applied to the auxiliary DC voltage output regardless whether a computer is connected...

Страница 25: ...filtering The power supply to the different modules that each are part of their own galvanic groups are implemented using DC DC converters with reinforced insulation 4 2 Signal Generation The generat...

Страница 26: ...out loss of accuracy In achieving the amplitude accuracy the drift behavior temperature and long term is of major importance in the voltage references the digital analog converters DAC the accurate vo...

Страница 27: ...current inputs 0 10 V DC voltage inputs BINARY ANALOG INPUT 10 binary inputs in 5 galvanically separated groups Hardware option ELT 1 The inputs can be configured as analog measurement inputs Without...

Страница 28: ...Vth 20 V 3 2 k Vth 132 k Vth 350 k 110 k 11 V Circuit diagram of a binary input with programmable threshold voltage wet operation Each binary input can be configured individually for wet or dry operat...

Страница 29: ...oltage outputs In non operative state relay contacts as illustrated in figure 5 3 protect the current amplifier from external power by shortening the outputs to N VOLTAGE OUTPUT 4 x 300 Vrms CURRENT O...

Страница 30: ...Generator combination socket WARNING The connections on the socket are dangerous when the test set is turned on Follow the safety information provided at the beginning of this manual when connecting...

Страница 31: ...rmation You can order the plug for generator combination socket directly from OMICRON For the part number refer to section 9 8 Ordering Information on page 127 Pin Signal 1 VOLTAGE N 2 VOLTAGE 3 3 VOL...

Страница 32: ...est set e g for end to end testing The Ethernet ports also provide the basis for the processing of substation protocols according to the IEC 61850 standard They allow flexible configurations e g for s...

Страница 33: ...oltages and endangering the person working there To prevent such a situation a special mechanism is integrated into the CMC test set that allows only authorized clients to control the test set By usin...

Страница 34: ...n progress LED B blinks quickly The computer writes e g the software image to the flash memory of the CMC test set Do not turn off the CMC test set as long as the writing is in progress 5 2 5 Ethernet...

Страница 35: ...f the firewall is done automatically during installation of the OMICRON Test Universe The software component on the computer that automatically detects test sets on the network OMFind exe requires an...

Страница 36: ...meters For more detailed information please refer to the technical data section 6 3 6 Low Level Binary Outputs ext Interf on page 54 Meter Testing For energy meter test applications the ext Interf pe...

Страница 37: ...ecting cable that was supplied with the amplifier For more detailed information please refer to the technical data section 6 3 5 Low Level Outputs LL out for External Amplifiers on page 52 5 2 6 3 LL...

Страница 38: ...CMC 356 Reference Manual 38...

Страница 39: ...e valid in the frequency range from 0 to 100 Hz unless specified otherwise The given input output accuracy values relate to the range limit value of range limit value 6 1 Main Power Supply Table 6 1 P...

Страница 40: ...oups on CMC 356 front panel VOLTAGE OUTPUT CURRENT OUTPUT A B AUX DC BINARY OUTPUT BINARY ANALOG INPUT ANALOG DC INPUT Basic insulation with maximum voltage of 600 Vrms to ground Clearance 3 mm 0 12 C...

Страница 41: ...idal signals2 harmonics interharmonics3 transient signals 1 If you purchased the option FL 6 the maximum output frequency is constrained to 599 Hz 2 Amplitude derating for current outputs at frequenci...

Страница 42: ...of the output filter The 3 dB bandwidth of this filter limits the amplitude at 3 kHz to about 70 of the maximum range value The application of the extended frequency range is the generation of harmoni...

Страница 43: ...or 0 3 of rg Harmonic distortion THD N 5 6 0 05 0 15 Phase error5 0 05 0 2 DC offset current 3 mA 10 mA Resolution 1 mA 2 mA 2 phases parallel Frequency range9 0 1000 Hz Trigger on overload Timer accu...

Страница 44: ...of the CMC 356 on page 92 0 100 200 300 400 500 600 700 800 900 1000 0 10 20 30 40 50 60 Output Current Arms Output Power per Phase VA W S 6 per phase VA P 6 per phase W S 3 A B per phase VA P 3 A B...

Страница 45: ...Voltage Vpeak 1 low sensitive 32A L L L L 1 high sensitive 32A L L L L 1 low sensitive 64A L L L L 1 high sensitive 64A L L L L 1 low sensitive 128A LL LN 1 high sensitive 128A LL LN LL LN 6 low sens...

