Cod. 710.0103.01.01 – Rev.04 – 09.2012
CF04
PB1 probe configuration (DEW POINT)
0 = Probe absent
1 = NTC temperature
1
CF05
PB2 probe configuration (AIR INLET)
0 = Probe absent
1 = NTC temperature
1
CF06
PB3 probe configuration (AMBIENT)
0 = Probe absent
5 = NTC temperature
5
CF07
PB4 probe configuration (REFRIGERANT CIRCUIT SUCTION)
0 = Probe absent
1 = NTC temperature
1
CF08
ID1 digital input configuration (1S2)
0 = refrigerant circuit thermal protection
0
CF09
ID2 digital input configuration (REMOTE ON/OFF)
3 = remote on/off
3
CF10
ID5 digital input CONFIGURATION (1Q2 – FAN THERMAL PROT.)
1 = Fan thermal protection
1
CF11
N.U:
4
CF12
ID1-MF digital input polarity (1S2)
0 = active with close contact
1 = active with open contact
1
CF
CF13
ID2-MF digital input polarity (REMOTE ON/OFF)
0 = active with close contact
1 = active with open contact
1
Configuration
Parameters
CF14
ID3 digital input polarity (1P1)
0 = active with close contact
1 = active with open contact
1
CF15
ID4 digital input polarity (1P3)
0 = active with close contact
1 = active with open contact
0
CF16
ID5 digital input polarity (1Q2 – FAN THERMAL PROTECTION)
0 = active with close contact
1 = active with open contact
0
CF19
PB4 polarity (REFRIGERANT CIRCUIT SUCTION)
0 = active with close contact
1 = active with open contact
1
CF20
Condensate drain valve/s relais polarity(RL4)
0 = active with close contact
1 = active with open contact
0
CF22
Refrigerant pressure value = 4ma
bar
0
CF23
Refrigerant pressure value = 20ma
bar
30
CF24
PB1 probe calibration offset (DEW POINT)
°C
-1
CF25
PB2 probe calibration offset (AIR INLET)
°C
0
CF26
PB3 probe calibration offset (AMBIENT)
°C
0
CF27
PB4 probe calibration offset (REFRIGERANT CIRCUIT SUCTION)
°C
0
CF28
Condensate drain unit operation
0 = Always ON
1 = Timed
1
CF29
Condensate drain ON - time
Sec
1
CF30
Condensate drain OFF - time
Sec
300
CF32
Selection: °C or °F
0 = °C / BAR
1 = °F / psi
0
CF33
Selection of mains frequency
0 = 50 Hz
1 = 60 Hz
2 = Direct current
2
CF34
Serial address
1
CF35
Remote controller
0 = 4 buttons
1 = 6 buttons
2 = 6 buttons with NTC probe on board
1
CF36
Default controller display
0 = IN / PROBE
1 = OUT / PROBE
2 = IN / rtC
3 = OUT / rtc
0
CF37
Firmware release
2.0