background image

5

WARNING

Air openings to combustion area must not be 

obstructed. Provide adequate supply of combustion 

air in accordance with Installation Code for Oil 

Burning Appliances, CSA 139.

!

   

1. 

Ventilation of boiler room must be adequate enough to 

provide suf

fi

 cient air to properly support combustion 

and venting.

2. 

When the boiler is located in an uncon

fi

 ned space in a 

building of conventional construction frame, masonry 

or metal, in

fi

 ltration normally is adequate to provide 

air for combustion and ventilation. However, in any 

building which has been altered to conserve energy 

or to minimize in

fi

 ltration, the boiler area should 

be considered as a con

fi

 ned space. If there is any 

doubt, install air supply provisions for combustion 

and ventilation in accordance with requirements of 

authority having jurisdiction, or in the absence of such 

requirements, CSA B139: Installation Code for Oil 

Burning Equipment. 

3. 

When the boiler is installed in an uncon

fi

 ned space, 

in a building of unusually tight construction, air  for 

combustion and room ventilation must be obtained 

from outdoors or from spaces freely communicating 

with the outdoors. A permanent opening or openings 

having a total free area of not less than 1 square inch 

per 5,000 BTU per hour of total input rating of all 

appliances shall be provided. Ducts may be used to 

convey make-up air from the outdoors and shall have 

the same cross-sectional area of the openings to which 

they are connected.

Table 5   COMBUSTION AIR REQUIREMENTS

(Minimum Opening Requirement)

BTU/Hr 

Input

(Mbh)

Uncon

fi

 ned Area*

Con

fi

 ned Area**

Outside

Inside

Outside Combustion Air

Combustion Air 1 Sq.

 In./5000 BTU/Hr 

(Step 4)

Combustion Air 1 Sq. 

In./1000 BTU/Hr 

(Min. 100 Sq. In.) 

Vertical Ducts 1 Sq. 

In./4000 BTU/Hr 

(Figures 2 & 3)

Horizontal Ducts 1 Sq. 

In./2000 BTU/Hr 

(Figure 4)

133

27

133

33

67

140

28

140

35

70

161

32

161

40

81

  * A space whose volume is not less than 50 cubic feet per 1000 BTU/Hour of all appliances installed in that space (cubic feet of space = height x 

width x length)
** A space whose volume is less than 50 cubic feet per Mbh of all appliances installed in that space (cubic feet of space = height x width x 

length)

VENTS

CHIMNEY

OR

L TYPE VENT PIPE

VENT PIPE

BASEBOARD

12"

12"

Figure 2  Combustion and Room Air From Inside 

Buildings

VENTILATION AND COMBUSTION AIR

WARNING

Air openings to combustion area must not be 

obstructed. By following the instructions below, 

adequate combustion air can be maintained.

!

   

4. 

When air for combustion and room ventilation is from 

inside buildings, the con

fi

 ned space shall be provided 

with two permanent openings, one starting 12 inches 

from the top and one 12 inches from the bottom of the 

enclosed space. Each opening shall have a minimum 

free area of 1 square inch per 1,000 BTU per hour of 

the total input rating of all appliances in the enclosed 

space, but must not be less than 100 square inches. 

These openings must freely communicate with the 

interior areas having adequate in

fi

 ltration from the 

outside. See

  Figure 2 .

Содержание OBC II Series

Страница 1: ...T IRON BOILER INSTALLATION OPERATION MAINTENANCE MANUAL Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com P N 240009512 Rev A 04 2012 Models OBC3...

Страница 2: ...nts may result in personal injury or loss of life TO THE OWNER Installation and service of this boiler must be performed by a qualified installer TO THE INSTALLER Leave all instructions with boiler fo...

Страница 3: ...a to be heated select boiler on basis of its Heating Capacity 5 Nozzle listed for use with Beckett Burner 6 Electrical service to be 120 Volts 15 Amps 60 Hz STANDARD EQUIPMENT Crated Boiler Flush Jack...

Страница 4: ...l base as near chimney as possible and centrally located with respect to the heat distribution system as practical Allow 24 inches in front top and right hand side for servicing and cleaning or removi...

Страница 5: ...sectional area of the openings to which they are connected Table 5 COMBUSTION AIR REQUIREMENTS Minimum Opening Requirement BTU Hr Input Mbh Unconfined Area Confined Area Outside Inside Outside Combust...

Страница 6: ...d each opening shall have a minimum free area 1 square inch per 2 000 BTU per hour total input rating of all appliances in the enclosed space See Figure 5 D When ducts are used they shall be of the sa...

Страница 7: ...ng as suggested in Figure 6 When boiler is used in connection with refrigerated systems A Chilled medium MUST BE IN PARALLEL with boiler Figure 6 Boiler Used In Connection With Refrigerated System B U...

Страница 8: ...t the system or condition of the installation Although this method of piping is not typically required for baseboard heating systems A This method is used to protect systems using radiant panels and t...

Страница 9: ...9 CONNECTING SUPPLY AND RETURN PIPING Figure 9 Bypass Piping Option Used to Protect From Converted Systems With High Water Temperature Figure 10 Typical Installation With Circulators...

Страница 10: ...10 CONNECTING SUPPLY AND RETURN PIPING Figure 11 Typical Installation With Valves Figure 12 Typical Installation With DHW...

Страница 11: ...fety relief valve outlet and downstream of union if used Terminate pipe with plain end not threaded Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installatio...

Страница 12: ...chimney performance Chimney should extend at least 2 ft above any portion of building within 10 ft See Figure 15 It should produce a 06 to 08 inch W C draft as measured with draft gauge between boiler...

Страница 13: ...13 VENTING SYSTEM INSPECTION INSTALLATION P N 240005186 Rev 1 0 06 05 Figure 16 Final Placement Of Boiler With New Vent Safety Switch Installed...

Страница 14: ...ended E Compression fittings on suction line often allows air to be drawn into fuel pump making it difficult to maintain oil pressure at the nozzle F Do not run overhead fuel lines from tank to oil bu...

Страница 15: ...be installed on an inside wall about four feet above the floor 2 NEVER install a thermostat on an outside wall 3 Do not install a thermostat where it will be affected by drafts hot or cold pipes sunli...

Страница 16: ...16 WIRING DIAGRAMS Figure 19 Wiring Diagram...

Страница 17: ...ration Thermostat calls for heat Circulator turns on Limit checks boiler water temperature Burner ignition delayed until limit determines call for heat cannot be met by residual heat in boiler and hea...

Страница 18: ...h limit point Burner should start B Verify Primary Control and Flame Sensor Flame Failure simulate by shutting off oil supply with hand valve while burner is on Sixty seconds after flameout safety swi...

Страница 19: ...14 5 Disconnect oil line from burner Recommend replacing nozzle at start of each heating season Lubricate burner motor and circulator motor if required with few drops of good grade of light motor oil...

Страница 20: ...ECR International 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...

Отзывы: