AC/DC Current Clamp C-Probe 1
10
3.2 General
Data
• Dimensions:
230 x 67 x 36 mm
• Max. wire diameter:
11.8 mm
• Max. opening of clamp jaws:
15 mm
• Connecting cable:
2 m length, isolated banana plugs
• Weight:
330 g (battery included)
3.3
Input and Output Quantities
Maximum system voltage of live wire: V
eff
= 600 V with reference to ground
Bandwith of frequency: DC up to 10 kHz.
Table 3-1:
Accuracy data
Switch position
100 mV/A
10 mV/A
Measurement
range
1
1
A higher modulation leads to the saturation of the core and hence to faulty measurements.
This does not affect safety.
0-10 A
AC/DC
0-40 A
AC/DC
40-60 A
AC/DC
60-80 A
AC/DC
Accuracy
10-100Hz
1% of
meas. value
± 5 mA
2% of
meas. value
± 30 mA
0/-8% of
meas. value
± 30 mA
0/-12% of
meas. value
± 30 mA
Accuracy
DC
1,5% of
meas. value
± 5 mA
2% of
meas. value
± 30 mA
0/-10% of
meas. value
± 30 mA
0/-10% of
meas. value
± 30 mA
Accuracy
10 Hz - 1 kHz
1,5% of
meas. value
± 5 mA
2% of
meas. value
± 30 mA
0/-10% of
meas. value
± 30 mA
0/-12% of
meas. value
± 30 mA
Accuracy
10 Hz - 10 kHz
1.5/-7% of
meas. value
± 5 mA
0/-8% of
meas. value
± 30 mA
0/-10% of
meas. value
± 30 mA
0/-12% of
meas. value
± 30 mA
Phase shift
45 - 55Hz
< 0.5°
< 0.5°
< 0.5°
< 0.5°
Phase shift
10 Hz - 1 kHz
< 2°
< 2°
< 3°
< 3°
Phase shift
10 Hz - 10 kHz
< 30°
< 30°
< 30°
< 30°
Содержание C-Probe 1
Страница 1: ...27 AC DC Current Clamp C Probe 1 User Manual...
Страница 6: ...AC DC Current Clamp C Probe 1 6...
Страница 9: ...9 Technical Data 3 Technical Data 3 1 Dimensions Figure 3 1 Dimensions of C Probe 1...
Страница 14: ...AC DC Current Clamp C Probe 1 14...
Страница 22: ...AC DC Current Clamp C Probe 1 22...
Страница 24: ...AC DC Current Clamp C Probe 1 24...
Страница 30: ...Contact Information Technical Support 30...