7.3.3 PTP configuration page
Select the corresponding pane to specify your PTP configuration settings. Click the
Save
button to
save and apply your PTP configuration specified in the individual tabs to
OTMC 100
.
7.3.3.1
General pane
PTP profile
Use this list box to select the PTP profile.
Default E2E
: Default profile with the end-to-end mechanism as
defined in IEEE 1588-2008. Intended for application in industrial
environments that use the IEEE 1588-2008 Precision Time Protocol.
Default P2P
: Default profile with the peer-to-peer mechanism.
Intended for application in industrial environments that use the
IEEE 1588-2008 Precision Time Protocol.
Power (C37.238-2011) - DEPRECATED
: The Power profile acc. to
IEEE C37.238-2011 is obsolete. This PTP profile was initially
intended for application in power system environments that use the
Precision Time Protocol according to the IEEE Std. C37.238-2011
(IEEE Standard Profile for Use of IEEE 1588-2008 Precision Time
Protocol in Power System Applications). (
OTMC 100p
only.)
Power (C37.238-2017)
: Power profile acc. to IEEE C37.238-2017.
Successor of the obsolete Power profile acc. to IEEE C37.238-2011.
This PTP profile is intended for application in power system
environments that use the Precision Time Protocol according to the
IEEE Std. C37.238-2017 (IEEE Standard Profile for Use of IEEE
1588 Precision Time Protocol in Power System Applications).
(
OTMC 100p
only.)
Power utility (61850-9-3:2016)
: Power Utility Automation profile acc.
to IEC 61850-9-3. This PTP profile is intended for application in
power utility automation using the Precision Time Protocol according
to IEC 61850-9-3:2016 (Precision time protocol profile for power
utility automation). (
OTMC 100p
only.)
OTMC 100 Series User Manual
62
OMICRON