background image

GENERAL

This  device  is  a  sounder  for  fire  detection 
panels  that  offer  a  strong  sound  and  an 
optical warning with a  beacon that covers 
many  square  metres.

 

The  main  tone 

frequency is 2.5kHz (±20%).
This  device  can  co-operate  with  any  fire 
detection  panel  (BSR-2104,  BSR-2114, 
BS-1632, BS-1634, BS-1636, BS-636).

Installation and Connection
1.

  First,  remove  the  retaining  screw,  place 

a flat blade screwdriver in the holes  of the 
plastic hooks and remove the plastic cover 
(Image 1 on page 2).

 

2.

 Use the supplied mounting parts to install 

the  siren’s  base  on  the  wall.  Place  the 
plastic  plugs  and  fasten  the  screws  to  the 
mounting holes

.

3

.

 

Place  the 

caps

  and  make  a  hole  in  the 

center  using  a  small  screwdriver.

 

Pass

 

through  the 

caps

 

the 

cables  to  connect  the 

device.

 

4.

 

The  (

+

)

 

of    the  terminal  block  is

 

connected  to  the

  (

+

)

 

output  of

 

Alarm-1

 

or

 

Alarm-2

 

of  the  panel  and  the  (

-

)

 

of  the 

terminal block is connected to the

 (

-

)

 out

put 

o f  

A l a r m - 1

  o r  

A l a r m - 2

 

o f   t h e  

panel.Accordingly connect in parallel all the 
sirens.  (The  maximum  number  of  sirens 
depends on the  type  of the  panel).

5

.

 

On  the  last  siren  of  the  line,  we  must 

connect in parallel with its power cables, 
the  terminal  resistor  that  was  removed 
from the alarm contacts of the panel.

 

6

.

 

Refit  the  plastic  cover  until  the  plastic 

hooks are securely attached (step 1) and 
fasten  the  retaining  screw  (torque 
0.6Nm).

7.

 Test the device after installation.

Certification

The electronic fire alarm sounder BS-
531  is  certified  from  EVPU

Also

 

EVPU  controls  the  production  under

 

CPD number:

 

921531000_09_013

Page 1 from 2

Thank you for your trust in our products.  

Olympia Electronics -  European manufacturer

.

 

Β

S-53

1

SOUNDER WITH BEACON FOR 

 

FIRE DETECTION PANEL

21-28V DC

40mA

OPERATION VOLTAGE
MAXIMUM CONSUMPTION

MAXIMUM SOUND OUTPUT in

1

m

Τ

YPE OF APPLICATION ENVIRONMENT

MOUNTING

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS
TYPICAL WEIGHT 
GUARANTEE

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

CONSTRUCTION MATERIAL

TECHNICAL CHARACTERISTICS

IP

42

EN 54-3: 2014

0 to 60  C

o

Up to 95% 

200gr.

141

 

x 141 x 95 mm

2 years

Bayblend FR3010

transparent

 

polycarbonate

Τ

ype

 

A

Wall

88dB

BEACON

red

 

LEDs

BS-531

 Siren with beacon for

               fire detection panel

1293

1293-

CPD-0356                                         12

EN-54-3

P C

300 P.O. Box 06 Eginio Pierias Greece

. . 60

 

 

Отзывы: