Olimpia electronics BSR-6160 Скачать руководство пользователя страница 1

BSR-

6160

   

Page

 1

 from

 4

GENERAL

The user have to read carefully the following instructions, in order to be properly informed and keep them 
for future use.

The 

BSR-6

1

60

 is an analogue addressable heat detector which integrates the function of rate-of-rise 

heat detection and it can work with any fire panel supports Olympia A Protocol. It can be adjusted to detect 
multiple levels of heat offering flexibility and rich functionality. Also, it integrates a short circuit isolation 
circuit which is automatically activated and disconnects the defective node from the remaining loop, 
allowing it to be located by the panel.
The detector sends to the main panel an analogue value which depends on the heat. The value is 100 at 

o

o

57 C

 

and increases proportionally to 120 at 90 C. When a sudden increase in temperature is detected the 

detector sends the value of 121.
By default the panel is set to sound an alarm when the temperature is 57 C. The user can change this 
setting from the panel for each detector and define any level of temperature between the lower and the 
upper limits, specifying the sensitivity of the system depending on the requirements of each site. Also, the 
user can select  A1R or A1S working mode through the panel.
They are composed by two parts. A plastic base which is placed on the ceiling and the main body of the 

o

detector which fits on the plastic base with a simple rotation to the right. The detectors have a 360  visible 
led and a remote led driver which are light up constantly in case of detection of fire, till cancelled from the 
panel. Also, they are staying lit even if the sirens are silenced from the panel, so the detector which 
detected the alarm is visible. They are turned off only when a reset command is given from the panel. The 
indicator led blinks every 10 sec indicating the connection status with the main panel.

o

Analogue addressable

 

rate-of-rise heat detector

with integrated isolator

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

TEMPERATURE SENSITIVITY

INDICATORS

OUTPUT

MAXIMUM LOOP CURRENT

 (

Ic max, -L in/out)

MAXIMUM SWITCH CURRENT

 (

Is max, -L in/out)

MAXIMUM SERIES RESISTANCE

 (

Zc max, -L in-out

)

MAXIMUM LEAKAGE CURRENT
IN ISOLATION MODE 

(

I max, -L in/out

)

L

 

ISOLATION VOLTAGE

 (

Vso min-max

)

RECONNECT VOLTAGE

 (

Vsc min-max

)

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

OPERATING TEMPERATURE RANGE
RELATIVE HUMIDITY

CONSTRUCTION MATERIALS

EXTERNAL DIMENSIONS

TYPICAL WEIGHT
GUARANTEE

1A

5

A

IP

42

EN 54-5 EN 54-17

100

m

Ω

Adjustable from

57 

to

 90 

in 

1

.

5

 steps

 

o

C

10.7 - 12.7

9.3 - 10.6

Up to

 95%

ο

-

40 

to

 7

0

  C

ABS/PC

145 

gr

.

103 (

d) x 

48

 (h) mm

years

Remote

 

LED driver

Alarm LED

2

5mA pulses (6ms duration every 

2

sec)

90

μΑ

1

1

-30

V DC

2.5mA (with

 

activated LED)

TECHNICAL CHARACTERISTICS

MAIN VOLTAGE

STANDBY CONSUMPTION

ALARM CONSUMPTION

CLASS

A1R/A1S

Olympia A Protocol

COMMUNICATION PROTOCOL

921

6

1

60

00_0

9

_00

2

Отзывы: