Bi2 Air
EN - 13
ENGLISH
The appliance connection MUST respect the European and national standards
and MUST be protected by a 30 mA differential switch.
&RQQHFWLRQWRWKHPDLQVVXSSO\FDQEHFDUULHGRXWZLWK¿[HGFRQQHFWLRQRUZLWKPRELOHSOXJDQG
MUST be equipped with an omnipolar switch compliant with the current IEC EN standards, with
a contact opening of at least 3mm (better if equipped with fuses).
Correct connection to the ground system is essential to ensure safety of the
appliance.
:LULQJGLDJUDPNH\¿JDE
H2:
Water temperature probe
AIR:
Air temperature probe
M1:
Fan motor
M2:
Flap motor (only for models with Flap)
Y1:
Hot water 230V-50Hz solenoid valve, max
10W
F1:
Fuse
L:
Line
N:
Neutral
S2:
Presence contact input
A:
Presence contact input
B:
Presence contact input
D1:
Visualization display
D&RQ¿JXUDWLRQ
7KHSULQWHGFLUFXLWERDUGPXVWEHFRQ¿JXUHGGHSHQGLQJRQWKHW\SHRILQVWDOODWLRQDQGEDVHGRQSDUWLFXODU
operating preferences of the machine.
7KHWKUHHVHOHFWRUV--DQG-LQGLFDWHGLQ¿JDEPXVWEHVHWDVGHVFULEHGEHORZ
J1.
ON (for appliances with radiant panel, SLR type): in night mode and ambient temperature close to
the desired one, room heating occurs through natural convection and irradiation, as in traditional
radiators (under these conditions ventilation is inhibited for maximum acoustic comfort);
J1.
OFF (for appliances without radiant panel, SL type): heating occurs always through forced convection,
with activation active also in night mode (at reduced speed).
J2.
ON: in cooling mode, the fan remains powered even when the desired ambient temperature is
reached.
J2.
OFF: in cooling mode, the fan is deactivated upon reaching the set temperature.
J3.
ON (appliances to be installed in 2-pipes systems): the board is set for management of a single water
valve for summer (cooling) and winter (heating) operation.
J3.
OFF (appliances to be installed in 4-pipes systems): the board is set for management of two water
valves, one for summer (cooling) operation and one for winter (heating) operation.
The three selectors can be positioned in all the possible combinations since the respective
functions are independent from each other.
At each reactivation, the display shows the code corresponding to the setting of the internal selectors for
5 seconds:
D1
C0
C1
C2
C3
C4
C5
C6
C7
J1
OFF
OFF
OFF
OFF
ON
ON
ON
ON
J2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
J3
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Содержание Bi2 Series
Страница 2: ......
Страница 5: ...2 6 8 1 4 3 3 7 5 9 10 Min 20 Min 20 Min 400 B A Min 80 Min 400 Min 80 Min 400 1 2...
Страница 6: ...T T S S 2 1 4 3 6 5 7...
Страница 7: ...T S S v T S 9 8 10 17 15 16...
Страница 8: ...11 13 12 18 9 19 25 12 23 24...
Страница 9: ...14 15 26 26 7 7a 26 26a...
Страница 10: ...17 27 27 16 27a 27a 27a 17 17a 27 27b 17 27a...
Страница 11: ...18 28 19 29...
Страница 13: ...M M 230Vac 50Hz 20b 21...
Страница 14: ...23 22 40 41 41 41 40 40a 40a 42 40 42a 40a 41 41...
Страница 87: ......
Страница 88: ...279930F...