3

ETO2 is an electronic controller for fully automatic, economical 

ice and snow melting on outdoor surfaces and in gutters.  

Ice forms due to a combination of low temperature and 

moisture. ETO2 detects both temperature and moisture, and the 

ice and snow melting system will usually only be activated if ice 

or snow is present. ETO2 is suitable for controlling both electric 

heating cables and hydronic heating pipes.

Product programme

ETO2-4550  

Thermostat. 

ETOG-55  

 Ground sensor for detecting temperature 

and moisture. 

ETOG-56/ETOK-1   Embedded ground sensor for detecting 

temperature and moisture. 

ETOR-55 

 Gutter sensor for detecting moisture.

ETF-744/99 

 Outdoor sensor for detecting temperature. 

ETF-522 

 Water pipe sensor for detecting 

temperature.  

WARNING! – Read this manual!  

Carefully read this instruction manual in its entirety, 

paying close attention to all the warnings listed below. Make 

sure that you fully understand the use, displays and limitations 

of the controller because any confusion resulting from 

neglecting to follow this instruction manual, or from improper 

use of the device it concerns, may cause an installer to commit 

errors which could lead to ice and snow conditions capable of 

causing serious injury or death.

WARNING! – Note that snow, ice and icicles may be 

present even though you follow the instructions 

contained in this manual. 

You are strongly advised to monitor any unexpected build-up of 

snow, ice or icicles. As an additional safety measure, you should 

always perform a manual inspection of public areas in order to 

ensure safe access to the controlled areas.

WARNING! – Important safety instructions.

Disconnect the power supply before carrying out 

any installation or maintenance work on this control unit and 

associated components. This control unit and associated 

components should only be installed by a competent person 

(i.e. a qualified electrician). Electrical installation must be in 

accordance with appropriate statutory regulations.

 

NOTE! – The output relays are potential free. The 

installer must connect a power source, e.g. from an 

electrical panel.

CE MARKING FOR EU

OJ Electronics A/S hereby declares that the product is 

manufactured in accordance with Council Directive 2004/108/

EC on electromagnetic compatibility (and subsequent 

amendments) and Council Directive 2006/95/EEC on electrical 

equipment designed for use within certain voltage limits.

Applied standards

ETO2-4550-EU28: 

CE marking LVD/EMC: EN60730-2-9

ETO2-4550-US28: 

CAN/CSA E 60730-2-9:01. 

ETO2-4550-RU28: 

CE marking LVD/EMC: EN60730-2-9

The product may only be used if the complete installation 

complies with current directives.

The product carries a manufacturer’s warranty if installed in 

accordance with these instructions and current regulations.

If the product has been damaged in any way, e.g. during 

transport, it must be inspected and checked by authorised 

personnel before being connected to the power supply.

TECHNICAL DATA

Thermostat ETO2-4550:

Designed for indoor mounting only! 

Supply voltage ............................115/240 V AC ±10%, 50-60 Hz

Supply voltage for ETOG/ETOR heating (SMPS) ..28 V DC, 8 VA

3 output relays (potential-free contact, NO) ...................3 X 16 A

Alarm relay (potential-free contact, NO) ........................ max. 5 A 

Control signal to actuator (mixing valve) .....................0-10 V DC

English

Instruction

Содержание ETO2

Страница 1: ...customers with the best controls in the industry WarmlyYours sells this product under part number SCE 120 The control s manufacturer identifies this same part with the model number of ETO2 in all the...

Страница 2: ...Type ETO2 Controller for ice and snow melting 67221 12 13 JRK 2013 OJ Electronics A S GREEN COMFORT Maximum comfort with low energy consumption English Fran ais...

Страница 3: ...013 OJ Electronics A S 2 I N S T R U C T I O N Type ETO2 INSTRUCTIONS English 3 6 Fran ais 7 12 USER MANUALS English 13 20 Fran ais 21 28 MENU OVERVIEW Menu overview 29 ILLUSTRATIONS Illustrations 30...

