olympia electronics GR-938/15L/ADR Скачать руководство пользователя страница 1

Page

 1

 from

 

5

923939015_09_004

GENERAL

These  luminaires  are  used  in  places  where 
emergency  luminaires  are  needed.  Each 
luminaire  must  be  permanently  connected  to 
mains  power  supply

.

  In  normal  operation  (L1 

connected to L) the led strip lights and the battery 
is charging. In  case  of  a  mains  power  supply 
failure    the  luminaire    will    light  the  led  strip 
automatically  in  emergency  mode  (powered  by     
its battery).  When the  mains  power  supply  is  
restored the device turns to normal operation. 

Address Operation

The  luminaires  can  be  connected  to  a  GR-6500 
address  panel.  For  address  operations  refer  to 
the installation manual of the panel. 
For address module connections see page 3. 
For dip-switch addressing selection see page 3, 4 
and 5.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 3.

Battery Charging

The  battery  charging  is  completely  controlled

.

 

Thereby, the best possible battery maintenance is

 

achieved

as  well  as  the  elongation  of  its 

duration

When  the  battery  has  completely 

charged

it charges with a maintenance current.

Battery Cut-off

The  luminaire  enters  in  this  operation  when  the 
mains  power  supply  fails

 

and  battery  has  lost  its 

energy

During this operation the luminaire enters 

the  idle  state

 

and  battery  consumption  is 

negligible,  in  order  to  be  protected  from  deep 
discharge.

Manual

 Test

The  manual  test  can  be  conducted  only  if  the 
mains power supply and the battery is connected. 
By  pressing  the  TEST/RESET  button  briefly 
(page 3) an operation test is initiated. During this 
test period all indication LEDs are OFF.

Tests

Normally  the  illumination  source  and  the 
autonomy  tests  are  programmed  by  the  control 
panel  and  the  test  results  are  sent  to  the  control 
panel.

If  the  luminaire  is  not  connected  to  GR-6500 
panel, the following automatic tests executed:
 

Automatic Operational Test

This  test  includes  all  the  operations  that  provide 
the  manual  test  and  is  conducted  automatically 
every  15  days.  In  order  to  be  performed,  the 
mains  power  supply  and  the  battery  should  be 
connected. 

ADDRESSABLE SELF TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs

220-240V AC/50-60Hz

4.5W / 4.9VA

Bayblend FR3010

transparent 

 

polycarbonate

TECHNICAL CHARACTERISTICS 

(for LED MODULE Specs. see page 5)

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)

CHARGING TIME

INDICATIONS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

ILLUMINATION (MAINS / EMERGENCY)

ILLUMINATION SOURCE 

90min

24h

Charge, Lamp Fault, Battery Fault indication LED

From overcharge and deep discharge

IP65

3.6V/3Ah

  210lm / 210lm 

  30 white LEDs 

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

o

5 to 40  C

Up to 95% 

3 years 

(1 

year for the battery

)

950gr.

363 x 145 x 73 mm

3.4W / 3.8VA

GR-938/15L/ADR GR-938/30L/ADR GR-939/15L/ADR GR-939/30L/ADR

3.6V/

0.6

Ah

  105lm / 105lm 

  15 white LEDs 

180min

5.3W /5.6VA

3.3W / 3.7VA

3.6V/1.5Ah

  210lm / 210lm 

  105lm / 105lm 

  30 white LEDs 

  15 white LEDs 

810gr.

880gr.

Thank you for your trust in our products.  