GENERAL

T h e s e   l u m i n a i r e s   a r e   u s e d   w h e r e  
emergency  light  is  needed.  Each  luminaire 
must  be  permanently  connected  to  the 
mains  power  supply

.

  In  normal  operation 

the  battery  is  charging,  the  green  LED  and 
2  yellow  LED’s  light  in  non-maintained 
operation.  The  green  LED  and    the  LED 
strip  light  in  maintained  operation

.

  In    case   

of    a    mains    power    supply  failure    the   
l u m i n a i r e     w i l l     l i g h t   t h e   L E D   s t r i p    
automatically  in  emergency  mode.    When 
the    mains    power    supply    is    restored  the 
device turns to normal operation.

Non  maintained  /  maintained  operation 

There  is  an  option  to  select  the  non-
maintained  or  maintained  operation  by 
placing  the  jumper  to  the  appropriate  place 
(page 2)

.

INSTALLATION

To install the luminaire follow the installation 
instructions on page 2.

ΑΤΤΕΝΤΙΟΝ

!

!!

1.  Operations  for  installation,  maintainance 

or  testing  must  be  done  by  authorized 
personnel only

.

2.  The 

luminaire

  must  be  connected  to  the 

m a i n s   p o w e r   s u p p l y   t h r o u g h   a   f u s e  
dependent  on the total amount of the line’s   
power load.

3. It is sug

g

ested to check every month the 

indication  LED  for  battery  charging,  and  by 
placing  the  test  card 

  (page  3)  an 

(

A-1900)

operation test is initiated, to check the 
emergency  cirquit.  The  illumination  source 
should  light  as  long  as  the  card  is  present

In  the  opposite  condition  contact  the 
installer.

 

 

4.  It  is  sug

g

ested  to  check  every  6  months 

the  minimum  autononous  duration  by 
disconnecting  the  mains  power  supply. 
Count the time that  the led strip lights and 
in  case  of  less  time  than  the  minimum 
autonomous  duration  the  battery  must  be 
r e p l a c e d .   I f   t h e   m e a s u r e d   t i m e   i s  
considerably  less  than  the  minimum 
autonomous  duration 

 

contact  the  installer.

In  case  of  battery  or  led  strip  replacement, 

 WATERPROOF NON MAINTAINED / MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs

220-240V AC/50-60Hz

3.3W/3

.5

VA

TECHNICAL CHARACTERISTICS

 

(for LED MODULE Specs see page 4)

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)

CHARGING TIME

INDICATIONS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

ILLUMINATION (MAINS / EMERGENCY)

ILLUMINATION SOURCE 

90min

24h

Charge indication LED

From overcharge and deep discharge

IP65

3.6V/3Ah

  40lm / 210lm 

  30 white LEDs 

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

o

5 to 40  C

Up to 95% 

3 years 

(1 

year for the battery

)

810gr.

3.1W/3

.3

VA

3.6V/

0.6

Ah

  40lm / 105lm 

  15 white LEDs 

180min

4.5W/4.8VA

3.4W/3

.6

VA

3.6V/1.5Ah

  40lm / 105lm 

  30 white LEDs 

  40lm / 210lm 

  15 white LEDs 

630gr.

710gr.

313 x 118 x 66 mm

Bayblend FR3010

transparent 

 

polycarbonate

Thank you for your trust in our products.  

Olympia Electronics -  European manufacturer

.

GR-1935/15L

GR-1936/15L

GR-1936/30L

GR-1935/30L