Installation & Operation Manual Merlin 1000V+
Rev: 04 08-22
10
Switch Settings
–
Time 1 & 2 (Automatic System Timeout Period)
Upon timeout the gas supply will be turned off.
There are two dipswitches [Time 1 & Time 2].
The system has an auto-shut down feature after a selected time. These can be configured to select the
required timeout/ shut-down period.
TIME 1
TIME 2
Timeout Period
OFF
OFF
2 Hours (Default)
ON
OFF
4 Hours
OFF
ON
8 Hours
ON
ON
Disabled
Automatic System Shutdown
–
Selectable Electrics
There is a switch located on the circuit board labelled [ELECTR]. This is
factory set to ‘Off’.
Upon installation, it can each
be switched ‘On’
- This will instruct the system to also turn off Electrical
supply when performing auto-shut down/ timeout or in the event of an emergency shutdown.