background image

The light source of this luminary is not replaceable when the light source 
reaches its end of life the whole luminary shall be replaced.

ATTENTION!!!

922502058

_0

9

_00

4

922502058

_0

9

_00

4

4

5

Warranty

European
manufacturers

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

KLIN-20/ST/ADR

ADDRESSABLE SELF TESTING MAINTAINED

EMERGENCY

 LUMINAIRE

Olympia Electronics guarantees the quality, condition and operation of the goods. The period of 
warranty  is  specified  in  the  official  catalogue  of  Olympia  Electronics  and  also  in  the  technical 
leaflet,  which  accompanies  each  product.  This  warranty  ceases  to  exist  if  the  buyer  does  not 
follow the technical instructions included in official documents given by Olympia Electronics or if 
the  buyer  modifies  the  goods  provided  or  has  any  repairs  or  re-setting  done  by  a  third  party, 
unless Olympia Electronics has fully agreed to them in writing. 

Products that have been damaged 

can  be  returned  to  the  premises  of  our  company  for  repair  or  replacement,  as  long  as  the 
warranty period is valid.

Olympia Electronics  reserves  the  right  to  repair or  to  replace the  returned  goods  and  to  or  not

 

charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to 
charge or not the buyer the transportation cost.

72

nd

 

km

O

.

N

.

R

Thessaloniki-Katerini

P.C. 60300 P.O. Box 06 Εginio Pierias Greece

www.olympia-electronics.com

[email protected]

Non Maintained operation: The luminary lights its illumination source, only in  
power supply’s failure.

(*) Maintained operation: The luminary lights its illumination source, when it is 
powered by the mains power supply or not

.  

 

IP5

4

250/77/12lm

Light output

1h/

3

h/8h

Duration

M

Maintained

Non

maintained

ΝΜ

Addres-

sable

ADR

X

1

8 0

1

A

B

E

C

F

NOTE: 

LED=

 

Light Emitting Diode

A: 

Including test device

C:

 Including inhibiting mode

E: 

With non-replacable lamp(s) and/or battery

LABELING EXPLANATION:
X: 

Self contained

1: 

Maintained

 

(*)

F:

 Automatic test gear complying with IEC 61347-2-7 denoted EL-T

B:

 Including remote test mode

60: 

1 hour duration

180: 

3 hours duration

480: 

8 hours duration

KLIN-20/ST/ADR

220-240V AC

 

/ 50-60Hz

3.9W / 4.4VA

2

2

0.08mm  - 1.5mm

39V DC

1h: 3.4, 3h: 1.4, 8h: 0.2

130mA

1.5W

70

V

20mA

KLIN-20/ST/ADR

Olympia Electronics S.A

.

11.2-13.2V DC

0.72

2711195

Built-in main board

45 °C max. across the board

Technical Characteristics

LED Characteristics

MANUFACTURER
MODEL NUMBER

VOLTAGE RANGE

CONNECTIONS

NOMINAL POWER

TEMPERATURE

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION

3.6V/1.5Ah

1

h (400-690mA), 3h (190-295mA), 8h (55-95mA)

2

0 - 120mA

0.87

BATTERY (Ni-MH)

INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT

MINIMUM POWER FACTOR

WIRE CROSS SECTION

EMERGENCY OUTPUT FACTOR (EoFx)

MAX OPEN CIRCUIT VOLTAGE

Irated

Prated

U-OUT

SUPPLY CURRENT

Basic insulation
Basic insulation

BATTERY PROTECTION

1h / 3h / 8h Manually Selected (Default 3h)

LED / CONSTANT CURRENT

CHARGE TIME

MINIMUM DURATION
LIGHT SOURCE / OUTPUT MODE

24 hours

LED Charge, Lamp Fault LED, Battery Fault LED / Test Button

80lm / 1h: 250lm, 3h: 77lm, 8h: 12lm

LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)

INDICATIONS

MAX CHARGE VOLTAGE

MIN MAX. CHARGE CURRENT
TRICKLE CHARGE VOLTAGE/CURRENT

MIN MAX. DISCHARGE CURRENT

MIN MAX. DISCHARGE VOLTAGE

3 - 4.5V

4.9V

4.4V / 40mA

Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3

IP54

DEGREES OF COVER PROTECTION

EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

PRODUCED IN ACCORDANCE WITH

OPERATION TEMPERATURE RANGE
CONTROL GEAR MAX.TEMPERATURE: tc

o

5

 to 40  C

o

58  C at BR1

PC

420gr.

260 x 35 x 60 mm

RELATIVE HUMIDITY

CONSTRUCTION MATERIAL

EXTERNAL DIMENSION (L x W x H)

WEIGHT
GUARANTEE

Up to 95% 

3 years

 (1 

year for the battery

)

CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION

Accessories for installation

(After request)

Α-2130

Accessor

y

 for ceiling

 (

1m)

Α-2131

Accessor

y

 for ceiling (0,5m)

Α-2132

Accessor

y

 for ceiling (0,25m)

Α-2133

: Accessory for wall mounting

Α-2136

: Accessory for hanging installation

 (2,5m)

Battery replacement

3. Install a new battery of the same type and rating.

2. Remove the battery connector and carefully remove the battery from its base.

1. Disassemble the luminary.

4. Assemble the luminary and power the device.  

Commissioning

A full duration test should be conducted after verifying that the CHARGE indicator is continuously ON. Test is 

initiated by isolating the mains power supply. Verify that the LED lamp is lit during the test period for at least 
the stated duration.

During commissioning of the luminaire write the commissioning date on the battery.

When power is applied to the unit inspect that the CHARGE indicator is either blinking or steady, all other 

indicators are OFF and that the led lamp is lit (maintained operation) or OFF (non-maintained operation)

After  installation,  a  24  hours  charging  cycle  must  be  completed,  in  order  to  achieve  the  nominal 

autonomy.

Отзывы: