olympia electronics GR-460 Скачать руководство пользователя страница 1

Lens

 GR-4

6

0

(Escape Route)

 GR-

4

61

(Anti-Panic Area)

ATTENTION!!!

During installation follow this light direction.

Corridor

lighting

Open

area

lighting

LAMP FAULT BAT. FAULT

CHARGE

TEST

CAUTION : Do not view directly with bare eyes.

The light source of this luminaire is not replaceable when the light source reaches its end of life the whole 
luminaire shall be replaced.

GR-460 & GR-461

SELF TESTING MAINTAINED/NON MAINTAINED 

EMERGENCY CEILING MOUNTED LUMINAIRES WITH LENS

FOR ESCAPE ROUTE OR ANTIPANIC AREA

LAMP FAULT BAT. FAULT

CHARGE

LAMP FAULT BAT. FAUL

T

CHARGE

9234

6000

1_09_00

1

9234

60

001_09_00

1

4

5

GR-

4

60 & GR-461

Magnetic Switch Usage

Autonomy Duration Selection

Olympia Electronics S.A.

65 °C max. across the board

2.7-3.3V DC

1h: 2.1W

3h: 0.9W

8h: 0.25W

2806183

Olympia Electronics -  European manufacturer

Thank you for your trust in our products  

Test

  operations  with  the  A-1900  card  (not  included and  available 

after

 

request).

 

For 

Manual Operational Test

, you must place the card in front of the TEST 

indicator and remove it immediately. 
For 

Manual  Capacity  Test

,  you  must  place  the  card  in  front  of  TEST 

and

 

hold it for 5 to 10 seconds.

ATTENTION!!!

Fixed connection between main pcb and led module

Warranty

Technical Characteristics

LED Characteristics

MANUFACTURER
MODEL NUMBER

VOLTAGE RANGE

CONNECTIONS

NOMINAL POWER

TEMPERATURE (tc)

European
manufacturers

IP42

Non

maintained

NM

Maintained

Μ

320/150/50lm

Light output

Olympia Electronics reserves the right to repair or to replace the returned goods and to or not

 

charge the 

buyer  depending  on  the  reason  of  defection.  Olympia  Electronics  reserves  the  right  to  charge  or  not  the 
buyer the transportation cost.

Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is 
specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies 
each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in 
official  documents  given  by  Olympia  Electronics  or  if  the  buyer  modifies  the  goods  provided  or  has  any 
repairs  or  re-setting  done  by a  third  party,  unless  Olympia  Electronics  has  fully  agreed  to  them  in  writing. 

Products  that  have  been  damaged  can  be  returned  to  the  premises  of  our  company  for  repair  or 
replacement, as long as the warranty period is valid.

72

nd

 

km

O

.

N

.

R

Thessaloniki-Katerini

P.C. 60300 P.O. Box 06 Εginio Pierias Greece

www.olympia-electronics.gr

[email protected]

GR-

4

60 & GR-461

220V-240V AC / 50-60Hz

25mA

5.5W / 5.6VA

0.9

10V

1h: 2.1W

1h: 695mA

3h: 0.9W

3h: 295mA

Basic Insulation
Basic Insulation

Deep discharge and overcharge protection

4-6V

1hour / 3 hours / 8 hours

IP

42

5 to 40°C

Up to 95%

ABS/PC, PC

500gr

3 years (1 year for the battery)

1 white power LED

Charge, Lamp Fault, Battery Fault, Test Magnetic Switch

EN 60598-1, EN 60598-2-22, EN 55015, EN 61547

EN 61000-3-2, EN 61000-3-3, EN62311

300lm / 1h: 320lm, 3h: 150lm, 8h: 50lm

23hours

100 - 130mA

3h: 190 - 280mA

8h: 70 - 115mA

1h: 460 - 645mA

4.8V / 1.2Ah (4KRMT 15/51)

500V

8h: 0.25W
8h: 95mA

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION

BATTERY (Ni-MH)

INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT

WORKING VOLTAGE AT WHICH THE INSULATION IS DESIGNED

MINIMUM POWER FACTOR (

λ)

Irated

Prated

U-OUT

MAXIMUM SUPPLY CURRENT

BATTERY PROTECTION
BATTERY VOLTAGE RANGE

CHARGE TIME

MINIMUM DURATION
LIGHT SOURCE

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

OPERATION TEMPERATURE RANGE

RELATIVE HUMIDITY

CONSTRUCTION MATERIAL

EXTERNAL DIMENSION (L x W x H)

WEIGHT
GUARANTEE

Controlgear is suitable for LED module only
The controlgear has mains-connected windings of transformer

INDICATIONS

BATTERY CHARGE CURRENT RANGE
BATTERY DISCHARGE CURRENT RANGE

LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)

CONTROL GEAR WITH AUTOMATIC

TEST FUNCTION

15

8

 x 15

8

 x 60.4mm

 

(without decorative bezel) - 1

95

 x

 

195

 

x 60.4 (with decorative bezel)

2

1

1h

(default position)

3h

8h

Dip Switch Positions

Autonomy duration selection

Technical label installation

The user can select one of the 3 available minimum autonomy duration 1hour, 3hours and 8hours. The selection 
must be done while the luminaire is disconnected from AC and battery supplies. The selection is achieved through 
Switches 1 & 2 of DS1.

Two additional labels are included in the package, one for 3 hours duration (180) and one for 8 hours duration (480). 
Depending on the selected duration, the installer must cover the default 1 hour (60) printing with one that has the 
required duration. Please take notice of the orientantion of the label.

3

ON

1 2

ON

2

1

ON

2

1

DS1

A-1900

Battery Replacement

2

 

Disconnect the connector and remove the old battery.

3

.

 

Connect the new battery with the same type

 

and place it in

 

the position of the old one.

1.  Detach  the  front  cover by applying pressure using  a  flat  blade screw driver. Next,  unfasten  the  four  retaining screws 

without removing them and remove the diffusor.

4

.

  Replace the removed parts 

and power the device.

It can be done only by a competent person and after the mains interruption

.

SELF

TESTING

ST

MAX. POWER 

CONSUMPTION

5.5W/5.6VA

Ni-MH

1h/

3

h/8h

Duration

5 to

o

40 C

TEMPERATURE 

RANGE