Страница 4: ...ion of public areas in order to ensure safe access to the controlled areas WARNING Important safety instructions Disconnect the power supply before carrying out any installation or maintenance work on...

Страница 5: ...nt temperature 40 248 F 40 120 C Dimensions L 0 26 1 97 Inches 6 5 50 mm NOTE The snow and ice melting system is deactivated in the event of sensor failure regardless of sensor type SENSOR INSTALLATIO...

Страница 6: ...ETOR sensors to terminals 11 20 Note that the pink and grey wires are not used Connect heating cable for zone 1 to potential free output relay 1 according to fig 8 Connect heating cable for zone 2 to...

Страница 7: ...mote control of standby and forced heat Fig 16 ETO2 controller terminal overview REMOTE CONTROL fig 15 The forced heat and standby functions can be remotely con trolled by wiring ETO2 to external butt...

Страница 8: ...contenues dans ce manuel Nous vous incitons fortement contr ler toute accumulation inattendue de neige de glace ou de gla ons Comme mesure de protection suppl mentaire vous devriez toujours effectuer...

Страница 9: ...tion Humidit Montage Goutti re ou tuyau de descente d eaux pluviales Norme du bo tier NEMA 6P IP 68 Temp rature ambiante 57 158 F 50 70 C Dimensions H L P 4 13 1 18 0 51 Inches 105 30 13 mm Sonde d ex...

Страница 10: ...Raccordez 1 ou 2 sondes ETOG aux bornes 11 20 Raccordez le c ble chauffant aux relais de sortie libres de potentiel 1 2 et 3 selon la fig 8 Contr le de chauffage lectrique 1 zone avec ETOR ETF fig 4...

Страница 11: ...e robinet m langeur fig 6 11 13 16 Raccordez 1 ou 2 sondes ETOG aux bornes 11 20 fig 6 Raccordez l alimentation externe de tension 24 V CA pour le robinet m langeur aux bornes 25 26 fig 13 Raccordez l...

Страница 12: ...Fig 3 Chauffage lectrique d une zone avec la sonde ETOG Fig 4 Chauffage lectrique d une zone avec la sonde ETOR ETF Fig 5 Chauffage lectrique de deux zones toit sol Fig 6 Connexion ETOG Fig 7 Connexi...

Страница 13: ...2013 OJ Electronics A S 12 I N S T R U C T I O N Type ETO2 Fran ais instruction...

Страница 14: ...ing systems Afterrun The heat provided by the system for a specified length of time after the moisture temperature signal has been eliminated by a heating cycle INTRODUCTION Type ETO2 is an electronic...

Страница 15: ...ssing the encoder button SENSOR 2 OFF ETOG ETOR SENSOR 2 is then shown on the display allowing the type of sensor connected for input 2 to be selected If no sensor is connected to input 2 OFF must be...

Страница 16: ...XIT DISPLAY TEXTS ZONE 1 OFF Heating zone 1 active ON or inactive OFF ZONE 2 OFF Heating zone 2 active ON or inactive OFF SENSOR 1 C Sensor 1 heated sensor core temperature Applies only when ETOG sens...

Страница 17: ...be selected here Select the required scale and press OK Press OK to return to the SETUP menu Set temperature for zone 1 The temperature at which the ice and snow melting system will become active can...

Страница 18: ...ing the encoder button Press OK The minimum return water temperature can be set here Set the required minimum temperature and press OK This menu option is only available when hydronic heating is used...

Страница 19: ...r heating of the ETO2 2 Wait a few hours until the sensor has acquired the same temperature as the ground 3 Measure the real ground sensor temperature and compare it with the temperature shown on the...

Страница 20: ...EAT o An igloo effect has occurred around the sensor The ground sensor has melted an insulated cavity under the snow Activate FORCE HEAT or set MOIST CTRL to OFF o The temperature is lower than the OF...

Страница 21: ...2013 OJ Electronics A S 20 I N S T R U C T I O N Type ETO2 English User Manual...

