![Oilon GP-600 M Скачать руководство пользователя страница 102](http://html1.mh-extra.com/html/oilon/gp-600-m/gp-600-m_operation-and-maintenance-manual_4505353102.webp)
Servomotor of air damper
D031517 ver. 1
Pos.
Description
Pos.
Description
1
Servomotor
4
Shaft coupling aligning screw
2
Servomotor bracket
5
Shaft coupling clamping screw
3
Shaft coupling
6
Servomotor fixing screw
1. Turn off the burner power supply.
2. Disconnect the cables.
3. Loosen the shaft coupling clamping screw and aligning screw; shaft coupling is left
on air damper axle.
4. Remove the servomotor fixing screws and take out the servomotor.
5. Connect a new servomotor to the shaft coupling.
6. Make sure that the shaft coupling aligning screw is aligned with the servomotor axle
plane.
7. Make sure that the clamping screw of the shaft coupling is securely fastened.
8. Mount the new servomotor.
9. Tighten the servomotor fixing screws.
10. Connect the cables according to the instructions.
6.7 Fault and lockout history
Reading fault and lockout history from display menu
The active burner control fault status is shown on the display.
Fault and lockout history can be accessed from the display menu.
100 (111)