Страница 46: ...equire more than 64 A we recommend to use the 1 x 64 A configuration rather than the 128 A one because the 1 x 64 A configuration provides more continuous output power Due to the large number of opera...

Страница 47: ...I A P W duty cycle t1 min ton s toff s 0 25 0 1200 100 30 1800 0 50 0 1200 100 30 1800 26 1400 80 7 5 80 20 52 1400 80 7 5 80 20 29 1300 75 6 0 60 20 58 1300 75 6 0 60 20 32 1200 71 3 5 50 20 64 1200...

Страница 48: ...ase AC L N 1 phase AC L L DC L N 3 x 0 300 V 4 x 0 300 V 1 x 0 300 V 1 x 0 600 V 4 x 0 300 V Output power2 Typical Guaranteed 3 phase AC3 4 phase AC4 1 phase AC L N 1 phase AC L L DC L N 3 x 100 VA at...

Страница 49: ...Technical Data 49 6 3 3 1 Power Diagram for Three Phase Operation Figure 6 7 Power diagram for three phase operation Output voltage in V Output power per phase in VA typical guaranteed...

Страница 50: ...peration Also refer to section 7 2 4 Single Phase Voltage on page 95 Figure 6 8 Single phase operation L N Figure 6 9 Single phase operation L L Output voltage L N in V Output power in VA typical guar...

Страница 51: ...low line voltages no other significant degradations in the technical data of the CMC 356 occur Table 6 8 Typical total output power at different mains voltages Mains voltage Current Typical total out...

Страница 52: ...e 119 and 9 6 9 Connection Cable for REF 54x Relays ABB with Low Level Signal Inputs on page 121 The low level outputs are short circuit proof and continually monitored for overload They are separated...

Страница 53: ...0 025 Guaranteed 0 07 for 1 10 Vpeak Harmonic distortion THD N 3 3 Values at nominal voltage 10 Vpeak 50 60 Hz and 20 kHz measurement bandwidth Typical 0 015 Guaranteed 0 05 Phase error4 4 Valid for...

Страница 54: ...from the cable wiring side Table 6 11 Data of the low level binary outputs 11 14 Pin Function Pin 1 Counter input 1 Pin 2 Counter input 2 Pin 3 Reserved Pin 4 Neutral N connected to GND Pin 5 Binary o...

Страница 55: ...ription about the connection sockets LL out and ext Interf visit the Web site www lemo com Rear side of CMC 356 Rpullup Inside of CMC 356 16 V 47 6 8 k 22 k Vextern 5 15 V Binary outputs 11 14 ext Int...

Страница 56: ...ntial free contacts software controlled AC loading Vmax 300 VAC Imax 8 A Pmax 2000 VA DC loading Vmax 300 VDC Imax 8 A Pmax 50 W refer to load limit curve Switch on current 15 A max 4 s at 10 duty cyc...

Страница 57: ...max 0 4 A 0 264 VDC max 0 2 A Power Max 50 W Accuracy1 1 Percentage is with respect to each range s full scale Error typical 2 guaranteed 5 Resolution 70 mV Connection 4 mm 0 16 banana sockets on fro...

Страница 58: ...ion time Max 220 s Sampling frequency 10 kHz Time resolution 100 s Max measuring time Unlimited Debounce time 0 25 ms refer to page 60 Deglitch time 0 25 ms refer to page 60 Counting function counter...

Страница 59: ...shown in of reading rd of upper range value rg 5 of rd 0 5 of rg Threshold voltage hysteresis Range I typ 60 mV Range II typ 900 mV Input impedance2 Threshold 0 20V Threshold 20 300V 2 Refer to figur...

Страница 60: ...t the first change of the input signal causes the debounced input signal to be changed and then be kept on this signal value for the duration of the debounce time The debounce function is placed after...

Страница 61: ...cable wiring side Table 6 18 Counter inputs 100 kHz Pin Function Pin 1 Counter input 1 Pin 2 Counter input 2 Pin 3 Reserved Pin 4 Neutral N connected to GND Pin 5 Binary output 11 Pin 6 Binary output...

Страница 62: ...urer description about the connection sockets LL out 1 6 and ext Interf visit the Web site www lemo com Rear side of CMC 356 15 V 100 k 22 k 47 pF Inside of CMC 356 Counter inputs 1 2 ext Interf Order...

Страница 63: ...wer over Ethernet ports ETH1 and ETH2 CMC 356 test sets with NET 1 board can be upgraded with the new NET 1B board to be able to communicate with the new CMControl and have Ethernet access at the same...

Страница 64: ...o crossover Connector RJ45 Cable type LAN cable of category 5 CAT5 or better Status indication Green LED physical link present Yellow LED traffic on interface Ethernet port ETH2 Type 100Base FX 100Mbi...

Страница 65: ...ng temperature 0 50 C above 30 C a 50 duty cycle may apply Storage and transportation 25 70 C Max altitude 2000 m Humidity 5 95 relative humidity no condensation Climate Tested according to IEC 68 2 7...

Страница 66: ...ibility EMC Directive 89 336 EEC and the low voltage Directive 73 23 EEC EMC Emission Europe International USA EN 61326 EN 61000 6 4 EN 61000 3 2 3 IEC 61326 IEC 61000 6 4 IEC 61000 3 2 3 FCC Subpart...

Страница 67: ...DC components DC voltages or DC currents Real time indication of effective values true RMS for all measurement signals Peak values indication Upeak Ipeak Phase angles with reference to a given input...

Страница 68: ...measured values are passed through an isolation amplifier to the Measurement Unit and digitized by an A D converter The further processing is done by a high performance floating point digital signal...

Страница 69: ...e measurement unit consists of a highly accurate voltage reference one ADC Analog Digital Converter for each input and the respective input circuits i e accurate voltage divider shunt filter The DC me...

Страница 70: ...rg means n of upper range value Guaranteed error 0 02 of rg Input impedance Approx 15 Connection 4 mm 0 16 banana connectors Insulation Insulation to all other front panel connections Reinforced insul...

Страница 71: ...h voltage outputs or shunt resistors OMICRON offers the C PROBE1 as a suitable current clamp refer to section 9 5 Current Clamp C PROBE1 on page 112 The C PROBE1 is not included in the scope of delive...

Страница 72: ...he installation of option ELT 1 Figure 6 20 Simplified diagrams of analog and binary inputs with option ELT 1 installed ANALOG DC INPUT Only available with option ELT 1 PTC 0 20 mA 0 10 V BINARY ANALO...

Страница 73: ...V 14 V 140 V 600 V 2 mV 20 mV 200 mV 2 V 20 V Max input voltage CAT II 600 Vrms 850 Vpk CAT III 300 Vrms CAT IV 150 Vrms Threshold voltage accuracy1 per range 100 mV 1 V 10 V 100 V 600 V 1 Valid for p...

Страница 74: ...nge 100 mV Frequency range Accuracy Typical Guaranteed DC 0 15 0 40 10 Hz 100 Hz 0 06 0 15 10 Hz 1 kHz 0 06 0 11 0 25 10 Hz 10 kHz 0 06 0 7 1 1 Frequency range Accuracy Typical Guaranteed DC 0 15 0 45...

Страница 75: ...gmamax value of an analog input are determined from 50 measurement values Frequency Response in the 100 V Range SR 28 44 kHz 2 5 2 1 5 1 0 5 0 0 5 1 0 2 4 6 8 10 12 14 Frequency kHz Rel Error Maximum...

Страница 76: ...neighboring channel of another potential group is greater than 120 dB in all measurement ranges f 50 Hz or 500 Hz 1 a b 3Sigmamax represents the maximum of the 3Sigma values of all 10 input channels...

Страница 77: ...ction of the input voltage Phase CH1 CH2 Range 100 V f 50 Hz 0 0 05 0 1 0 15 0 2 0 25 0 3 1 10 100 Amplitude CH2 Vrms Phase Error CH1 10V CH1 70V CH1 50V Phase error in Phase error as function of the...

Страница 78: ...s less than 0 2 the sign positive or negative of the measurement results can not be definitely determined If this causes a problem please refer to the phase measurement in the harmonic analysis 3 For...

Страница 79: ...on greater than 10 from measurement full scale duty cycle 50 Note With the harmonic analysis input frequencies up to 3 4 kHz can be measured Error in Frequency Measurement as a Function of the input v...

Страница 80: ...he apparent power error of the current clamp is not taken into account Table 6 38 Sampling rates 28 44kHz 9 48kHz 3 16kHz Table 6 39 Sampling rate 28 44kHz P 1 T u t i t t d 0 T Q S 2 P 2 sign_Q 1 T u...

Страница 81: ...requency range Power Accuracy1 AC Typical Guaranteed 10 Hz 750 Hz S 0 3 0 7 1 8 10 Hz 750 Hz P 0 3 0 7 1 8 10 Hz 750 Hz Q 0 8 1 2 2 5 Frequency range Power Accuracy1 AC Typical Guaranteed 10 Hz 250 Hz...

Страница 82: ...4kHz f 50Hz 0 0 02 0 04 0 06 0 08 0 1 0 12 0 14 0 16 0 18 0 2 0 10 20 30 40 50 60 70 80 90 100 Excitation CH1 CH2 Rel Error phi 1 phi 60 cos phi 0 01 89 4 Typical error of apparent power S as function...

Страница 83: ...reactive power Q as a function of the excitation fs 28 44kHz f 50Hz 0 15 0 1 0 05 0 0 05 0 1 0 15 0 2 0 25 0 3 0 10 20 30 40 50 60 70 80 90 100 Excitation CH1 CH2 Rel Error phi 1 phi 60 cos phi 0 01...

Страница 84: ...10 7 Harmonic Analysis This operating mode is designed for measuring stationary signals e g not sinusoid shaped The input signal is separated into fundamental and harmonic waves Fourier Analysis The f...

Страница 85: ...20 Hz 1 kHz Note Through recursive averaging the measurement uncertainty can be further reduced Sampling rate Input frequency range 28 44 kHz 49 Hz 3400 Hz 9 48 kHz 17 Hz 1100 Hz 3 16 kHz 5 Hz 380 Hz...

Страница 86: ...V 100 V 10 V 1 V Table 6 46 Sampling rate 28 44 kHz measurement range 100 mV Table 6 47 Sampling rate 9 48 kHz 3 16 kHz measurement range 600 V 100 V 10 V 1 V Sampling rate Input frequency range 28 4...

Страница 87: ...raging the measurement uncertainty can be reduced further Frequency range Accuracy Typical Guaranteed fmin 100 Hz 0 15 0 4 fmin 1 kHz 0 2 0 5 0 8 fmin 4 kHz sampling rate 9 48 kHz 0 2 1 0 1 5 fmin 1 4...

Страница 88: ...dow relative to the trigger event can be specified The trigger delay can be positive recording begins after the trigger event or negative recording begins already before the trigger event Figure 6 33...

Страница 89: ...art Each selected measurement function appears in a separate diagram i e all frequency measurements in the frequency diagram RMS current and voltage appear in separate diagrams Time is displayed in se...

Страница 90: ...hese six high accuracy analog signal sources can serve to either control an external amplifier or to directly provide small signal outputs The outputs 7 12 extend the low level outputs 1 6 LL out 1 6...

Страница 91: ...e OMICRON Test Universe software 7 1 Safety Instructions for High Current Output Observe the following safety instructions when using the operating modes and connection methods described in this chapt...

Страница 92: ...B are connected in series The currents 1 and 2 of a group are phase opposite This results in four times the compliance voltage of a single output Observe the safety instructions given in Section 7 1...

Страница 93: ...each group are phase opposite In addition the groups A and B are connected in parallel Observe the safety instructions given in Section 7 1 on page 91 when using this operating mode Figure 7 2 Single...

Страница 94: ...C the third phase is used to support the N socket The currents 1 2 of groups A and B are connected in parallel Observe the safety instructions given in Section 7 1 on page 91 when using this operating...

Страница 95: ...N 1 x 0 600 V 1 x 275 VA 200 600 V typical Figure 7 5 Single phase operation of the voltage system L L phase opposition Refer to the output curves shown in the figures 6 8 through 6 9 in section 6 3...

Страница 96: ...available 7 3 1 2 x 64 A High Current Mode LL LN 2 x 0 64 A 90 ADC max 35 Vpeak 2 x 500 VA at 40 A Since the current over the N socket is limited to 32 Arms 45 ADC the third phase is used to support t...

Страница 97: ...e L L 2 x 0 32 A 45 ADC max 70 Vpeak 2 x 870 VA at 25 A The currents 1 and 2 of each group are phase opposite Observe the safety instructions given in Section 7 1 on page 91 when using this operating...

Страница 98: ...eparate phases it is possible to double the available compliance voltage However this configuration does not make sense if a common N connector is required Do not connect N1 N2 and N3 to each other Ob...

