3
– Installation and wiring
7
Chapter 3
│ Installation and wiring
Mounting the controller
The
MX 15
should be mounted on a DIN rail (see Figure 3), with 5 cm of free
space on every side of the controller.
The
MX 15
controller may be installed in any area except for explosive
atmospheres, ideally in a monitored area (security office, control room,
equipment room, etc.), in a dry (no condensation) and temperate area (see
page 23).
The unit’s access panel should be forward facing, so that settings, monitoring
and wiring can be easily accessed.
Figure 4: Dimensions of the controller
Wiring
Also refer to the
Particular Specifications
chapter on page 25.
The controller meets Class II surge protection and Degree 2 pollution
requirements.
The electrical connection must:
■
Be carried out by a specialist and (with the controller) with the power
supply disconnected (electric power cut) ;
■
Respect the current regulations (NF C 15-100) ;
■
Use a power cable connected to the grid (230 VAC) with a minimum
diameter of 1.5 mm² and a maximum diameter of 2.5 mm
2
.