Using This Quick Start Manual

Use this Quick Start Manual to set up your controller
and begin operation.  Information is provided on how to:
¥

Connect ac power

¥

Connect the RTD

¥

Set basic options for operation

For complete information on all setup options, see the
OperatorÕs Manual.

Before You Begin

In addition to the meter and the related parts, you will
need the following items to set up your meter:
¥

ac power, as listed on meterÕs ID/Power Label

¥

RTD 

¥

1

Ú

8

Ó flat blade screwdriver

Mount the Meter

1.

Cut a panel opening
using the dimensions
shown here.

2.

Position the meter in
the opening, making
sure the front bezel is flush with the panel.

Connect ac Power

Warning: Do not connect ac power to your meter
until you have completed all input and output
connections. Failure to do so may result in injury!

1.

Remove the panel at the back of the meter.

2.

Locate the TB1 connector.

3.

Insert the correct wire in each terminal and tighten
the lockdown screws.  Tug gently on the wires to
verify connections.

Main ac Power Connections

To:

Take This Action

Select a value

1.  Press  

/MAX

. to display

for that submenu

the option you want.

function.

2.  Press 

MENU

to select it.

The message 

STRD

quickly 

flashes, indicating that the 
selection has been stored in 
memory.  Then the next
menu function displays.

Go back to the

Press 

RESET

once.

previous menu
function.

Exit the meter

¥    Press 

RESET

twice.  The 

Configuration

reinitializes (displays 

RST

,

Menu.

then 

RTD

). When the

temperature displays, the
meter is back in run mode.

¥    Optionally, you can press 

MENU

to move through all

the menu functions until the
meter reinitializes.

To Set the RTD Type:

1.

Press 

MENU

until the meter

displays:

2.

Press  

/DEV

. The meter

displays:

3.

Press 

/MAX

until the 

RTD

for your installation is shown. 

¥ RTD.2 is for a 2-wire RTD

¥ RTD.3 is for a 3-wire RTD

¥ RTD.4 is for a 4-wire RTD

4.

Press 

MENU

to select the RTD shown. The 

meter displays:

4-Wire RTD Input Connection

Turn on the Meter

1.

Apply ac power to the meter. The meter initializes,
flashing RST then RTD on the front panel.  Then
the temperature should appear.

2.

Verify that a temperature is displayed.  If not:

¥

Remove ac power

¥

Verify the TB1 power connections

¥

Check your power source

¥

Apply ac power again

Configure the Meter

To configure the meter, use the buttons on the front
panel.

To:

Take This Action

Display  the

Press the 

MENU

button.

Configuration

The first function on the

Menu.

menu, INPT, displays.

Select the 

1. Press 

MENU

until the

sub-menu

function you want is shown.

(a function you

2.  Press 

/DEV

.

want to perform).

The information you can change
begins to flash.

8

VERSION #1

RTD

7

+S

+E

5

1

6

2

3

TB2

+E1

-S

-R

+R

8

4

+S1

RTD

VERSION #2

TB2

5

1

6

2

7

3

4

-E1

-S1

Connecting the RTD

1.

Locate the TB2 connector on the rear of the
meter.

2.

Attach the RTD wires, referring to the appropriate
diagram below and tighten down lockdown
screws.

3.

Tug gently on the wires to verify the connections.

4.

Replace the panel at the back of the meter.

2-Wire RTD Input Connection

3-Wire RTD Input Connection

VERSION #2

+S1

TB2

VERSION #1

1

-R

+S

3

+E

2

5 6

TB2

+R

4

7 8

+E1

1

5

2

-S1 -E1

RTD

6

3

7

4

8

-S

RTD

VERSION #2

+S1

TB2

VERSION #1

1

-R

+S

-S

3

+E

2

5 6

TB2

+R

4

7 8

+E1

1

5

2

-S1 -E1

RTD

6

3

7

4

8

RTD

START HERE

2

3

4

45,00  + 0,61/-0,00

(1.772  + .024/Ð.000)

92,00  + 0,81/Ð0,00

(3.622  + .032/Ð.000)

PANEL THICKNESS

1,5

R(.06)

4 PLCS

6,4 (.25) MAX
0,8 (.03) MIN

NOTE: Dimensions in Millimeters (Inches)

SINGLE RTD MODEL

NOT AVAILABLE FOR

TB2 PINS 1 THRU 4

VERSION #2

TB1

LINE

NEUTRAL

10 11 12

FUSE

AC POWER

EARTH 
GROUND

TB1

VERSION #1

TB2

TB2

8

9

7

8

7

6

5

6

5

4

3

2

1

4

3

2

1

10 11 12

8

9

7

8

7

6

5

6

5

4

3

2

1

SETPTS

/DEV

MENU

RESET

/MAX

SETPTS

/DEV

MENU

RESET

/MAX

SETPTS

/DEV

MENU

RESET

/MAX

SETPTS

/DEV

MENU

RESET

/MAX

SETPTS

/DEV

MENU

RESET

/MAX

12504ML-98A_CN1000-RTD_OMG.qxd  8/13/99  11:29 AM  Page 1

Отзывы: