6.3 Performance data
To view performance data in other conditions, please use the Oilon
Selection Tool (www.oilon.com).
Design conditions of condenser and brine circuits
EN 14511.
Brine 0 °C / –3 °C and water 30 °C / 35 °C (B0/W35)
MODEL / RATED OUTPUT (kW), 3~ 400 V, 50 Hz, PE
6
8
10
13
17
21
Heating capacity
kW
5.6
7.4
10.0 12.7 17.0 21.1
Cooling capacity
kW
4.4
5.8
8.0
10.2 13.5 16.9
Coefficient of performance (COP)
-
4.4
4.6
4.8
4.8
4.7
4.8
Compressor electric power (active power)
kW
1.3
1.6
2.1
2.7
3.6
4.4
Electric current taken by the compressor
A
2.6
3.2
4.0
5.4
6.9
8.1
Brine 0 °C / –3 °C and water 47 °C / 55 °C (B0/W55)
MODEL / RATED OUTPUT (kW), 3~ 400 V, 50 Hz, PE
6
8
10
13
17
21
Heating capacity
kW
5.1
6.8
9.1
11.7 15.4 19.1
Cooling capacity
kW
3.3
4.4
6.1
7.8
10.4 13.0
Coefficient of performance (COP)
-
2.7
2.8
2.9
2.9
2.9
3.0
Compressor electric power (active power)
kW
1.9
2.5
3.2
4.1
5.4
6.4
Electric current taken by the compressor
A
3.4
4.3
5.4
6.9
9.1
10.6
Brine 0 °C / –3 °C and water 55 °C / 65 °C (B0/W65)
MODEL / RATED OUTPUT (kW), 3~ 400 V, 50 Hz, PE
6
8
10
13
17
21
Heating capacity
kW
4.9
6.5
8.7
11.2 14.8 18.1
Cooling capacity
kW
2.7
3.6
5.0
6.3
8.6
10.8
Coefficient of performance (COP)
-
2.1
2.2
2.3
2.2
2.3
2.4
Compressor electric power (active power)
kW
2.3
3.0
3.9
5.1
6.5
7.7
Electric current taken by the compressor
A
3.9
5.0
6.1
8.1
10.7 12.4
SCOP and SPF value
MODEL / RATED OUTPUT (kW), 3~ 400 V, 50 Hz, PE
6
8
10
13
17
21
Low temperature application, cold climate,
brine 0 °C, flow water upper limit 35 °C (floor heating)
SCOP (EN 14825)
SPF value (National Building Code of Finland)
5.1
5.6
5.6
5.6
5.5
5.6
High temperature application, cold climate,
brine 0 °C, flow water upper limit 55 °C (radiator
heating)
SCOP (EN 14825)
SPF value (National Building Code of Finland)
3.9
4.0
4.2
4.2
4.1
4.2
50 (59)