GENERAL
The user have to read carefully the following instructions, in order to be properly informed and keep them
for future use.
The
BSR-6
1
60
is an analogue addressable heat detector which integrates the function of rate-of-rise
heat detection and it can work with any fire panel supports Olympia A Protocol. It can be adjusted to detect
multiple levels of heat offering flexibility and rich functionality. Also, it integrates a short circuit isolation
circuit which is automatically activated and disconnects the defective node from the remaining loop,
allowing it to be located by the panel.
The detector sends to the main panel an analogue value which depends on the heat. The value is 100 at
o
o
57 C
and increases proportionally to 120 at 90 C. When a sudden increase in temperature is detected the
detector sends the value of 121.
By default the panel is set to sound an alarm when the temperature is 57 C. The user can change this
setting from the panel for each detector and define any level of temperature between the lower and the
upper limits, specifying the sensitivity of the system depending on the requirements of each site. Also, the
user can select A1R or A1S working mode through the panel.
They are composed by two parts. A plastic base which is placed on the ceiling and the main body of the
o
detector which fits on the plastic base with a simple rotation to the right. The detectors have a 360 visible
led and a remote led driver which are light up constantly in case of detection of fire, till cancelled from the
panel. Also, they are staying lit even if the sirens are silenced from the panel, so the detector which
detected the alarm is visible. They are turned off only when a reset command is given from the panel. The
indicator led blinks every 10 sec indicating the connection status with the main panel.
o
Analogue addressable
rate-of-rise heat detector
with integrated isolator
Thank you for your trust in our products
Olympia Electronics - European manufacturer
TEMPERATURE SENSITIVITY
INDICATORS
OUTPUT
MAXIMUM LOOP CURRENT
(
Ic max, -L in/out)
MAXIMUM SWITCH CURRENT
(
Is max, -L in/out)
MAXIMUM SERIES RESISTANCE
(
Zc max, -L in-out
)
MAXIMUM LEAKAGE CURRENT
IN ISOLATION MODE
(
I max, -L in/out
)
L
ISOLATION VOLTAGE
(
Vso min-max
)
RECONNECT VOLTAGE
(
Vsc min-max
)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATING TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
1A
5
A
IP
42
EN 54-5 EN 54-17
,
100
m
Ω
Adjustable from
57
to
90
in
1
.
5
steps
o
C
10.7 - 12.7
9.3 - 10.6
Up to
95%
ο
-
40
to
7
0
C
ABS/PC
145
gr
.
103 (
d) x
48
(h) mm
2
years
Remote
LED driver
Alarm LED
2
5mA pulses (6ms duration every
2
sec)
90
μΑ
1
1
-30
V DC
2.5mA (with
activated LED)
TECHNICAL CHARACTERISTICS
MAIN VOLTAGE
STANDBY CONSUMPTION
ALARM CONSUMPTION
CLASS
A1R/A1S
Olympia A Protocol
COMMUNICATION PROTOCOL
921
6
1
60
00_0
9
_00
2