in accord with the device that is connected to the serial port.
Stop bit
:
You can choose stop bit 1 or stop bits 2. Default is stop bit 1. Please keep this
parameter in accord with the device that is connected to the serial port.
Receive character interval
:
When receiving packets Frame interval detection time can be chose from 1.5t to 200t.
Default is 3.5t. In general, you don't have to change this parameter.
Slave response delay
:
The gateway acts as a Modbus RTU/ASCII slave, from the time it receives a message
from the master to when it sends a reply. This parameter relates to the performance of the
master.
Figure 3.19 Set the corresponding serial port to slave mode
4.Configure the Ethernet parameters of the gateway by the "Ethernet
Configuration" on the left of the software.
Some of the parameters are as follows
:
Modbus gateway IP
:
The device's own IP address;
Subnet mask
:
Subnet mask of the device;
LAN gateway IP
:
Gateway IP address of the network where the device resides;
Modbus-TCP data communication port
:
Generally 502
;
Configure the port
: The configuration software downloads the configuration to the