Страница 99: ...alone cannot cover Each LL output socket LL out 1 6 and the optional LL out 7 12 can connect up to four external amplifiers with six independent channels The following configurations are possible 9 2...

Страница 100: ...CMC 356 Reference Manual 100...

Страница 101: ...error messages 6 If you call the OMICRON hotline please have your computer and test set available and be prepared to repeat the steps that caused the problem To speed up the support please attach the...

Страница 102: ...d from the power source Replace the fuse T 12 5 AH 250 V 5 x 20 mm Malfunction of internal test set components Please contact the OMICRON technical support refer to section Contact Information Technic...

Страница 103: ...r limit of the current outputs set the compliance voltage of the internal current amplifiers To do so go to the Compliance Voltage group box of the Output Configuration Details dialog box in the Test...

Страница 104: ...CMC 356 Reference Manual 104...

Страница 105: ...1 Connecting a CMA S amplifier to the CMC 356 Table 9 1 Technical data of CMA S amplifiers Detailed information about the CMA S amplifiers can be found in the corresponding user manuals the product c...

Страница 106: ...e tester in getting reliable results quickly The CMControl can either be used attached to the CMC test set as front panel control or detached as a handheld control device Its magnetic rear allows easy...

Страница 107: ...cron at For ordering information about the CMGPS refer to table 9 5 Order numbers overview on page 128 Table 9 2 Basic technical data of the CMGPS synchronization unit Antenna ext Interf ext Interf Pu...

Страница 108: ...extension of the antenna cable an optional set of 2 20 m cables is available from OMICRON For ordering information refer to table 9 5 Order numbers overview on page 128 Figure 9 5 Adapter to connect t...

Страница 109: ...e test modules supporting the IRIG B time reference is the starting and synchronizing of CMC 356 states signal output with high accuracy synchronous to the IRIG B1 time reference or PPS PPX2 signal re...

Страница 110: ...ex html Detailed information about how to configure the Test Universe software component Time Trigger Configuration for the use of CMIRIG B with or without CMGPS can be found in the CMIRIG B Reference...

Страница 111: ...nverter This converter connects the CMC 356 to a network via fiber optics The 100TX to 100FX SC Converter transfers data from a 10 100Base TX copper to a fiber interface It is designed to receive both...

Страница 112: ...t ranges Figure 9 9 Current clamp C PROBE 1 For detailed information about the C PROBE1 current clamp and the option ELT 1 please refer to the respective reference manuals the product catalog or visit...

Страница 113: ...rce Figure 9 10 The optical scanning head OSH256 attached to an energy meter by rubber adhesive The OSH256 has a unique fixing method as the lightweight unit can be attached to smooth surfaces by mean...

Страница 114: ...w 9 6 2 Interface Box IFB256 Typically the combination of a scanning head OSH256 with an interface box IFB256 is used for relay testing when binary information a trigger signal originates from a relay...

Страница 115: ...p to the infrared wavelength range It includes a spiral cable for the connection to the adapter cable or to a CMLIB B Figure 9 13 The photoelectric scanning head TK 326 The TK 326 connects to the EXIF...

Страница 116: ...able for electronic meters with optical pulse outputs and matching mechanical interface Figure 9 14 The magnetic scanning head TVS 6 15 1 The TVS 6 15 1 connects to the EXIF socket of a CMC 356 by mea...

Страница 117: ...nnector is plugged into the LEMO socket ext Interf at the rear of a CMC test set From there the scanning heads are supplied with 14 VDC and meter pulses are fed to the counter input of the CMC Figure...

Страница 118: ...t set need to be accessed For these applications the CMLIB B is used as interface Figure 9 17 Connecting a CMLIB B For detailed information about the CMLIB B please refer to the CMLIB B reference manu...

Страница 119: ...hat do not have an OMICRON connection socket to the CMC analog low level signal outputs Connection of OMICRON amplifiers to controlling sources that do not have an OMICRON connection socket Convenient...

Страница 120: ...e battery checking method The CMC 356 injects a special continuous voltage or current test signal at one point Then CPOL checks the polarity at all terminals and provides a clear indication as to whet...

Страница 121: ...onnect ABB relays of the REF 54x series with AMPHENOL twin BNC bulkhead receptacles type 31 223 to the low level outputs of the CMC 356 16 pole LEMO connector Figure 9 20 REF 54x cable connector Order...

