2.2 Equipment nameplate values
(Nameplate values extracted from Calculation data sheet)
Fluid
Circuit Side
Press. Max. Amm.
Safety devices set
Work. Temp
Design Temp
MAWP
"PS" (bar rel)
(bar rel)
(°C)
(°C)
Freon HFC
(R507, R407c, R134a, R404a)
R134a R407c
R404a,
R507
R134a
R407c
R407c
R404a,
R507
Low press. -LP
20
20
18*
18*
18*
min -10°
min -15°
High Press. -HP
28
30,8
18*
27,9*
29*
max +100°
max +100°
Compressed air (Dryers)
Compress. Air Side min 0
(Customer care)
min 0°
min 0°
max. 12 (aluminium)
max +55°
max +55°
max. 16 (copper)
Refrigerant Liquid (Chiller)
Liquid side
min 0
(Customer care)
min -10°
min -15°
max 8
max +45°
max. +45°
Ambient air
Ventilation side
Atm.
( Not Appl.)
min 5°
min -15°
max +45°
max. +45°
* - Safety Pressure switch Cat IV PED, Manual reset
Welding Joints Coefficient
z
0,7
(Table 5.6-1)
Tickness allowance
c
0,1
mm
( Per rame - For copper )
(Not required for surfaces in contact with freon - EN 14276-1)
c
1
mm
( Per acciaio - For carbon steel )
Manufacturer design code
717.0012.01.00
Rev.03
Essential Safety Requirements
ON10.0010.02
Rev.01
Manufacturer Working Procedure
PO 08.2
Rev.01
Assembly classification according PED 97/23
Cat. II
Evaluation Module according PED 97/23
Mod. A1
PED Notified Body number
0474
WHAT SHOULD BE DONE:
•
Be familiar with the manual.
•
Respect all limit values indicated in this manual.
•
Before performing any maintenance make sure that the dryer is isolated from the compressed air network (inlet and outlet cut-off
valves closed) and that internal pressure has been released.
•
Before removing protection panels disconnect electrical power and allow the machine to cool down for about 15 minutes.
•
Before removing cooling fan protection grid ensure that the electrical power is disconnected.
•
Ensure that all protection panels are properly attached during operation and after any maintenance operation.
•
The inlet air should not contain any flammable gases or vapours.
WHAT SHOULD BE AVOIDED:
•
No maintenance operation except the one’s mentioned in Chapter 5 can be carried out by any personnel without the Manufacturer’s
written approval.
•
Do not modify the pressure equipment, including the calibration of control and safety devices.
•
Never place flammable objects near the dryer.
•
Never use dryer if power cable is defect or the connection is not safe.
•
Never allow anyone to operate the dryer without giving him/her proper instructions.
•
Never do any alteration to safety parts.
•
Never strike or use excessive force on internal parts.
•
Never touch any parts of the cooling circuit while machine is running. Danger – Burn hazard!
•
Never drain the condensate directly into the sewage system.