Страница 22: ...age lectrique Post chauffage La chaleur fournie par le syst me pendant une dur e sp cifique apr s que le signal d humidit temp rature a t limin par un cycle de chauffage INTRODUCTION Le type ETO2 est...

Страница 23: ...SENSOR 2 OFF ETOG ETOR SENSOR 2 est alors affich l cran afin que se fasse le choix du type de sonde raccord e l entr e 2 S il n y a pas de sonde de raccord e l entr e 2 OFF arr t doit tre s lectionn...

Страница 24: ...Chauffage de la zone 1 actif ON ou inactif OFF ZONE 2 OFF Chauffage de la zone 2 actif ON ou inactif OFF SENSOR 1 C Sonde 1 sonde chauff e temp rature du centre S applique uniquement quand une sonde...

Страница 25: ...marrer le chauffage forc Le contr leur ETO2 fournira la chaleur pour la p riode de post chauffage qui est pr programm voir POST CHAUFFAGE 1 et 2 Ici vous pouvez choisir l affichage de la temp rature...

Страница 26: ...la sonde ETOG 55 la temp rature affich e sur l cran de l ETO2 est toujours celle du centre de la sonde Pour la calibration veuillez vous r f rer CALIBRATION D OFFSET La temp rature ext rieure peut tr...

Страница 27: ...ne 1202 Le contr leur retournera alors au menu STARTUP d marrage voir STARTUP d marrage S lectionnez cette option et appuyez sur OK pour retourner au menu principal RED MARRAGE Apr s un changement des...

Страница 28: ...t faites correctement et que tous les c bles sont attach s sur les supports Pour des r ponses aux questions fr quentes FAQ visitez notre site www ojelectronics com support FAQ Snowmelting La glace nei...

Страница 29: ...Si le bouton d alarme rouge clignote un des d fauts suivants est survenu Le message pertinent sera affich dans le menu ALARM alarme RETURN TEMP LOW La temp rature de l eau dans la conduite de retour...

Страница 30: ...L ON SENSITIVITY NORM LANGUAGE ENGLISH FACTORY RESET REINSTALL EXIT OPERATION ZONE 1 HEAT OFF ZONE 2 HEAT OFF AFTERRUN 1 0 00 AFTERRUN 2 0 00 STANDBY OFF SHOW INFO APP E 1 ZONE SW VERSION 1 13 SENSOR...

Страница 31: ...g 1 Installation of ETOG ground sensor BR978A31a Fig 2 Installation of ETOR gutter sensor and ETF outdoor sensor BR978A12a Fig 3 1 zone electric heating with ETOG sensor BR978A23a Fig 4 1 zone electri...

Страница 32: ...cs A S 31 Type ETO2 Fig 5 2 zone electric heating roof ground BR978A25a BR978A05c 2010 OJ Electronics A S Fig 6 ETOG connection BR978A05c Fig 7 ETOR connection BR978A06c Fig 8 Heating cable connection...

Страница 33: ...nnection Y BR978A28a BR978A04a ETF 522 Hot water Optional Main Pump 3 way valve Circulation Pump Return sensor Supply sensor Optional air sensor Ground sensor ETF 522 Fig 11 1 zone hydronic heating co...

Страница 34: ...Type ETO2 Fig 13 Hydronic mixing valve connection Fig 14 Hydronic pump connection BR978A29a BR978A20a Fig 12 1 or 2 zone hydronic heating control simple same application setup as 1 or 2 zone electric...

Страница 35: ...2013 OJ Electronics A S 34 Type ETO2 FORCED CONTROL HEAT Fig 15 Connections for remote control of standby and forced heat BR978A21a...

Страница 36: ...2013 OJ Electronics A S 35 Type ETO2 Fig 16 ETO2 controller terminal overview BR978A03h...

Страница 37: ...ONICS A S Stenager 13B DK 6400 S nderborg Tel 45 73 12 13 14 Fax 45 73 12 13 13 oj ojelectronics com www ojelectronics com The trademark is registered and belongs to OJ Electronics A S 2013 OJ Electro...

Отзывы: