GENERAL

o

These  luminaires  are  used  indoors  (ta  40 C) 
where  emergency  light  is  needed.  Each 
luminaire  must  be  permanently  connected  to 
mains  power  supply.  In  normal  operation  the 

power

 indicator lights and the 

charge

 indicator 

blinks  to  show  that  the  batteries  are  in 
charging  condition.  In    case    of    a    mains   
power    supply  failure    the   

power 

and  the 

charge

  indicators  turns  off  and  the  luminaire   

will    light  the  spot  lamps  automatically  in 
emergency  mode.    When  the    mains    power   
supply  is  restored the device turns to normal 
operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions οn page 3.

OPERATION

When  the  device  is  powered  from  the  mains, 
the 

charge

  indicator  blinks  and  confirms  the 

charging  of  the  batteries.  When  the  batteries 
are  charged,  it  lights  constantly.  If  it  does  not 
light, probably, the batteries are disconnected. 
If  it  does  not  light  and  the  batteries  are 
connected,  then  contact  the  technician.  As 
long  as  the  charge  indicator  blinks,  the 
batteries  of  the  luminaire  are  charging  and  in 
this  period,  any  autonomy  test  must  be 

avoided.  When  the  charging  circle  is 
complete,  the  indicator  lights  continuously  (it 
can  be  used  as  an  indication  of  a  power 
interruption).  The  batteries  charging  is  done 
by an 3 stages 
technological  advanced  procedure,  to  ensure 
the  appropriate  and  full  charging  of  the 
batteries.
The

  power

  indicator  confirms  the  proper 

connection  to  the  mains.  The  TEST  button, 
has  a  dual  use.  If  pressed  instantlly  while  the 
device  is  connected  to  the  mains,  the  device 
simulates  the  power  interruption,  by  lighting 
the  lamps  for  3''.  In  this  way,  we  can  control 
the driver circuit of the lamps and the lamps as 
indicated in paragraph 3 in the text below.

Dimming option

When  the  voltage  is  interrupted,  with 
corresponding pressings of the button, we can 
choose the illumination of 100%, 50%, 33%   or 
turned off, either to increase the autonomy time 
or  not  to  consume  the  battery  power 
unnecessarily. This option is canceled when the 
network is restored.

ΑΤΤΕΝΤΙΟΝ!!!

1.  Operations  for  installation,  maintainance  or 
testing  must  be  done  by  authorized  personel 
only.

Page 1 from 3

 

GRL-22

 

``POWER LIGHT`` SERIES  NON-MAINTAINED EMERGENCY LUMINAIRE

923022100_09_006

Bayblend FR3010, transparent  polycarbonate

TECHNICAL CHARACTERISTICS

(

for LED MODULE Specs. see page 2)

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERY (Pb)

CHARGING TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

<24h

Power indicator, battery charge indicator, TEST button

From overcharge and deep discharge

IP42

5 to 40  C

o

Up to 95% 

3 years (1 year for the battery)

  White LEDs

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

302 x 103 x 230 mm

220-240V AC/50-60Hz

600 min

12V/7Ah

710lm 

16VA

3400gr.