Oliver IGD TOCSIN 102 SERIES Скачать руководство пользователя страница 1

EEx d IIC T6 Gb               
Rating 4W Max
Sira 02ATEX1271X

II 2 GD

IIIC

TOCSIN 102 4-20mA 2 Wire Gas Transmitter.

Fitting, Service and Maintenence

Explanation of Markings

Flameproof Housing Concept

Equipment Protection Level

Gas Group 

Maximum Housing Temperature Taking
Into Account Maximum Ambient Temperature

Ingress Protection Rating

6-Complete Protection From
    Live Components Inside
    Housing, Dust Ingress
    Protection
6-Protection Against
   Conditions On Ships Decks

Certificate Number

Maximum Rating Of
Internal Circuitry

Suitable For Use In
Zone 1 & 2 Areas
In Potentially Explosive
Atmospheres Due To Gases, Vapours
Mists or Dusts.

250 Ohms

Sense

18-28V DC

Typical Control Card
Connections

Use Lock
Nut Supplied

Fit Fibre
Washer

Check Supply Voltage And Load
Resistance With Card Manufacturers
Instructions.

Note
The Tocsin 102 Must Be Earthed, If necessary fit 
a brass earthing tab washer between the locknut 
and housing to bond to. Ensure the junction box, 
cable and glands carry appropriate certification 
for the area in which they are fitted. Cable 
screens should be earthed at the control panel 
and the bond checked to be <0.5 Ohms.

18

28

DC 
SUPPLY
VOLTS

R (Ohms)

200

800

Allowable
Operating
Region

There are no user serviceable components inside the Tocsin 102.

Do not connect to portable equipment

Under no circumstances should the housing be opened in a potentially hazardous 
atmosphere.

Calibration should be undertaken at a minimum of six monthly intervals.

Refer to Configurator manual for more advanced options, available from Oliver IGD 
Limited.

Do not overtighten 
the 102 into the 
junction box 
housing.

Mounting Thread 
M20 x 1.5

Black -Ve (0V DC)

Yellow RS232 Rx

White RS232 Tx
Red  +Ve (24V DC)

Blue  Signal 4-20mA Current Source

Observe Marked Warnings

Manufacturer

Environmental Rating

Test Body Report Number & Power

EEX d Hazardous area
ratings. Note change of rating
with change in ambient
temperature range.

Device Serial Number

EU 'CE' Marking and
ATEX Lab Number

IP66

DO NOT OPEN WHEN AN
EXPLOSIVE ATMOSPHERE
MAY BE PRESENT.
 

0518

II 2 GD

-20 C < Ta < +40 C

 

-20 C < Ta < +55 C

 

IP66

IP66

Serial Number T102-xxxxx-2002

Sira 02ATEX1271X  Rating 2W

Ex d IIC T6 Gb
Ex tb IIIC T6 Db

Ex d IIC T5 Gb
Ex tb IIIC T5 Db

OLIVER IGD Ltd

DO NOT OPEN WHEN AN
EXPLOSIVE ATMOSPHERE
MAY BE PRESENT.
 

0518

II 2 GD

-20 C < Ta < +40 C

 

-20 C < Ta < +55 C

 

IP66

IP66

Serial Number T102-xxxxx-2002

Sira 02ATEX1271X  Rating 2W

Ex d IIC T6 Gb
Ex tb IIIC T6 Db

Ex d IIC T5 Gb
Ex tb IIIC T5 Db

OLIVER IGD Ltd

Main Body Material of Construction
316 Stainless Steel.

Conductive Dusts

TOCSIN 102 SERIES GAS DETECTORS                           2 WIRE 4-20mA VERSIONS

0V mA

 +24V

T102 Sensor

PC

- mV +

Enclosure
Earth