background image

GENERAL

o

These  luminaires  are  used  indoors 

(

ta  40 C

)

  where  emergency 

light is needed. Each luminaire must be permanently connected 
to  mains  power  supply

In  normal  operation  the 

power

  indicator 

lights  and  the 

charge

  indicator  blinks  to  show  that  the  batteries 

are in charging condition. In  case  of  a  mains  power  supply 
failure    the   

power 

and  the 

charge

  indicators  turns  off  and  the 

luminaire    will    light  the  spot  lamps  automatically  in  emergency 
mode.  When the  mains  power  supply  is  restored the device 
turns to normal operation.

INSTALLATION

To install the luminaire follow the installation instructions 

ο

n page 

3.

OPERATION

When  the  device  is  powered  from  the  mains

,

  th

e

 

charge

 

indicator 

blinks and 

confirms 

the 

charg

ing of

 the batter

ies

When 

the batteries are charged, it lights constantly. 

If 

it does 

not li

gh

t, 

probably,  the  batter

ies  are

  disconnected.  If 

it  does 

not  li

gh

t  and 

the batter

ies

 

are

 connected, then contact the technician. 

As long 

as  the  charge  indicator  blinks,  the  batteries  of  the  luminaire  are 
charging and in this period, any autonomy test must be avoided. 
When  the  charging  circle  is  complete,  the  indicator  lights 
continuously  (it  can  be  used  as  an  indication  of  a  power 
interruption).  The  batteries  charging  is  done  by  a  3  stages 
technological  advanced  procedure,  to  ensure  the  appropriate 
and  full  charging  of  the  batteries. 

The

  power

  indicator  confirms 

the 

proper connection to the 

mains

. The

 TEST

 

butto

n, has a dual 

use.  If  pressed 

instantlly 

while  the  device  is 

connected  to  the 

mains

,  the  device  simulates  the 

power  interruption

by 

lighting 

the 

lamps for 

3

''. In this way

,

 we can control the driver circuit of 

the lamps

 and

 the

 lamps as indicated in paragraph 

3

 

in 

the text

 

below.

DIMMING OPTION

When the voltage is interrupted, with corresponding press

ing

s of 

the button,

 

we ca

n

 choose 

the illumination of 100%, 50%, 33% 

 or 

turned off

, either to increase the autonomy time or not to consume 

the 

battery power unnecessarily. This option is canceled when the 

network is restored.

ΑΤΤΕΝΤΙΟΝ

!!!

1. Operations for installation, maintainance or
    testing must be done by authorized
    personnel only

.

2. 

The device must be connected to the

    mains power supply through a fuse
    dependent by the total amount of the line’s 
    power load

.

3. 

It is suggested to check every month the

    indication LED for battery charging, and by
    pushing instantly the TEST button to check
    the emergency circuit and the lamps. If the
    luminaire does not light 

4. 

It is suggested to check every 6 months

    the minimum autononous duration by
    disconnecting the mains power supply

.

    Count the time that  the lamps light and in
    case of less time than the minimum
    autonomous duration the batteries must be
    replaced. If the measured time is
    considerably less than the minimum
    autonomous duration 
    The replacement of the battery and the
    light source must be done using parts of
    the same type, by the manufacturer or by a
    competent person.

5. 

t  i

 

in  battery  recycling 

points. Do not incinerate.

Battery replacement

It  can  be  done  only  by  a  competent  person  and  after  the  mains 
interruption

.

1.

 Follow the step 2 

o

f the installation procedure.

2.

 Disconnect the 

cables

 and remove the old battery.

contact the

    installer.

 

contact the installer.

In case of inactive use for a period greater

    than 2 months, disconnect the battery by
    pulling out the battery’s connector.

6. 

I

s  not  allowed  to  discard  batteries  in  to  common  trash 

bins,  they  must  be  discarded  only 

Page

 1

 from 3

 

``POWER LIGHT`` SERIES FOR NON MAINTAINED EMERGENCY LUMINAIRES

923029009_09_012

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

ABS/PC, PC

OPERATION TEMPERATURE RANGE

RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERY

 (

Pb

)

CHARGING TIME

INDICATIONS 

CONTROLS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

24h

Power indicator, battery charge indicator, TEST button

From overcharge and deep discharge

IP42

5 to 40  C

o

Up to 95% 

3 years 

(1 

year for the battery

)

180 min

90 min

  1620lm 

  790lm 

  White  LEDs

3560gr.

2080gr.

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

220-240V AC/50-60Hz

12V/7Ah

6V/4Ah

14.4W/16VA

5.6W/7.5VA

30

2

 

x 94 x 345 mm.

TECHNICAL CHARACTERISTICS

 (

for LED MODULE Specifications see page 2)

GRL-2

1

GRL-29

Отзывы: