14
Status
Settings
Setting
Description
Interval
temperature compensation
Actual pressure
Actual measured pressure
xxx Pa
is displayed. Is shown auto-
matically whenever constant
pressure controller
is not being operated.
Outside temp.
Display of actual outside
xx,x °C
temperature. Only active
if outside temperature
compensation has been
selected.
See settings
Back
See settings
Setpoint
120 Pa
Current setpoint and actual
Actual
xxx Pa
measured pressure are
displayed.
Motor speed
Actual motor speed signal
Signal
xx%
is displayed.
Pressure transducer
The constant pressure
0-150 Pa
controller must always be set
for the same pressure range
as the pressure transducer.
Motor, signal
Setpoint for max. motor
Max
100%
speed signal.
Motor, signal
Setpoint for min. motor
Min
20%
speed signal.
Controller
Setpoint for controller
Amplif. 20
amplification. The higher the
amplification, the quicker the
controller will respond, but
the greater will be the risk of
oscillation. The lower the
amplification, the slower the
controller will respond, but
the lower will be the risk of
oscillation.
Alarm limit
Pressure fluctuations within
Δ
Pa
±70 Pa
the
Δ
Pa alarm limit setting
will not activate an alarm.
Alarm limit
An alarm is activated if
Min. dur. 300 s
pressure continuously
exceeds the
Δ
Pa alarm limit
setting for longer than the
min. duration setting.
Language
Selection of menu language.
English
Back
Return to status display.
Change settings
Enter password
The underlying settings
----
are password protected.
Enter 1234 for access.
Back
Return to status display.
Setpoint day
Adjustment of setpoint
30 - pressure transducer
120 Pa
for daytime operation.
max Pa
Table 1. Constant pressure controller status and settings displays