Cod. 710.0138.01.00 Rev04A 

– 03.2017 

© Copyright 2017 OMI Srl - All rights reserved

                  

  6 

– 12

 

 

 

Push the SET key for 10 seconds to enter the parameters configuration menu: the display will show in sequence 
the set point value, the code of the first modifiable parameter (C8) and its value). 
Only if strictly necessary, use the UP and/or DOWN keys to change the displayed parameter value. 
Press  the  SET  key  to  store  the  previously  changed  parameter  value  or  to  browse  the  parameters  without 
changing them. 
15 seconds after the last performed operation, the controller will return automatically to the normal operation 
mode. 

 
 

 

 

 

PARAMETER 

DESCRIPTION 

RANGE 

DEFAULT SET VALUE 

C8 

Delay between condensate 

discharges 

1 ÷ 240 (min) 

C9 

Time required for condensate 

discharge 

1 ÷ 240 (sec) 

ED18-144 

ED180 

ED225-1000 

 
 

NOTE: Changes entered for timing values will be effective only after exiting the programming, while changes to other variables 
will be immediately effective. 
Please remember that eventual changes to the configuration parameters of the machine could negatively affect its efficiency. 
Thus, changes have to be performed by a person familiar with the operation of the dryer. 

 
 

 

WARNING FOR USER:IT’S FORBIDDEN TO ATTEMPT TO MODIFY THE OTHER CONFIGURATION PARAMETERS 
OF THE ELECTRONIC CONTROLLER WITHOUT AUTHORIZATION AND COLLABORATION OFOMI

’S 

AUTHORIZED DISTRIBUTOR.

 

 

 

3.1.3 DISPLAY INDICATIONS 

The  controller  is capable  of  recognizing  certain  types  of  anomalies  in  the  drying circuit.  In  such cases,  a  message  will blink  on  the 
display, alternated to the current dew point value. 

 

MESSAGE 

(BLINKING) 

CAUSE 

OUTPUTS 

ACTIONS 

HtA 

High dew point value 

(delayed alarm) 

Alarm output ON 
Refrig. Compressor output OFF 
Fan output ON 
Drain cycle standard 

Resettable by switching off the 
dryer.  
If problem persists call your 
localOMI distributor. 

Ht2 

Very high dew point value 

(immediate alarm) 

PF1 

Interruption or short circuit on the 

PTC probe input line 

Alarm output ON 
Refrig. Compressor output OFF 
Fan output OFF 
Drain cycle standard 

Resettable by switching off the 
dryer. May require replacing the 
faulty probe. 
If problem persists call your 
localOMI distributor. 

ESA 

The automatic Energy saving 

mode activated due to low load 

Alarm output OFF 
Refrig. Compressor output OFF 
Fan output OFF 
Drain cycle standard 

No action necessary. 
Automatic Reset 

ES2 

ASt 

Activated after repeated alarms 

Alarm output ON 
Refrig. Compressor output OFF 
Fan output ON 
Drain cycle standard 

Call your localOMI distributor. 

 

Note: PF1 has priority on all other messages. 

 
 
 
 

 
 
 

3.1.4  REMOTE SIGNALING ALARM 

 

Содержание ED18

Страница 1: ...138 01 00 Rev04A 03 2017 Copyright 2017 OMI Srl All rights reserved 1 11 DIRECT EXPANSION COMPRESSED AIR DRYERS Operators Manual ED18 ED24 ED72 ED54 ED108 ED144 ED180 ED225 ED260 ED360 ED480 ED660 ED7...

Страница 2: ......

Страница 3: ...ion 4 3 START UP 3 1 Control panel 4 3 1 1 Keys function 5 3 1 2 Condensate discharge parameters programming 6 3 1 3 Anomaly warning 6 3 1 4 Remote signalling alarm 7 3 2 Before start up 7 3 3 Start u...

Страница 4: ...Cod 710 0138 01 00 Rev04A 03 2017 Copyright 2017 OMI Srl All rights reserved...

Страница 5: ...ion to the risk of electric shock Condensate drain point Rotation direction of the fan Pay particular attention to the risk of moving parts Explosion risk Lifting point Don t lift from this point Atte...

Страница 6: ...s counterflow the initial air air exchanger and it is reheated by the inlet hot air with the consequence of energy recovering and also reduction of the relative humidity contained in the outflowing ai...

Страница 7: ...empt to lift heavy objects without proper lifting equipment i e crane hoist slings or fork truck Lifting any unit without proper lifting equipment may cause serious injury Use fork lift channels where...

Страница 8: ...l isolation switch if present The control panel will show the message OFF indicating that the line and control voltages are available Start sequence The dryer will initially start by pressing and hold...

Страница 9: ...splayed value of one unit per second during the first 10 seconds than of one unit every 0 1 sec ON OFF Pressed it activates or deactivates the dryer When the dryer is deactivated the display shows OFF...

Страница 10: ...R USER IT S FORBIDDEN TO ATTEMPT TO MODIFY THE OTHER CONFIGURATION PARAMETERS OF THE ELECTRONIC CONTROLLER WITHOUT AUTHORIZATION AND COLLABORATION OFOMI S AUTHORIZED DISTRIBUTOR 3 1 3 DISPLAY INDICATI...

Страница 11: ...e operations specified below must be performed after the first start up and at each start up after a prolonged inactive period of time due to maintenance operations or any other reason 1 Make sure tha...

Страница 12: ...ed YEARLY OR EVERY 2000 HOURS OF OPERATION Check if the flexible tube used for condensate drainage is damaged and replace it if necessary Check if all connecting pipes are properly tightened and fixed...

Страница 13: ...1000 Intervention of the high pressure switch Reset the high pressure switch Problems with cabling or with the electronic control board Check the cabling and the electronic control board if the troubl...

Страница 14: ...extremely delicate Do not remove the probe from its position In case of any kind of problem please contact your localOMI distributor Pic 3 drain solenoid valve When it is necessary Clean the mesh filt...

Страница 15: ...than 30 seconds see terminal block diagrams attachment B for futher details Maintenance Zero Drain is equipped with Service Unit which is recommended to be changed every year to ensure proper working...

Страница 16: ...electricity supply to the dryer and then affix appropriate warning signs to avoid the machine being reconnected to the electricity mains Please consult the contents and the safety instructions in the...