charging mode and the Charge led starts to blink
until the batteries are fully charged.
Automatic operational test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected.
Automatic autonomous test
The Automatic autonomous test is conducted and
measures the device’s back up operation and
emergency duration. This test is conducted
automatically every 6 months
.
In order to be
performed, the mains power supply and the
battery should be connected and fully charged
.
If
the battery is not fully charged
,
the test is
postponed
until the battery is completely
charged. If during this test, the autonomy is less
than nominal then the LED battery fault will
permanently be on and the battery must be
replaced.
Back up operation
The autonomous duration of battery during
emergency mode is at least the one that is stated
in the list of the technical characteristics. During
emergency mode, a light source test is also
performed.
Resetting errors
Push the test button for more than 10 seconds, to
delete all the LED indicated errors. Then the
device enters regular
operation mode.
Changing the operating mode
The control of maintained or non maintained
operation of the luminary is achieved through
Switch 4 of DS1. For maintained operation,
switch number 4 must be in ON position. For
non-maintained operation, switch number 4
must be in OFF position according to the step 5
in page 3.
ΑΤΤΕΝΤΙΟΝ!
!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only
.
2. The device must be connected to the mains
power supply through a fuse that is dependent
on the total line’s power load.
3.
In case of battery replacement, this must be
replaced by part of the same type,
by the
manufacturer or
by a competent person.
4. In case of inactive use for a period greater than
2 months, disconnect the battery by pulling out
the battery’s connector.
5. I
s not allowed to discard batteries into
t i
common trash bins, they must be
discarded only
in battery recycling
points.
Do not incinerate.
2
Installation methods
Luminary disassembly
3
3
6
5
2
1
Ενδεικτικά
1
2
Insert the
power cable
Insert the
cable grommet
Insert the
cable grommet
Insert the
power cable
Insert the
power cable
After the desired installation follow the steps below
o
This luminaire is used indoors
(
ta 40 C
)
where
emergency light is needed. Each luminary must
be permanently connected to mains power
supply. In normal operation the led strip lights
and the battery is charging. In case of a mains
power supply failure the luminary will light the
led strip automatically in emergency mode
(powered by its battery). When the mains power
supply is restored the device turns to normal
operation.
Autonomy duration selection
The user can select one of the 3 available
minimum autonomy durations 1 hour, 3 hours
and 8 hours. The selection must be done while
the luminaire is disconnected from AC and
battery supplies. The selection is achieved
through Switches 2 & 3 of DS1 according to step 5
in page 3. Switch 1 is not used.
Technical label installation
Two additional labels are included in the package.
one for 1 hour duration (60) and one for 8 hour
duration (480). Depending on the selected
duration, the installer must cover the default 3
hour (180) printing with one label that has the
required duration. Please take notice of the
orientation of the label.
Battery charging
The battery charging is completely controlled by a
microprocessor and is protected from complete
discharge and over charge
.
Battery cut-off
The luminary enters in this operation when the
mains power supply fails
and battery has lost its
energy
.
During this operation the luminary enters
the idle state
and battery consumption is
negligible, in order to be protected from deep
discharge.
Manual
t
est
for emergency operation and light
source.
The manual test can be conducted only if the
mains power supply and the battery is connected
:
During the Test the lamp fault LED blinks.
Manual
a
utonomous
t
est
A
duration test can be conducted if the TEST
button is pressed from 5 to 10 seconds. The
luminar
y
enters emergency mode, the charge LED
is turned OFF and the Battery Fault led starts to
blink. The test is conducted until the battery is
depleted.If at the end of the test the autonomy is
low then the Battery Fault LED will be ON. If the
result of the test is good then the luminar
y
enters
Insert the
power cable
Insert the
cable grommet
Note
:
Description
CHARGE
(
green
)
Charging
Battery fully charged
Faulty battery
(
When not in emergency
)
Faulty
LED
LED OK
LED test
Battery OK
Battery test
Battery autonomy fault
LAMP
FAULT
(
red
)
BATT.
FAULT
(
yellow
)
Permanently
ON
:
Blinks
:
OFF
:
Indiferrent
:
Ceiling mounting
1
1
1
1
1
Luminaire
Wall mounting accessories
Ceiling mounting accessories
Manual
Package contents
General
Hanging installation
Luminary
assembly
Indications
LED Status
ON
1 2 3 4
ON
1 2 3 4
Maintained operation
Non-maintained operation
1h
ON
ON
1
1
2
2
3
3
4
4
3h
(default position)
8h
ON
1 2 3 4
L
N
Insert the
power cable
DS1
4
Accessories for installation
(After request)
Α-2130
:
Accessor
y
for ceiling
(
1m)
Α-2131
:
Accessor
y
for ceiling (0,5m)
Α-2132
:
Accessor
y
for ceiling (0,25m)
Α-2133
: Accessory for wall mounting
Α-2136
: Accessory for hanging installation
(2,5m)
A-2520/PL
/ST:
Suspended ceiling base
Battery replacement
1.
Disassemble the luminary
.
2.
Remove the battery connector and carefully remove the battery from its base
.
3.
Install a new battery of the same type and rating
.
4.
Assemble the luminary and power the device
.
>5mm
: