Olimpia splendid Unico Скачать руководство пользователя страница 14

30

ENGLISH

To prevent the creation of large amounts of dust and rubble due to drilling, the core borer can be fitted with a vacuum system applied
by means of suction cups to the drilling zone. Our Service Department can give you all necessary information to enable you to
find these devices.
To drill the holes, proceed as follows:
Fasten the drilling template to the wall leaving the necessary space from the ceiling, floor and side walls as shown on the template
that may be fixed using adhesive tape.
Use a small drill or punch to mark, with extreme care, the exact centre of each of the holes to be drilled.
Using a core boring head measuring at least 162 mm to drill the two holes for entry and exit of the air.

WARNING: drill the foregoing holes tilted slightly downwards to prevent water from being fed back through the
ducts (fig. 5).

Most of the removed material is expelled outwards, therefore make sure that it does not hit any person or object when it falls out.
In order to avoid as much as possible outer plaster breaking, it is necessary to proceed carefully with the last part of hole execution,
decreasing pressure on core borers.

Next, drill the holes for anchoring the fastening brackets to the wall using as a first option the 4 holes on the ends of the bracket
as shown on the drilling template.

If the wall is not very solid, it is advisable to use some extra anchor bolts.
As you can see, the bracket can be fastened in a number of different ways and positions. The majority of the weight of the appliance
is to the right side so ensure that fixing is more secure on this side.The anchor bolts provided require holes with a diameter of
10 mm.

In any case, the wall should be inspected carefully to determine the best possible anchorage and type of bolts suitable for particular
situations.

WARNING

: the manufacturer will not be held liable for any underestimates made in the structural consistency of the anchor prepared

by the installer.
Therefore, pay utmost attention to the foregoing operation that could cause serious injury/damage to people/property if carried
out incorrectly.

When installing models equipped with heating pump, if no condensate discharge was built into the wall (see paragraph 2.3.2),
in order to drain the condensate it will be necessary to drill a hole through the wall in the position shown on the template.

2.3.3

Preparing the condensate discharge

As far as machines equipped with a heating pump are concerned, connect the unit to the condensate discharge pipe (supplied)
by coupling it with the specific vent (fig. 6 ref. A) that is on the back of the machine (remove cap B). When the max level is reached,
a solenoid valve ensures the condensate will flow out from the internal tray. For cold-only machines, connect the condensate
discharge pipe if you intend running the unit at low outdoor temperatures (lower than 23°C).
Since condensate drains by gravity, there must be a minimum slope of at least 3% at every point of the discharge line. Use a rigid
or flexible tube having an inside diameter of at least 16 mm.
If the line empties into a sewerage system, install a siphon before the point in which the pipe reaches the main discharge, at least
300 mm below the inlet from the unit (fig. 6).

If the drainpipe drains into a vessel (tank or other container), this container 

should not be sealed and the drainpipe should

not remain immersed in the water

 (see fig. 7).

The hole through which the condensate pipe passes should always slope towards the outside (see fig. 8).

The exact position in which to place the pipe inlet, as compared to the machine, is shown on the drilling template.

CAUTION: make sure, in this case, that the water expelled outward does not damage or disturb persons or
property. During the winter this type of drainage may cause sheets of ice to form.

When the condensate drainage is fitted, pay much attention not to compress the rubber hose.

2.3.4

Assembly of the air ducts and external grids

After having drilled the holes, insert the plastic sheet supplied with the conditioner into them.
Since the sheet was made for 202 mm holes, you will have to cut off 130 mm from the long side of the sheet for the 162 mm holes.

The length of the sheets must be 65 mm less than the thickness of the wall.

Roll the sheet and insert it into the hole (fig. 9), 

paying attention to the splicing line (fig. 9 ref. A), which must always face

upwards.

Use an ordinary cutter for the foregoing operation (fig. 9).
To position the external grids, proceed as follows:

-

Apply the seal (fig. 10 ref. B) to the wall flange (fig. 10 ref. A), ensuring it lines up with the outer edge of the flange as indicated
in the figure.

-

Fix the two flanges using 2 pegs having a diameter of 6 and check that the two fixing holes are horizontal.

-

Fit the small eyelet of the spring, with the long stem, on the cap pin (on both components) (fig. 11).

-

Insert the two caps (with spring), on the front part of the external grid, on its two housings, pulling until it clicks (fig. 12) and

2

Содержание Unico

Страница 1: ......

Страница 2: ...C TION S POU R L IN STA LLAT ION L EM PLO I ET L EN TRE TIEN HAN DBU CH F R INST ALL ATIO N GEB RAU CH UND WAR TUN G INST RUC CION ES PAR A LA INST ALA CI N USO Y MAN TEN IMIE NTO MAN UAL DE INST ALA...

Страница 3: ...3 UNICO 5 300 mm B A 6 7 8 A 9...

Страница 4: ...4 15 A 16 10 11 13 14 12 A B...

Страница 5: ...5 UNICO 17 18 B A A 19 N L N L A C B 20 A A D C B 21...

Страница 6: ...6 A B 25 22 H G LEDD LEDC LEDB LEDA 24 23 A B...

Страница 7: ...7 UNICO 26 A B C B D C A E F B A C 27...

Страница 8: ...8 28 1 2 M H AUTO F A N S E T AUTO T2 T1 T11 T8 T10 T9 T3 T7 T4 T6 T5 D10 D2 D4 D3 D1 D6 D8 D9 D7 D5...

Страница 9: ...NTENANCE user part 3 1 WARNINGS 34 3 1 1 Description of the warning panel 34 3 2 MANAGING THE UNIT WITH THE REMOTE CONTROL 34 3 2 1 Remote control 34 3 2 2 Fitting the batteries 34 3 3 REMOTE CONTROL...

Страница 10: ...he aim of providing you with all the explanations necessary to manage perfectly your conditioning system Therefore please read the manual carefully before using the equipment By following the suggesti...

Страница 11: ...emove the master plug from the mains before making any electrical connections or any other maintenance intervention on the appliances Make sure that all personnel responsible for transport and install...

Страница 12: ...registered letter with receipt within 3 days of receipt of the goods and enclosing photographic evidence Send the same information by fax to OLIMPIA SPLENDID No complaints will be accepted if made mor...

Страница 13: ...s to circulate both on the top air intake curtains plants furniture and at the front where the air exits This could cause air swirls that would inhibit the working efficiency of the unit The air condi...

Страница 14: ...te discharge As far as machines equipped with a heating pump are concerned connect the unit to the condensate discharge pipe supplied by coupling it with the specific vent fig 6 ref A that is on the b...

Страница 15: ...with plug Y type connection If the socket is in proximity to the appliance simply plug it in Before connecting the conditioner ensure that The power supply voltage and frequency values comply with tho...

Страница 16: ...on the right hand side in the opening fig 21 ref C and the flap s left hand hole on the lower pin that is on the left hand side in the opening fig 21 ref D After having performed the mechanical operat...

Страница 17: ...cond and third LEDs from the left the alarm status To enable the air conditioner to work temporarily until the service personnel arrive you can drain the water out by following these simple instructio...

Страница 18: ...set forth by law The installation instructions are contained in the appropriate paragraph of this manual No structural object furniture curtains plants leaves blinds etc should ever obstruct the norma...

Страница 19: ...Description of the remote control Buttons fig 28 used to set or bring up machine functions T1 ON OFF standby T2 Well being key automatic T3 Night well being mode T4 Operating mode selector T5 Fan spe...

Страница 20: ...unction intermittently 3 3 7 Ventilation only When used in this mode the air conditioner does not perform any action with regard to temperature and air humidity in the room Activate this mode by press...

Страница 21: ...ant the air conditioner to start shortly before you return home so that it is cool when you get there To use these functions it is first necessary to set the exact time on the remote control and then...

Страница 22: ...ed rooms Keep sunlight out of the room by using curtains lowering the shades or closing the shutters Do not obstruct the air flow channels both inlet and outlet of the unit apart from preventing the o...

Страница 23: ...d correct it if need be Check the air filter and clean it if necessary Remove anything that might clog the air flows The unit does not turn on The unit does not cool or heat adequately No power supply...

Страница 24: ...on rating of the containers Max working pressure Dimensions W x H x D mm 902x516x229 Weight without packing kg 40 OPERATIONAL LIMITS Internal ambient temp Outside ambient temp Maximum operating temper...

Страница 25: ...g Do not insert the fingers or foreign objects into the air inlet or outlet grills as this may cause electric shock fire or damage to the fan heater To prevent fire do not block or tamper with the gri...

Отзывы: