OJ Electronics PTH Series Скачать руководство пользователя страница 1

Type PTH

INSTRUCTIoNS

English

PTH is a series of electronic pressure transmit-

ters designed primarily to measure total and 

differential air pressures in ventilation systems. 

The resulting measurements are used for 

monitoring, control and regulation purposes via 

a regulator, PLC or monitoring system. The re-

sulting measurements are used for monitoring, 

control and regulation purposes via a regulator, 

PLC or monitoring system. 

Typical applications include:

- The maintenance/control of constant pressure 

at a given position within the duct system. 

- The maintenance/control of desired under-

pressure within the duct system.

- The measurement of pressure differentials 

across filters to determine optimum filter 

replacement time.

- Flow determination via differential pressure 

measurements across a standard aperture. 

PRoDUCT PRoGRAMME

Type Product

PTH-3202 

Pressure transmitter, 

 

0-2500 Pa, 1 channel, IP54

FUNCTIoN

PTH is a pressure transmitter for comfort 

ventilation systems. It provides an active current 

or voltage signal proportional to the measured 

air pressure. PTH consists of semiconduc-

tor elements. There is no air throughput and 

the unit is thus protected against dust in the 

ventilation system. The pressure element is 

temperature compensated to provide accurate 

pressure measurement throughout the specified 

temperature range. 

The required measuring range of the pres-

sure transmitter is set with DIP switches. The 

output signal can be changed from voltage 

[V] to current [mA] by setting a jumper. A DIP 

switch allows two different damping times to be 

selected so that pressure fluctuations within the 

ventilation system are attenuated in the trans-

mitter output signal. A green LED indicates that 

supply voltage has been connected correctly. 

If the actual pressure is outside the selected 

measuring range, the green LED flashes. 

CE MARKING

OJ Electronics A/S hereby declares that the 

product is manufactured in accordance with 

Council Directive 92/31/EEC on electromagne-

tic compatibility (and subsequent amendments) 

and Council Directive 73/23/EEC on electrical 

equipment designed for use within certain 

voltage limits.

Applied standards

EN 61000-6-2 and EN 61000-6-3

Electromagnetic compatibility (EMC)

TECHNICAL DATA

Full scale pressure range  PTH-3202 / 0-2500 Pa

Pressure ranges ................ PTH-3202 (see fig. 5)

Supply voltage  ............24 V AC ±15%, 50/60 Hz

 

 

13.5-28 V DC

Own consumption (-20/+40°C)  ...... max. 0,5 VA

Output signal (selectable)  ................. 0-10 V DC, 

 

 

2-10 V DC

 

 

4-20 mA, 0-20 mA

Accuracy output signal ........................................  

1.5 %xMV+0.3 %xSR+2.5 Pa 

(MV = measured value / SR = set measuring range)

Dampening (selectable)  .................  0.4 s or 10 s

Max. pressure  ..........................................20 kPa

Ambient temperature ......................... -20/+40 °C 

 

 

(constant operation)

 

 

-30/+50 °C (transient)

Dimensions  .............75 x 36 x 91 mm (see fig. 1)

Cable dimensions   ................. 4 x max. 1.5 mm2

Pressure connector  ........................2 x ø6.2 mm

Enclosure ..................................................... IP54

MoUNTING

PTH must be securely mounted on a level surfa-

ce using screws. PTH is insensitive to mounting 

orientation. However, in order to maintain the 

specified enclosure, tubes should be attached 

to both tube connectors if the connectors point 

upwards. The enclosure is equipped with screw 

holes, see fig. 1.

Pressure is connected by means of tubes. 

The higher pressure must be connected to the 

“+ connector” and the lower pressure to the 

“- connector”. If the tubes are unintentional-

ly exchanged, or the pressure is outside the 

measuring range, the green LED flashes. See 

table 1. The pressure tubes must be as short 

as possible and must be secured in position to 

prevent vibration. To obtain the best possible 

results, pressure must be measured where 

there is least risk of turbulence, i.e. in the centre 

of the ventilation duct and at a suitable distance 

from bends and branches. See fig. 2.

The enclosure is opened without the use of 

tools by pressing the snap lock at the side of 

the connectors. The transmitter cable may be 

up to 50 m in length and must be connected as 

shown in fig. 3. The transmitter cable must be 

kept separate from mains-carrying cables as 

voltage signals from these may affect transmit-

ter function. 

SETTINGS

Pressure range is set by turning the dial, SW2 

(see fig. 3)

PTH types in this product series, pressure range 

can be set to 8 different intervals, ranging from 

-50/+50 Pa to 0-2500 Pa (see fig. 5).

If the dial is set to values other than the speci-

fied positions (0-7), the pressure transmitter will 

interpret the setting as position 7 corresponding 

to the highest pressure range. 

If the pressure transmitter is inadvertently set 

to a pressure range lower than the pressure 

encountered in the connectors, the green LED 

will light constantly (see table 1). 

The screw terminals of the pressure transmitter 

can provide a 0/2 - 10 V output signal and/or a 

0/4 - 20 mA output signal (see fig. 4).

The 0-10 V output signal is provided by terminal 

2 with DIP 1 of SW1 in position “Off”.

The 2-10 V output signal is provided by terminal 

2 with DIP 1 of SW1 in position “On”.

The 0-20 mA output signal is provided by termi-

nal 4 with DIP 1 of SW1 in position “Off”.

The 4-20 mA output signal is provided by 

terminal 4 with DIP 1 of SW1 in position “On” 

(see figs 4 & 7).

Output signal damping time can be set to 0.4 

s or 10 s using DIP2 of SW1 (see figs 3 & 8). 

The transmitter measures the pressure several 

times within the set time and the output signal 

consists of the average of these measurements. 

This allows any pressure fluctuations within 

the ventilation system to be dampened in the 

transmitter output signal. 

ZERoING

The transmitter can be zeroed after it has 

been mounted and the power supply con-

nected. Before zeroing the transmitter, it is 

important to ensure that the pressure on the 

+ and - connectors is equal (e.g. by stopping 

the ventilation system). If the yellow LED is 

constantly lit, the transmitter is measuring a 

differential pressure of more than 50 Pa. This 

may be caused by unintended pressure within 

the system (draughts or compressed tubing). It 

is recommended that tubes be removed from 

the + and - connectors during zeroing. Zeroing 

is activated by pressing the integrated zero-set 

switch (see fig. 3), after which the yellow LED 

will continue to flash until zeroing has been 

completed. 

LED INDICATIoN

The green LED is lit when the power supply has 

been connected correctly and flashes when the 

actual pressure is above or below the selected 

measuring range. The yellow LED is lit if pres-

sure exceeds 50 Pa and flashes for approx. 3 

seconds during zeroing. 

Table 1

LED on 

on

Flashing

off

Green OK

Pressure outside 
set range

No supply

Yellow >0,5 mbar Zeroing in progress <0,5 mbar

FIGURES

Fig. 1: Dimensioned sketch 

Fig. 2: Transmitter position in relation to bends 

and branches 

Fig. 3: PCB component positions 

Fig. 4: Wiring diagram

Fig. 5: Selection of pressure range: PTH-3202

Fig. 6: Selection of output voltage/current

Fig. 7: Selection of damping time 

Fig. 8: Free DIP switch 

Bailey & Mackey Ltd

Baltimore Road

Birmingham B42 1DE

Tel: 0121-357 5351 · Fax: 0121-357 8319

www.baileymackey.com

57433B 03/14  (OSH)

 © 2012 OJ Electronics A/S

1

Отзывы: