Technical Data
85
Table 6-43:
Sampling rate
9.48 kHz
Table 6-44:
Sampling rate
3.16 kHz
Table 6-45:
DC accuracy
Note:
The accuracy specifications include linearity, temperature, ageing drift,
frequency and phase response.
Frequency range
Power
Accuracy
1
AC
Typical
Guaranteed
10 Hz ... 750 Hz
S
+ 0.3 % / - 0.7 %
± 1.8 %
10 Hz ... 750 Hz
P
+ 0.3 % / - 0.7 %
± 1.8 %
10 Hz ... 750 Hz
Q
+ 0.8 % / - 1.2 %
± 2.5 %
Frequency range
Power
Accuracy
1
AC
Typical
Guaranteed
10 Hz ... 250 Hz
S
+ 0.3 % / - 0.5 %
± 1.3 %
10 Hz ... 250 Hz
P
+ 0.3 % / - 0.5 %
± 1.3 %
10 Hz ... 250 Hz
Q
+ 0.8 % / - 1 %
± 2.2 %
Power
Accuracy
1
1
S = Apparent power
P = Active power
Q = Reactive power
DC
Typical
Guaranteed
P, S
± 0.3 %
± 0.9 %
Actual - Expected
Full scale
x 100 %
Relative error: