background image

GENERAL

o

These  devices  are  used  indoors 

(

ta  40 C

)

 

in places where emergency luminaires are 
needed.  The  luminaires

 

GR-470/WP  and 

GR-472/WP  are  suitable  for  corridors 
lighting  and  the

 

GR-471/WP  and  GR-

473/WP  for  open  area  lighting

.

  Each 

device  must  be  permanently  connected  to 
mains  power  supply

.

  In  normal  operation 

the battery is charging. In case  of a mains 
power  supply  failure    the  device  will  light 
the  illumination  led  automatically  in 
emergency mode. When the  mains  power  
supply  is  restored  the  device  turns  to 
normal operation.

INSTALLATION

To install the luminaire follow the 
installation instructions 

ο

n page 2.

ΑΤΤΕΝΤΙΟΝ

1. Operations for installation, maintainance 
or  testing  must  be  done  by  authorized 
personel only

.

2. 

The  device  must  be  connected  to  the 

mains power supply thru a fuse dependent 
by  the  total  amount  of  the  line’s    power 
load

.

3. 

It is suggested to check every month the 

indication LED for battery charging, and by 

!!!

placing  the  test  card 

  (page  5)  an 

operation test is initiated, to check the 
emergency  cirquit.  The  illumination  source 
should  light  as  long  as  the  card  is  present

4. 

It  is  sugested  to  check  every  6  months 

the  minimum  autononous  duration  by 
disconnecting  the  mains  power  supply

.

 

 

Count the time that  the luminaire lights and 
in  case  of  less  time  than  the  minimum 
autonomous  duration  the  battery  must  be 
r e p l a c e d .   I f   t h e   m e a s u r e d   t i m e   i s  
considerably  less  than  the  minimum 
autonomous duration 
  I n   c a s e   o f   b a t t e r y   o r   l i g h t   s o u r c e  
replacement,  these  must  be  replaced  by 
parts of the same type, by the manufacturer 
or by a competent person.

t i

 

in  battery 

recycling points. Do not incinerate.

(

A-1900)

In  the  opposite  condition  contact  the 
installer.

 

 

contact the installer.

5. 

In  case  of  inactive  use  for  a  period 

greater  than  2  months,  disconnect  the 
b a t t e r y   b y   p u l l i n g   o u t   t h e   b a t t e r y ’s  
connector.

 

6. 

I s not allowed to discard batteries in 

to  common  trash  bins,  they  must 
be  discarded  only 

Page

 1

 from 6

 

923473000_0

9

_00

1

 WATERPROOF NON-MAINTAINED LUMINAR

IES

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL

EXTERNAL DIMENSION
WEIGHT
GUARANTEE

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY

 (

Ni-Cd

)

CHARGE TIME

INDICATIONS 

BATTERY PROTECTION

MINIMUM DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

24 hours

 

Charge LED, Magnetic Test

 

Contact 

Deep discharge and overcharge protection

IP65

3,6V/1

 

Ah

1

 

white

 

power LED

2,

6

W / 2

,9

VA

5

 to 40  C

o

Up to 95% 

3 years

 (1 

year for the battery

)

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

3 hour

1,5

 hour

  145lm 

  80lm 

470gr.

220-240V AC

 

/ 50-60Hz

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 4)

Thank you for your trust in our products.  

Olympia Electronics -  European manufacturer

.

 

GR-47

0

/WP

 

GR-471/WP

 

GR-472/WP

 

GR-473/WP

158 x 158 

x

 60,4mm (

without decorative bezel

)-195 

x

 1

95

 

x

 60,4 (

with decorative bezel

)

ABS/PC

PC

Содержание GR-470/WP

Страница 1: ...ed If the measured time is considerably less than the minimum autonomous duration In case of battery or light source replacement these must be replaced by parts of the same type by the manufacturer or by a competent person t i in battery recycling points Do not incinerate A 1900 In the opposite condition contact the installer contact the installer 5 In case of inactive use for a period greater tha...

Страница 2: ... in order to preserve the IP rating Install the cable grommet in the open hole of the plastic base and open a hole in the center of the grommet using a small screw driver Pass the power cable through the hole in the grommet If required open another cutout cable entry hole and install the second supplied cable grommet Connect the cables as shown in the photograph Use the supplied self adhesive pad ...

Страница 3: ... brackets with the four screws figure 3 4 Mark the positions of the mounting holes on the brackets 5 Install the two supplied plaster board plugs by screwing them on the plaster board ceiling 6 Open a cable entry cutout hole on the plastic base and follow step 3 in the initial installation section 7 Re install the front cover that was removed in step 1 8 Use the supplied screws to fasten the lumin...

Страница 4: ...n the desired mounting location and mark and drill these 4 holes Fit the supplied 4 plastic mounting plugs to these drilled holes on the mounting location 4 If the cable entry hole is not suitable then use one of the supplied cables grommets to cover the holes and open another cable entry cut out hole figure 3 Follow step 3 of the initial installation procedure 5 Mount the base to the desired loca...

Страница 5: ...In order to test the device you must place the card in front of the indications TEST mark and remove it instantly for TEST GR 470 WP GR 471 WP GR 472 WP GR 473 WP CAUTION Do not view directly with bare eyes Battery replacement It can be done only by a competent person and after the mains interruption 3 Disconnect the connector and remove the old battery 4 Connect the new battery with the same type...

Страница 6: ...any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or replacement as long as the warranty period is valid Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defe...

Отзывы: