26
10.4.2.
Parameters and settings
Main menu
View with deactivated network
View with activated network
When the network is activated, the parameters not shown are configured via the network.
menu
description
basic setting
"raw water"
Enter the raw water hardness in
Range from 70… 1070 ppm
in steps of 20 ppm
180 ppm
"hardness limit"
Enter the hardness limit in
Range from 1… 20 ppm
in steps of 1 ppm
2 ppm
"interval"*
Enter the pause between two
measurements in the pure measurement
modes in the range of 0… 60 minutes
in steps of 1 minute
5 minutes
see chapter
"operating mode"
"alarm delay"**
Delay of the alarm in the
range of 1 ... 30 minutes
in steps of 1 minute
10 minutes
"measure"
Selection of the unit of measurement
between °dH, mmol / l, °f or ppm
°dH
"language"
Choice of language between
German and English
German
"calibration"**
Performing a
complete functional test
(automatic restart)
see
chapter "service"
"test 4..20mA"
Service to test the
4 ... 20 mA current loop
see
chapter "service"
"date/time"
Check date and time and
update if necessary
with
commissioning
"network setup"**
Calling up the submenu with
the network setup
see chapter
"network setup"
* If the interval is set to 0 minutes, measurements are volume-controlled via a water meter or
a release contact.
** The menu items marked in this way are password protected.