background image

921661001_09_003

921539000

_

09_003

921539000

_

09_003

2

3

1

Installation Instructions

1
1
1

Package Contents

General

Detector

Mounting Accessories

Manual

The 

BS-

661/A  is  a  conventional  heat  detector  which  integrates

 

the 

function  of  rate-of-rise  heat  detection.  The  detector  transitions  to 

o

alarm state when the temperature   reaches 57 C. Also, the detector 

o

transitions to alarm state when the temperature rises suddenly by 32 C 
regardless of the initial temperature at the beginning of the sudden rise 
event.

The user have to read carefully the following instructions, in order to be 
properly informed and keep them for future use.

The detector has fault diagnosis function, which automatically informs 
you through the onboard LED when detector replacement is required. 
The indication LED blinks every 7 seconds. In normal operation it blinks 
1  time  and  if  there  is  a  failure  it  blinks  3  times.  These  functions 
combined with periodic manual testing ensure maximum security level. 
It is suggested to carry out a test every 6 months or after a change in the 
position of the sensor.

INSTALLATION

MAINTENANCE & FUNCTIONAL TESTING

The detector have a visible led and a remote led driver which are light 
up constantly in case of detection of fire, till cancelled from the panel.

 

They are turned off only when a reset command is given from the panel. 
The indicator led blinks every 

7

 sec indicating the normal function.

CAUTION !!

For spacings, heights and all mounting points consult the local/national 
regulation  or  the

    standard

 

EN  54-14/2018

.  The  detectors  must  be 

placed at least 50 cm away from fluorescent lamps. Cable cross-section 

2

should be from 

0

.

to 

2

.

5mm .

 

After  installation  the  device  must  not  be  covered  with  dust  or  be 
painted or anything else happen that will block the air to get to the 
sensor. Special attention must be given during the installation and the 
use of the device, since the user assumes full responsibility for proper 
operation afterwards.

3

4

5

6

2

1

B

BS-66

1

/A

BS-66

1

/A

+

-

LED BS-572

CONNECTION DIAGRAM

1

2

3

4

Sealing rubber

IP65

ATTENTION!!!
DO NOT UNSCREW THE SENSOR’S LID

A