SLD-34/DZ
SLD-44/DZ
SLD-28/DZ
220-240V AC/50-60Hz
3h
24h
Overcharging and deep discharging protection
Charge LED, Lamp LED, Fault LED, Test Button
IP30
3.6V/1.5Ah
100lm /100lm
125lm /125lm
9.5 VA
9 VA
5 to 40 C
o
up to 95%
ABS/PC, aluminum, Acrylic plate
280x120x15mm
3 years (1 year for the battery)
680gr.
1020gr.
1380gr.
340x190x15mm
440x240x15mm
289x65x34mm
TECHNICAL CHARACTERISTICS
(for LED MODULE specifications see page 4)
Operation temperature range
Relative humidity
Construction materials
External panel's dimensions
External unit’s dimensions
Typical weight
Guarantee
Mains voltage
Maximum power consumption
Battery (Ni-MH)
Recharging time
Battery protection
Indications
Minimum emergency duration
Degrees of cover protection
Produced in accordance with
Light source intensity (230V) / (emerg.)
Page 1 from 4
Description
The Automatic Autonomous Test is conducted and measures the
The luminaire consists mainly from two parts.
luminaire`s back up operation. This test is conducted automatically
The body, where all the electronics are located and the lamp-head
every six months. In order to be performed, the mains power supply
where the indication sign and the high efficiency LEDs are located.
and the battery should be connected (the battery should be charged).
If the battery is not charged, the test is postponed until the battery is
Maintained/Non maintained selection capability
completely charged. If during the Automatic Autonomous Test the
Power on the device and press continuously the TEST button for 10
luminaire’s duration is lower than the nominal, then the battery must
seconds, until the led strip turns off. Release the button and after a
be replaced.
short emergency test, the device operates as non-maintained. If you
want to restore the previous condition (maintained operation), press
Back Up Operation
continuously the TEST button for 10 seconds, until the led strip
The autonomous duration of battery during emergency mode is at
lights. Release the button and after a short emergency test, the
least the one that is stated in the list of the first page. During
device operates as maintained illumination sign.
emergency mode, a LED strip test is also performed.
Installation
Resetting Errors
To install the illumination sign follow the installation instructions on
Push the Test button for >5 seconds, to delete all the indicated LED
page 2.
errors. Then the luminaire enters regular operation mode.
Battery Charging
Indication LED status (with connected mains power supply).
The battery charging is completely controlled. In this case, is
Charge
achieved the perfect battery maintenance , as well as the elongation
On:
Good charge current.
of its duration. When the battery has completely charged, it charges
Οff:
No battery (No charging current or disconnected battery).
with a maintenance current.
Lamp Fault
Οn:
Faulty LED strip or back up circuit.
Battery Cut-off
Off:
Good LED strip or back up circuit.
The luminaire enters in this operation when
Battery Fault
the mains power supply fails and battery has lost its energy. During
Οff:
Battery OK.
this operation the luminaire enters the idle state and battery
consumption is negligible, in order to be protected from deep
Blink
(With
Charge LED
ON): Autonomy or low battery problem
(the
discharge.
battery must be replaced).
Blink
(With
Charge LED
Off):
Manual Test
No charging current or disconnected battery.
The manual test can be conducted only if the mains power supply
and the battery is connected. By pressing the test button briefly an
operation test is initiated. During this test period all indication LEDs
are OFF.
Automatic Test
This test includes all the operations that provide the manual test and
is conducted automatically every 15 days. In order to be performed,
the mains power supply and the battery should be connected.
Automatic Autonomous Test
SELF TESTING MAINTAINED EMERGENCY ILLUMINATION SIGNS WITH WHITE LEDs
922044000_09_027
Thank you for your trust in our products
Olympia Electronics - European manufacturer
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3