The light source of this luminary is not replaceable when the light source
reaches its end of life the whole luminary shall be replaced.
ATTENTION!!!
922502058
_0
9
_00
4
922502058
_0
9
_00
4
4
5
Warranty
European
manufacturers
Thank you for your trust in our products
Olympia Electronics - European manufacturer
KLIN-20/ST/ADR
ADDRESSABLE SELF TESTING MAINTAINED
EMERGENCY
LUMINAIRE
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of
warranty is specified in the official catalogue of Olympia Electronics and also in the technical
leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not
follow the technical instructions included in official documents given by Olympia Electronics or if
the buyer modifies the goods provided or has any repairs or re-setting done by a third party,
unless Olympia Electronics has fully agreed to them in writing.
Products that have been damaged
can be returned to the premises of our company for repair or replacement, as long as the
warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not
charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to
charge or not the buyer the transportation cost.
72
nd
km
.
O
.
N
.
R
.
Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.com
Non Maintained operation: The luminary lights its illumination source, only in
power supply’s failure.
(*) Maintained operation: The luminary lights its illumination source, when it is
powered by the mains power supply or not
.
IP5
4
250/77/12lm
Light output
1h/
3
h/8h
Duration
M
Maintained
Non
maintained
ΝΜ
Addres-
sable
ADR
X
1
8 0
1
A
B
E
C
F
NOTE:
LED=
Light Emitting Diode
A:
Including test device
C:
Including inhibiting mode
E:
With non-replacable lamp(s) and/or battery
LABELING EXPLANATION:
X:
Self contained
1:
Maintained
(*)
F:
Automatic test gear complying with IEC 61347-2-7 denoted EL-T
B:
Including remote test mode
60:
1 hour duration
180:
3 hours duration
480:
8 hours duration
KLIN-20/ST/ADR
220-240V AC
/ 50-60Hz
3.9W / 4.4VA
2
2
0.08mm - 1.5mm
39V DC
1h: 3.4, 3h: 1.4, 8h: 0.2
130mA
1.5W
70
V
20mA
KLIN-20/ST/ADR
Olympia Electronics S.A
.
11.2-13.2V DC
0.72
2711195
Built-in main board
45 °C max. across the board
Technical Characteristics
LED Characteristics
MANUFACTURER
MODEL NUMBER
VOLTAGE RANGE
CONNECTIONS
NOMINAL POWER
TEMPERATURE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
3.6V/1.5Ah
1
h (400-690mA), 3h (190-295mA), 8h (55-95mA)
2
0 - 120mA
0.87
BATTERY (Ni-MH)
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT
MINIMUM POWER FACTOR
WIRE CROSS SECTION
EMERGENCY OUTPUT FACTOR (EoFx)
MAX OPEN CIRCUIT VOLTAGE
Irated
Prated
U-OUT
SUPPLY CURRENT
Basic insulation
Basic insulation
BATTERY PROTECTION
1h / 3h / 8h Manually Selected (Default 3h)
LED / CONSTANT CURRENT
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE / OUTPUT MODE
24 hours
LED Charge, Lamp Fault LED, Battery Fault LED / Test Button
80lm / 1h: 250lm, 3h: 77lm, 8h: 12lm
LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)
INDICATIONS
MAX CHARGE VOLTAGE
MIN MAX. CHARGE CURRENT
TRICKLE CHARGE VOLTAGE/CURRENT
MIN MAX. DISCHARGE CURRENT
MIN MAX. DISCHARGE VOLTAGE
3 - 4.5V
4.9V
4.4V / 40mA
Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3
IP54
DEGREES OF COVER PROTECTION
EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
CONTROL GEAR MAX.TEMPERATURE: tc
o
5
to 40 C
o
58 C at BR1
PC
420gr.
260 x 35 x 60 mm
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
Up to 95%
3 years
(1
year for the battery
)
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
Accessories for installation
(After request)
Α-2130
:
Accessor
y
for ceiling
(
1m)
Α-2131
:
Accessor
y
for ceiling (0,5m)
Α-2132
:
Accessor
y
for ceiling (0,25m)
Α-2133
: Accessory for wall mounting
Α-2136
: Accessory for hanging installation
(2,5m)
Battery replacement
3. Install a new battery of the same type and rating.
2. Remove the battery connector and carefully remove the battery from its base.
1. Disassemble the luminary.
4. Assemble the luminary and power the device.
Commissioning
—
A full duration test should be conducted after verifying that the CHARGE indicator is continuously ON. Test is
initiated by isolating the mains power supply. Verify that the LED lamp is lit during the test period for at least
the stated duration.
—
During commissioning of the luminaire write the commissioning date on the battery.
—
When power is applied to the unit inspect that the CHARGE indicator is either blinking or steady, all other
indicators are OFF and that the led lamp is lit (maintained operation) or OFF (non-maintained operation)
—
After installation, a 24 hours charging cycle must be completed, in order to achieve the nominal
autonomy.