CN710/CN730/CN740   Temperature Controller 

Instruction Sheet

 

Thank you very much for purchasing Omega Engineering CN700 Series Temperature Controller. Please read this 
instruction sheet before using your controller to ensure proper operation and please keep this instruction sheet handy 
for quick reference. 

1   

Precaution 

 

 

DANGER!

 

Caution! Electric Shock!

 

1.  DO NOT touch the AC terminals while the power is supplied to the controller to prevent an electric shock. 
2.  Make sure power is disconnected while checking the unit inside. 

3. The 

symbol    indicates this Controller is protected throughout by DOUBLE INSULATION or REINFORCED 

INSULATION (equivalent to Class II of IEC 536). 

 

WARNING!

 

Mount the controller in a location that will not be subject to excessive temperature, shock, or vibration. All 
models are designed for mounting in an enclosed panel. 

1.  Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm, hole 

diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Recommended tightening torque: 0.4 N.m 
(4kgf.cm). Applicable wire: Solid/twisted wire of 2 mm

2

, 12AWG to 24AWG. Please be sure to tighten them 

properly. 

2.  DO NOT allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning. 
3.  Never modify or disassemble the controller. 
4.  DO NOT connect anything to the “Not used” terminals. 
5.  Make sure all wires are connected to the correct polarity of terminals. 
6.  DO NOT install and/or use the controller in places subject to: Dust or corrosive gases and liquid, high humidity and 

high radiation, vibration and shock, high voltage and high frequency 

7.  Power must be off when wiring and changing a temperature sensor. 
8.  Be sure to use compensating wires that match the thermocouple types when extending or connecting the 

thermocouple wires. 

9.  Please use wires with resistance when extending or connecting a platinum resistance sensor (RTD). 
10.  Please keep the wire as short as possible when wiring a platinum resistance sensor (RTD) to the controller and 

please route power wires as far as possible from load wires to prevent interference and induced noise. 

11.  This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, 

dripping water, corrosive materials, airborne dust and electric shock or vibration. 

12.  Please make sure power cables and signals from instruments are all installed properly before energizing the 

controller, otherwise serious damage may occur. 

13.  Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent 

an electric shock. 

14.  Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any 

internal circuit within this period. 

15.  DO NOT use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller. 
16.  This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install 

the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse 
type: Time-lag fuse 

17.  Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent 

protection device(s) must be added to ensure compliance with all relevant electrical standards and codes. (Rated 
250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-use 
installation. 

2  

Display, LED, & Pushbuttons 

 

 

3  

Model Number Identification 

 

 

 

 

  

 

4  

Temperature Sensor Type & Temperature Range 

 

Input Temperature Sensor Type 

Register Value 

LED Display 

Temperature Range 

Platinum resistance (Pt100) type3 

15 

 

0.0 ~ 100.0°C 

Input Temperature Sensor Type 

Register Value 

LED Display 

Temperature Range 

Platinum resistance (Pt100) type2 

14 

 

-20.0 ~ 500.0°C 

Platinum resistance (Pt100) type1 

13 

 

-200 ~ 600°C 

Platinum resistance (JPt100) type2 

12 

 

0.0 ~ 100.0°C 

Platinum resistance (JPt100) type1 

11 

 

-20.0 ~ 400.0°C 

Thermocouple (TC) B type 

10 

 

100 ~ 1,800°C 

Thermocouple (TC) S type 

 

0 ~ 1,700 °C 

Thermocouple (TC) R type 

 

0 ~ 1,700 °C 

Thermocouple (TC) N type 

 

-200 ~ 1,300 °C 

Thermocouple (TC) E type 

 

0 ~ 600 °C 

Thermocouple (TC) T type2 

 

-20.0 ~ 400.0°C 

Thermocouple (TC) T type1 

 

-200 ~ 400°C 

Thermocouple (TC) J type2 

 

-20.0 ~ 400.0°C 

Thermocouple (TC) J type1 

 

-100 ~ 850°C 

Thermocouple (TC) K type2 

 

-20.0 ~ 500.0°C 

Thermocouple (TC) K type1 

 

-200 ~ 1,300°C 

Thermocouple (TC) L type 

16 

 

-200 ~ 850°C 

Thermocouple (TC) U type 

17 

 

-200 to 500°C 

Thermocouple (TC) Txk type 

18 

 

-200 to 800°C 

 

5  

Operation 

 

There are three modes of operation: operation, regulation and initial setting. When power is applied, the controller will 
default to the operation mode. Press   

  to switch to regulation mode. If 

  is pressed for more than 3 seconds, 

the controller will switch to the initial setting mode. Pressing 

  while in the regulation mode or initial setting mode, 

forces the controller to return to the operation mode. PV/SV: Sets the temperature set point and displays the 
temperature process value. Use 

 

  to set the temperature set point. 

Setting method: While in any function mode, press 

  to select the desired function and use 

 

 to change 

settings. Press 

  to save the changes. Menu items are listed below. 

Regulation Mode 

Operation Mode 

Initial Setting Mode 

 Auto-tuning 

(Set in PID control & RUN mode) 

Press 

 

V

 Use 

 

 

to set 

temperature set point 

Press 

 

V

  Set input type 

 

Press 

 

V

  Set proportional band (Kp) 

(in PID control) 

Press 

 

V

  Control setting RUN or STOP

 

Press 

 

V

 Set temperature unit 

(Not displayed when in analog input)

Press 

 

V

  Set integral time (Ki) 

(in PID control) 
 

Press 

 

V

 Upper-limit alarm 1 

(This parameter is available only when 
ALA1 function is enabled.) 

Press 

 

V

  Set upper-limit of 

temperature range 
 

Press 

 

V

  Set derivative time (Kt) 

(in PID control) 
 

Press 

 

V

 Lower-limit alarm 1 

(This parameter is available only when 
ALA1 function is enabled.) 

