background image

Installation & Operation Manual                                                                                              Merlin 1000V+ 

 

 

 

 Rev: 04    08-22

 

9

 

 

Switch Settings 

 Auto RST (Panel Auto Reset) 

 

There are various dipswitches on the front circuit board that can be adjusted to configure your system as 

per the following. There is a switch located on the circuit board labelled [AUTO RST].

 

 

 

OFF 

When power is restored after the power cut/ loss, the panel must be restarted manually. (Default) 

ON 

This will instruct the system to restart automatically when power is restored after power cut/loss. 

 

Switch Settings 

 Pressure (Gas Pressure Threshold Configuration) 

 

There is a dipswitch located on the circuit board labelled [Pressure].  
The gas supply will be turned off if pressure will drop below threshold value continuously for 10 secs.  
 

OFF 

Low pressure threshold is set to 1.2 kPa. (Default) 

ON 

Low pressure threshold is set to 0.5 kPa. 

 

Switch Settings 

 EM SEL (Fan Switch Configuration) 

 

This option is not available if a fan switch is not installed! 
 

A fan switch (Merlin FS1 or FS2 - sold separately) provides the facility to turn on fan(s) when the 
 panel is switched on and removes power to fan(s) when the switched off. 
 

 

OFF 

Instructs the system to shut down fan(s) and gas upon activation of emergency shut off button(s). (Default) 

ON 

Instructs the system to leave the fans on and shut off the gas supply only upon activation of emergency shut 
off button(s). 

 

Switch Settings 

 Fill & Prove Time (Gas Proving Setting) 

 

Once the settings have been changed - remove power for 10 seconds. 

 

FILL TIME:

 

Amount of time the gas valve opens to fill the gas line on power up or reset.

 

PROVE TIME:

 

Amount of time the system tests the gas line for leaks on power up or reset.

 

 

FILL TIME 

PROVE TIME 

OFF 

5 Seconds (Default) 

OFF 

30 Seconds (Default) 

ON 

10 Seconds 

ON 

50 Seconds 

 
 
 
 
 

Содержание Merlin 1000V+

Страница 1: ...lation Controller with Ventilation Interlocking Installation Operation Maintenance Please read this manual carefully and retain for future use For specific requirements that may deviate from the infor...

Страница 2: ...anel Auto Reset 9 Switch Settings Pressure Gas Pressure Threshold Configuration 9 Switch Settings EM SEL Fan Switch Configuration 9 Switch Settings Fill Prove Time Gas Proving Setting 9 Switch Setting...

Страница 3: ...nty extends to the original consumer purchaser of the product only Warranty disclaimers Any implied warranties arising out of this sale including but not limited to the implied warranties of descripti...

Страница 4: ...h will automatically shut off the gas solenoid valve at the end of a specific time this time can be adjusted to 2 5 8 hours or can be overridden if required Mounting Cabling If mounting direct to wall...

Страница 5: ...d valve which can shut the gas supply on alarm status Refer to your valve manual for more information and wiring ELECTRIC CONTACTOR 240VAC electrical power supplied from the ELECTRIC CONTACTOR connect...

Страница 6: ...5 or 1 2 kPa the gas valve will close See section Switch Settings for Pressure options EM REMOTE FIRE PANEL Connections for remote emergency shut off buttons or integrated with a fire alarm to close t...

Страница 7: ...Connecting a Merlin Gas Detector X Connecting a Merlin CO2X FAN SWITCHES This terminal switches when the key is turned on and off This can be connected to a fan switch supplied separately which can pr...

Страница 8: ...erminal is linked out as a factory setting Wiring to external air pressure switches or current monitors should made using a two core cable This is a volt free connection The example is monitoring two...

Страница 9: ...1 2 kPa Default ON Low pressure threshold is set to 0 5 kPa Switch Settings EM SEL Fan Switch Configuration This option is not available if a fan switch is not installed A fan switch Merlin FS1 or FS2...

Страница 10: ...nfigured to select the required timeout shut down period TIME 1 TIME 2 Timeout Period OFF OFF 2 Hours Default ON OFF 4 Hours OFF ON 8 Hours ON ON Disabled Automatic System Shutdown Selectable Electric...

Страница 11: ...est Fail Under normal working conditions this LED is off When the panel detects a gas leak on start up the LED will illuminate AMBER Gas valve will remain closed OFF OK ON gas proving failed Pressure...

Страница 12: ...unit to a known concentration of the target gas that usually exceeds the highest alarm point If the detector goes into alarm and all signals outputs activate then the system is working If the system...

Страница 13: ...Installation Operation Manual Merlin 1000V Rev 04 08 22 13 Page intentionally left blank...

Страница 14: ...Installation Operation Manual Merlin 1000V Rev 04 08 22 14 Page intentionally left blank...

Страница 15: ...Overvoltage Category II Pollution Degree 2 Equipment Class 2 Environmental Ingress Protection Not Formally Evaluated Operating 10 50 C 14 122 F 30 80 RH non condensing Storage 25 50 C 13 122F up to 9...

Страница 16: ...ensure the equipment performs as intended and is free from any unforeseen damage caused by transit installation Every effort is made to ensure the accuracy of this document however OGS can assume no r...

Отзывы: