26 |
M 5 7 7 9
6.4.1.2.2
Factory Calibrate
The Factory Calibrate bit is not used for DIO types.
6.4.1.2.3
Writeable
This indicates that the sensor value may be overwritten. Not used on DIO inputs.
6.4.1.2.4
Smart Sensor
Refer to the
Smart Sensor Device Interface
documentation.
6.4.1.3
DIO Input Configuration
DIO Input Configuration
7
6
5
4
3
2
1
0
Available Assigned
Apply
Scaling
Lock
Sub Channel Selection
0
0
1
?
0x03 == bits 0 and 1
6.4.1.3.1
Lock
If set, the user-specified units of measure string (4 character maximum) will be used in
place of the default
DIN.
6.4.1.3.2
Apply Scaling
If set, the user-defined Offset and Gain values will be used to adjust the sensor reading:
Result = (Raw Reading * Gain) + Offset
6.4.1.3.3
Assigned
The Assigned bit will always read as 0. Refer to the
Smart Sensor Device Interface
documentation for further information.
6.4.1.3.4
Available
The Available bit will always read as 0. Refer to the
Smart Sensor Device Interface
documentation for further information.
6.4.1.4
DIO Device Configuration
The DIO Device Configuration allows enabling each of the 2 input bits and selecting whether the
input is active HIGH (reads as 1 when input is not grounded) or active LOW (reads as 1 when input is
grounded).
DIO Device Configuration
7
6
5
4
3
2
1
0
Reserved
DIN 1
DIN 0
0
0
0
0
ENABLE
INVERT
ENABLE
INVERT
1
1
1
1
6.4.1.4.1
Invert
If the Invert bit is set the input is active LOW.
6.4.1.4.2
Enable
If the Enable bit is set the input is enabled.