Press 

 

V

  Set lower-limit of 

temperature range 
 

Press 

 

V

 or 

 P/PD control 

offset (when PID control is ON and 
Ki=0 set the value of PdoF. If Ki

0, AT 

(Auto-tuning will automatically set the 
value of ioF. 

Press 

 

V

 Upper-limit alarm 2 

(This parameter is available only when 
ALA2 function is enabled.) 
 
 

Press 

 

V

  Set Control method: 

ON/OFF, PID, or manual. 
 
 
 

Press 

 

V

 or 

 Heating/cooling 

hysteresis 
(in ON/OFF control) 

Press 

 

V

 Lower-limit alarm 2 

(This parameter is available only when 
ALA2 function is enabled.) 

Press 

 

V

  Select heating or cooling 

control.  
 

Press 

 

V

 or 

 Heating/cooling 

control cycle setting 
(Set in PID control mode) 

Press 

 

V

  Set lock mode 

 
 

Press 

 

V

  Alarm 1 mode setting 

 
 

Press 

 

V

 Regulate temperature 

deviation value 

Press 

 

V

  Display and adjust output 

value. 

Press 

 

V

  Alarm 2 mode setting 

 

Press 

 

V

  Regulate upper-limit of 

analog output value 
(The setting is displayed when in 
analog output) 

Press 

 

V

 

 Communication write 

function enabled/disabled 
 
 

Press 

 

V

  Regulate lower-limit of 

analog output value 
(The setting is displayed when in 
analog output) 

Press 

 

to return to “auto-tuning" 

 

 Communication address 

setting 
 
 

Press 

 

V

 

 

  Communication baud rate 

setting 

Press 

 

V

 

 

  Data length setting 

Press 

 

V

 

 

 Parity bit setting 

Press 

 

V

 

 

  Stop bit setting 

Press 

 

to return to “set input type”

 

„

 

Parameters List 

1. Operation Mode:

 The default mode after start-up 

LED Display 

Explanation 

Default 

 

RUN/STOP: Control setting. Run (

) or Stop (

) mode on the SV 

display. 

 

RUN 

 

ALARM 1 HIGH: Upper limit for alarm 1. (Only available when alarm is set in the 
initial setting mode). 

4.0°C 

 

ALARM 1 LOW: Lower limit for alarm 1. (Only available when alarm is set in the 
initial setting mode). 

4.0°C 

 

ALARM 2 HIGH: Upper limit for alarm 2. (Only available when alarm is set in the 
initial setting mode). 

4.0°C 

 

ALARM 2 LOW: Lower limit for alarm 2. (Only available when alarm is set in the 
initial setting mode). 

4.0°C 

 

Lock Function Setting: LoC1, LoC2, or OFF. LoC1 mode will lock all settings, LoC2 
locks everything except the set point value, and OFF will not lock any settings. 

Press 

 and 

  keys simultaneously, to release the lock status. 

OFF 

 

OUT: The Output value adjustment and display in manual tuning control. (Not 
available in ON/OFF or Auto-tuning control). 

2. Regulation Mode:

 Control parameters Settings 

LED Display 

Explanation 

Default 

 

AT (Auto-Tuning): ON or OFF, when set ON, the execution of the auto-tuning 
function in PID control mode is automatically started. (Only available when PID 
control is selected in initial settings) 

OFF 

 

P (Proportional Band in PID control): Sets P value. 

47.6 

 

I (Integral Time in PID control): Sets I value. 

260 

 

D (Derivative Time in PID control): Sets D value. 

41 

 

PdoF: Offset output when P or PD control function is on. PID in initial settings is 
selected and the value of Ki (Integral Time in regulation mode) is equal to zero.   

 

ioF: Default value of integral volume when PID control is ON and the Ki (Integral 
Time in regulation mode) is not equal to zero. AT function can automatically set this 
parameter when PID control is active and Ki

0. 

 

HtS (Heating Hysteresis): Available only in ON/OFF control. Sets the value the 
heating hysteresis. 

 

CtS (Cooling Hysteresis): Available only in ON/OFF control. Sets the value the 
cooling hysteresis. 

 

HtPd: PID heating control cycle setting. Only available when a PID control is 
selected in the initial settings. 

 

ClPd: PID cooling control cycle setting. Only available when a PID control is 
selected in the initial settings. 

Output 
Selection: 
Voltage: 4 sec.
Relay : 20 sec.

 

TPoF: Regulates the temperature deviation value. 

 

CrHi: Regulates the 20mA output deviation value. 

 

CrLo: Regulates the 4mA output deviation value. 

 

HtS (Heating Hysteresis): Available only in ON/OFF control. Sets the value the 
heating hysteresis. 

3. Initial Setting Mode: 

Initial settings of the controller and communication parameters

 

LED Display 

Explanation 

Default 

 

INPUT: Select input temperature sensor type   
(Please refer to the contents of the “Temperature Sensor Type and Temperature 
Range” for detail)

 

PT2 

 

Engineering Unit(°F or °C): Select engineering unit F or C. 

°C 

 

T-High: Upper limit for temperature range. 

500.0 

 

T-Low: Lower limit for temperature range. 

-20.0 

CONTROL METHOD (ON/OFF, PID, or manual tuning [

]): Sets the control 

method for the set point value. 

PID 

 

Control Action (Direct or Reverse Acting): Cooling [Cool] or heating [HEAT]. 

HEAT 

PV   

displays process value 

SV displays 

setpoint 

value. 

  INDEX: advances the display to the next menu item. 

  UP ARROW: Increments a value or changes a menu item. 

  DOWN ARROW: Increments a value or changes a menu item. 

  ENTER: stores the value or item change.

 