Страница 122: ...Z0081 C Shunt 10 is a 10 m precision shunt for current measurements It can be directly inserted into the test set s binary analog inputs C Shunt 1 Electrical resistance 0 001 Resistance Tolerance 0 1...

Страница 123: ...ead 2 m 6 ft test lead to connect the CMC 356 output to other safety sockets of for example amplifiers test objects or to banana adapters in control cabinets Specification 1000 V 32 A Amount supplied...

Страница 124: ...o connect to screw clamp terminals Specification 1000 V 32 A Amount supplied 12 pieces 9 7 2 Optional CMC Wiring Accessory Package Figure 9 22 The CMC Wiring Accessory Package The CMC Wiring Accessory...

Страница 125: ...ection 9 7 1 Specification 600 V 32 A Amount 6 x red 6 x black 2 Flexible jumper Flexible jumper to connect current outputs in parallel up to 32 A or to short out the neutrals of binary inputs Identic...

Страница 126: ...Cable lug adapters for M4 0 15 screws to connect regular test leads to screw clamp terminals of SEL ABB GE relays and others Specification 1000 V 20 A Amount 20 pieces 6 M5 0 2 Cable Lug Adapters Cab...

Страница 127: ...cables II CMC 356 test set Test object relay meter Plug for generator combination socket VEHS0103 Generator combination cable VEHK0103 Ampl in Ampl in Ampl out Amplifier CMA CMS ext Interf LL out 1 6...

Страница 128: ...soft bag VEHP0014 VEHO2806 CMControl 6 add on for a new CMC 356 VEHO2805 CMIRIG B Interface box section 9 3 2 CMIRIG B Interface box incl all accessories VEHZ1150 CMIRIG B Interface box VEHZ1151 Conne...

Страница 129: ...s section 9 6 5 VEHK0010 CMLIB B Interface box for testing with reference meters accessing the transistor outputs section 9 6 6 VEHZ1102 CMLIB A Interface box to connect non OMICRON amplifiers tap the...

Страница 130: ...112 CMC Wiring Accessory Package VEHZ0060 containing the following items 1 Flexible test lead with retractable sleeve 600 V 32 A 6 x red 6 x black 2 Flexible jumper 600 V 32 A 4 x black 3 Crocodile cl...

Страница 131: ...case with wheels and extendable handle for the CMC 356 test set with or without CMControl 6 for CMB IO 7 and for CMA or CMS amplifiers VEHP0021 Soft bag for CMC 356 test set Soft bag for CMC 356 test...

Страница 132: ...CMC 356 Reference Manual 132...

Страница 133: ...e or promote products derived from this software without specific prior written permission This software is provided by the copyright holders and contributors as is and any express or implied warranti...

Страница 134: ...nditions and the following disclaimer in the documentation and or other materials provided with the distribution 3 The name of the author may not be used to endorse or promote products derived from th...

Страница 135: ...re must not be misrepresented you must not claim that you wrote the original software If you use this software in a product an acknowledgment in the product documentation would be appreciated but is n...

Страница 136: ...The OMICRON Bootloader Software Copyright Notices 136...

Страница 137: ...sia Ltd Suite 2006 20 F Tower 2 The Gateway Harbour City Kowloon Hong Kong S A R Phone 852 2634 0377 E Mail support asia omicron at Web http www omicron at Europe Africa Middle East OMICRON electronic...

Страница 138: ...Contact Information Technical Support 138...

Страница 139: ...0 signal generation 25 active power calculation 80 address OMICRON addresses 137 altitude max altitude for operation 65 amplifier CMA current amplifier 105 CMS voltage amplifier 105 current amplifier...

Страница 140: ...ion 67 128 e mail OMICRON addresses 137 EN certified safety standards 66 Ethernet Power over Ethernet 63 Ethernet cables ordering information 127 external interface ext Interf 54 F fiber optics 111 FL...

Страница 141: ...for CMC 356 overview 12 option ELT 1 67 option LLO 2 90 ordering information for CMC 356 accessories 127 OSH256 scanning head 113 output power per phase when group A group B 44 voltage outputs 3 phas...

Страница 142: ...standards 66 storage temperature 65 supply voltage and output power relation 51 synchronization via GPS 36 107 synchronized operation 41 system components of CMC 356 13 T Technical Support 137 temper...

Отзывы: