INSTALLATION INSTRUCTIONS
Page 2 of 3
1.
Detach the plastic base (located in the bottom of the luminaire) by pulling the unlock hook and
pass the cables from area or and through the cable entry hole.
The luminaire must be
connected to a permanent electrical installation
to ensure
the
immobilization of the cable.
Mount
the plastic base with the included mounting accessories
.
2.
Connect the mains cables to the respective detachable
terminal block
.
Ν
for neutral
,
L for live wire
.
3.
Attach the luminaire by sliding it on the plastic base until the
plastic hook locks, and power the luminaire
.
4. MAINTAINED/NON-MAINTAINED OPERATION
JUMPER SELECTION
You can choose the luminaire’s operation. When the
jumper is installed (by default) in the middle and right pins
maintained operation is selected.
When the jumper is installed in the middle and left pins
non-
maintained operation
is selected
.
NOTE!!
After finishing the installation you must power the device at least for 24 ours for battery
charging to perform the nominal autonomy.
Maintained
operation
Non-maintained
operation
3
L 230V AC
N
Plastic base
1
2
Cable entry hole
N
L
A
B
N
L
A
B
Battery replacement
It can be done only by a competent person and after
the mains interruption
.
1.
Detach the luminaire from its base (
step
1
of the
installation
procedure
)
.
2.
Use a flat blade screwdriver to remove the diffusor.
3
.
Remove the reflector.
4.
Disconnect the connector and remove the old battery.
5
.
Connect the new battery with the same type
and
place it in the
position
of the old one.
6
.
Replace the removed parts (
step
1,2 and 3)
.
2
LED MODULE CHARACTERISTICS
Olympia Electronics S.A
.
Cable connection between main pcb and led module
45 °C max. across the board
2.9-3.6VDC
780mW
0111163
GR-108/12L/90
GR-109/12L/180
Lock - unlock hook
Manufacturer
Model Number
Voltage Range
Connections
Nominal Power
Temperature (tc)
923109004_
0