OMICRON
13
Introduction
3.2.3
Warning lights
CIBANO 500
provides the following warning lights to indicate safe operation and possible hazards.
3.2.4
Emergency Stop button
Pressing the
Emergency Stop
button
immediately
shuts off all
CIBANO 500
outputs and stops the
running measurement. After pressing the
Emergency Stop
button,
Primary Test Manager
does not
allow starting a measurement.
To restart the measurement after the reason for the emergency stop has been resolved, release the
Emergency Stop
button by carefully turning it, click the
Start
button in
Primary Test Manager
, and then
press the
Measurement Start/Stop
button.
For information about the
CIBANO 500
accessories, see "Accessories" in the CIBANO 500 PTM User
Manual.
Table 3-1: Warning lights
Warning
light
Description
CIBANO 500
state
Operating condition
Green light on the front
panel is on.
CIBANO 500
is up and
running in the stand-by
mode.
Safe operating condition as long as
no voltage is applied from outside
(As long as the warning symbol on
the side panel is off.)
Blue ring on the
Measurement
Start/Stop
button is on.
A test is prepared and
ready to start.
Blue ring on the
Measurement
Start/Stop
button is
flashing.
A test is starting.
Possibly there are
hazardous voltage
and/or current levels at
the
CIBANO 500
outputs.
Dangerous operating
condition
Red light on the front
panel is flashing.
A test is running.
Possibly there are
hazardous voltage
and/or current levels at
the
CIBANO 500
outputs.
Dangerous operating
condition
Warning symbol on the
side panel is flashing.
There are hazardous
voltage levels (> 42 V)
at the
CIBANO 500
inputs/outputs
independent of the
measurement state.
Dangerous operating
condition